TOPFLEX -EMV-UV-2YSLCYK-J for power supply connections to frequency converters, double screened, 0,6/1kV, meter marking Technical data Cable structure Properties Special motor power supply cable for Bare copper, fine wire conductor to Behavior in fire: Test according to frequency converters adapted to DIN VDE 0295 cl. 5, BS 6360 cl. 5 or VDE 0482-332-1-2, DIN EN 60332-1-2/ DIN VDE 0250 IEC 60228 cl. 5 IEC 60332-1 (equivalent DIN VDE 0472 Temperature range Polyethylene (PE) core insulation part 804 test method B) flexing -5 C to +70 C Core colours: green-yellow, brown, black, Low mutual capacitance, to DIN VDE 0472 fixed installation -40 C to +70 C grey part 504, test method B Nominal voltage U0/U 600/1000 V Cores stranded in concentric layers Features PE-insulation secures a lower dielectric loss, double potential strength, Max. operating voltage 1. screening with special aluminium film A.C. and 3-phase 700/1200 V high longevity and low screen-interference 2. screening with copper braiding, tinned DC operation 900/1800 V currents copper, coverage approx. 80% Low mutual capacitance Test voltage 2500 V Special PVC outer sheath, black (RAL 9005) Meets EMC requirements according to Insulation resistance with meter marking, change-over in 2011 min. 200 MOhm x km EN 55011 and DIN VDE 0875 part 11 Low coupling resistance for high Coupling resistance electromagnetic compatibility according to different cross-sections Note UV-resitant max. 250 Ohm/km The current carrying capacity for permanent Outdoor application, possible for Mutual capacitance operation at ambient temperature of according to different cross-sections installation in underground at 4G16mm 30 C. For deviating ambient temperatures core/core 70 to 250 nF/km This screened motor supply cable with low the conversion factors should be used and mutual capacitance of the single cores core/screen 110 to 410 nF/km for further see the indication in DIN VDE 0298 Minimum bending radius because of the special PE core insulation part 4 and low screen capacitance enable a fixed installation for outer : low-loss transmission of the power up to 12 mm: approx. 5x cable >12 to 20 mm: approx. 7,5x cable compared to PVC-sheathed connecting cables >20 mm: approx. 10x cable free-movement for outer : Due to the optimal screening an interference-free operation of frequency up to 12 mm: approx. 10x cable converters is obtained >12 to 20 mm: approx. 15x cable >20 mm: approx. 20x cable The materials used in manufacture are cadmium-free and contain no silicone and Radiation-resistance 6 up to 80x10 cJ/kg (up to 80 Mrad) free from substances harmful to the wetting properties of lacquers Application This TOPFLEX -EMC-2YSLCYK-J motor power supply cable for the frequency converters assures electromagnetic compatibility in plants and buildings, facilities with units and operating equipment where the fields of electromagnetic interference might cause adverse effects on the surroundings. As a supply and connecting cable for medium mechanical stresses in fixed installations and forced movements in dry, moist and wet environments and for outdoor applications, possible for installation in underground at 4G16 mm. Used in the automotive and food industries, environmental technology, packaging industry, machine tools. Handling equipment, for SIMOVERT drives, they are particularly suitable for use with industrial pumps, ventilators, conveyor belts and air-conditioning installations and similar applications. Installation in hazardous areas. EMC = Electromagnetic compatibility The screen must be connected at both ends and ensure lare-area contact over the entire cable circumference for compliance with the functional interference requirements of EN 55011. = The product is conformed with the EC Low-Voltage Directive 2006/95/EG. Part no. No.cores x Outer Mutual capacitance Coupling resistance Power ratings **) Cop. Weight AWG-No. cross-sec. approx. mm Core / Core Core / Screen at 1 MHz at 30 MHz with 3 loaded cores weight approx. mm approx. nF / approx. nF / Ohm/km Ohm/km in Amperes kg / km kg / km km km 22234 4 G 1,5 10,3 70 110 18 95,0 230,0 16 22235 4 G 2,5 12,3 80 130 18 210 26 150,0 300,0 14 22236 4 G 4 13,9 90 150 11 210 34 235,0 485,0 12 22237 4 G 6 15,3 90 150 6 150 44 320,0 630,0 10 22238 4 G 10 19,5 120 200 7 180 61 533,0 860,0 8 22239 4 G 16 23,3 140 230 9 190 82 789,0 1290,0 6 Continuation D 19 TOPFLEX -EMV-UV-2YSLCYK-J for power supply connections to frequency converters, double screened, 0,6/1kV, meter marking Part no. No.cores x Outer Mutual capacitance Coupling resistance Power ratings **) Cop. Weight AWG-No. cross-sec. approx. mm Core / Core Core / Screen at 1 MHz at 30 MHz with 3 loaded cores weight approx. mm approx. nF / approx. nF / Ohm/km Ohm/km in Amperes kg / km kg / km km km 22240 4 G 25 27,4 120 210 4 95 108 1236,0 1860,0 4 22241 4 G 35 30,3 150 260 3 85 135 1662,0 2610,0 2 22242 4 G 50 35,5 190 320 2 40 168 2345,0 2950,0 1 22243 4 G 70 40,2 190 320 2 45 207 3196,0 3950,0 2/0 22244 4 G 95 44,5 250 410 1 50 250 4316,0 5300,0 3/0 22245 4 G 120 50,3 292 5435,0 6600,0 4/0 22246 4 G 150 56,1 335 6394,0 7040,0 300 kcmil 22247 4 G 185 58,0 382 7639,0 8380,0 350 kcmil D Dimensions and specifications may be changed without prior notice. (RD01) Tools Cable shears Box spanners Strippers Crimping tools Pliers Skinning knife You can nd tools in our catalogue Cable Accessories. Request it now at www.helukabel.de D 20