GE1A Timers GE1A Series ON Delay Timers GE1A Single Function Key features: DPDT or SPDT + instantaneous SPDT 8-pin, octal base Repeat error 0.2% maximum Large, clear knob for easy setting Instant monitoring of operational status by LED indicators UL, c-UL Listed File No. E55996 Specifications 24V AC/DC Rated Operating Voltage 100 to 120V AC 220 to 240V AC AC: 85 to 110% Voltage Tolerance DC: 90 to 110% 240V AC/5A Contact Rating 24V DC/5A Contact Form DPDT or SPDT+ instantaneous SPDT Repeat Error 0.2% 10msec maximum Voltage Error 0.5% 10msec maximum Temperature Error 3% maximum Setting Error 10% maximum Reset Time 0.1 sec maximum Insulation Resistance 100M minimum (500V DC megger) Between power and output terminals: 1,500V AC, 1 minute Dielectric Strength Between contact circuits: 750V AC, 1 minute Damage limits: Amplitude 0.75mm, 10 to 55 Hz Vibration Resistance Operating extremes: Amplitude 0.5mm, 10 to 55 Hz 2 Shock Resistance Damage limits: 500m/s (Approx. 50G) 24V AC type: 1.6 VA 24V DC type: 1.0W GE1A-B 110V AC type: 3.8 VA 220V AC type: 7.7 VA Power Consumption 24V AC type: 2.0 VA 24V DC type: 0.8W GE1A-C 110V AC type: 3.5 VA 220V AC type: 8.0 VA Electrical Life 100,000 operations minimum (at full rated load) Mechanical Life 10,000,000 operations minimum Operating Temperature 10 to +55C (without freezing) Operating Humidity 35 to 85% RH (without freezing) www.IDEC.com 866 Circuit Breakers Terminal Blocks Contactors Timers Relays & Sockets Signaling Lights Switches & Pilot LightsSwitches & Pilot Lights Signaling Lights Relays & Sockets Timers Contactors Terminal Blocks Circuit Breakers GE1A Timers Part Numbering List Mode of Operation Contact Output Rated Voltage Time Range Complete Part Number 220-240V AC GE1A-B10HA220 110-120V AC 0.1s - 10h GE1A-B10HA110 24V AC/DC GE1A-B10HAD24 Delayed SPDT + Instantaneous SPDT 220-240V AC GE1A-B30HA220 110-120V AC 0.3s - 30h GE1A-B30HA110 24V AC/DC GE1A-B30HAD24 24V DC/120V AC, 5A ON-Delay 240V AC, 5A 220-240V AC GE1A-C10HA220 110-120V AC 0.1s - 10h GE1A-C10HA110 24V AC/DC GE1A-C10HAD24 Delayed DPDT 220-240V AC GE1A-C30HA220 110-120V AC 0.3s - 30h GE1A-C30HA110 24V AC/DC GE1A-C30HAD24 Timing Diagrams/Schematics GE1A-B GE1A-C Delayed SPDT + Instantaneous SPDT Delayed DPDT m n m n l o l o Operation Mode Selection k p k p (-) (+) (-) (+) j q j q POWER POWER Item Terminal Number Operation Item Terminal Number Operation Set Time Set Time ON-Delay 1 Power 2 - 7 (8p) Power 2 - 7 (8p) 5 - 8 (8p) (NC) 5 - 8 (8p) (NC) MODE Delayed Delayed Contact Contact 6 - 8 (8p) (NO) 6 - 8 (8p) (NO) A 1 - 4 (NC) POWER Instantaneous Indicator Contact 1 - 3 (NO) OUT POWER Indicator OUT Note: Terminals 1, 3, and 4 are for the instantaneous contact 800-262-IDEC (4332) USA & Canada 867