Instruction Data 374-DREM Elkay easyDALi Remote Control Installer Instructions Features The easyDALI Remote Control consists of eight soft touch Dual purpose DALI Remote Control buttons to control the Elkay easyDALi PIR (374-CMPIRDALI) For use with Elkay easyDALi system It can program basic installation and commissioning User mode for day to day control functionality and has one hidden button that changes the Installer mode for installation set up remote control from user mode to Installer Mode. Installer Mode is detailed below but for End User Modes see separate Elkay easyDALi Remote Control Instructions must be read in End User instructions. conjunction with Elkay easyDAli PIR 374-CMPIRDALI Instructions in order to enable all features of the PIR. Installer Modes- How to program your easyDALi system Remote Control Rear View In Installer mode it is possible to control the timing options and also select Room and Corridor Options Open battery cover at rear and remove paper tab from Small Hole battery area to enable the remote (Hidden You must turn lights OFF with the remote first to operate Installer Button) and program in this mode To begin installer mode, remove battery cover at rear and place pin in hole and press once. Once feed back light goes RED you are in Installer Mode Installer Mode information should never be given to End users of the system Installer mode only A. Feedback LED - E. Override ON/OFF Button continuous RED in Installer Option B. SET Button For Walk test D. Minimum Arc Power C. Mode Options Up and Adjustment Mode Options DOWN Sets the minimum level the Setting room timing options harvester will not go below and Corridor timing options as per Table 1 1. Add group to pre- addressed luminaires 4. Reset to Manual controls 3. Update all discovered 2. Find pre-addressed luminaires of the current group with 16 pre-set levels luminaires or address new uncommitted luminaires as scenes. 16 Green flashes per ballast then a blue flash to indicate completeFitting and operation instructions A. Feedback LED - Continuous RED light for 3 minutes (after last button push). It will then revert back to End User mode. B. Set Button - Initiates Walk Test only in Installer Mode. Walk test can be used to test and setup the Elkay easyDALi PIR sensitivity by moving in & out of the PIRs detection range. The signal LED on the PIR indicates presence by flashing blue and can be used as a basic walk test. During walk test detection the luminaires will be illuminated to full brightness then after a short delay with no presence detection the luminaires will dim but not go off. (See Walk Test). C. Mode Up and Mode Down Setting Timing Room Options and Timing Corridor Options The product is pre-set to a factory default Room option 20 minutes on Dim to Min Level 10 minutes Off To set the Room, Corridor and Timing Options a) Open battery cover at rear and remove paper tab from battery area to enable the remote. b) You must turn lights OFF with the remote first to operate and program in this mode. To do this, point the remote control at the Elkay easyDALi PIR & press the override off button. While in override off the Elkay easyDALi PIR LED flashes white. c) To begin installer mode, remove battery cover at rear and place pin in hole and press once. Once feed back light goes RED you have initiated the Installation Option on the remote. d) You will automatically be in the DEFAULT mode of Room Mode 6, which gives 20 minutes ON with 10 minutes dimmed and then switches off (if no presence detected) This is highlighted in Table 1. e) By pressing the MODE button + UP and DOWN you will scroll through the room and corridor modes. When you push the button UP or DOWN you should press once only and observe and count the coloured flashes on the PIR. The number and colour of flashes corresponds to the Room Timing or the Corridor Timing Options shown in Table 1. Corridor Options flash RED on the PIR and Room Modes flash GREEN on the PIR. For example, press the mode + button once and the PIR will flash GREEN four times indicating it is now in Room Option 5. To go back to the DEFAULT setting press the mode - button once and the PIR will flash GREEN 3 times returning the PIR to the default setting. Scrolling up or down one press at a time moves you through the options in Table 1. TABLE 1 Timing Options selectable in Installer Mode from the Remote Control Corridor Option ON DIM OFF Number of PIR Colour Flashes Mode UP and DOWN 1 30min Yes 10% No 2 20min Yes 10% No 3 10min Yes 10% No 4 5min Yes 10% No Room Option ON DIM OFF Number of PIR Colour Flashes Mode UP and DOWN 5 30min 15min Yes 6 20min 10min Yes PRE-SET FACTORY DEFAULT 7 10min 5min Yes 8 5min 5min Yes Corridor Option When selecting Corridor Option lights never go off, they will just dim to the selected minimum arc power. In Corridor Option all end user remote control functions are disabled except override off. In corridor option the luminaires will be illuminated to full brightness while presence is detected. When presence is no longer detected the luminaires will be dimmed after a preset time. The luminaires will remain dimmed until presence is again detected. Corridor Shutdown Option For Facility managers, caretakers and building maintenance teams, there is the ability to turn off corridor mode completely by pressing the on/off button in Corridor Option which will dim lights to 10% for 10 minutes and then OFF. This may be useful for factory shutdowns or when office space will be empty for a long period.