Axial Lead and Cartridge Fuses
Designed to IEC Standard
V
DE
5 x 20 mm Time Lag Fuse (Slo-Blo Fuse) 218/213 Series
Designed to International (IEC) Standards for use globally.
Meets the IEC 60127-2, Sheet 3 specification for Time Lag Fuses.
Available in Cartridge and Axial Lead Form.
Available in ratings of 0.032 to 10 amperes.
ELECTRICAL CHARACTERISTICS:
% of Ampere Ampere Opening
Rating Rating Time
.032.100 60 minutes, Minimum
150%
.1256.3 60 minutes, Minimum
.032.100 2 minutes, Maximum
210%
.1256.3 2 minutes, Maximum
.032.100 0.2 sec., Min.; 10 sec. Max.
275%
213 000 213 000 XE
.1256.3 0.6 sec., Min.; 10 sec. Max.
223 000
.032.100 .04 sec., Min.; 3 sec. Max.
400%
218 000 218 000 XE
.1256.3 .15 sec., Min.; 3 sec. Max.
228 000
.032.100 .01 sec., Min.; 0.3 sec. Max.
.635
1000%
(.025")
.1256.3 0.02 sec., Min.; 0.3 sec. Max.
AGENCY APPROVALS: Sheet III IEC 60127-2:* SEMKO, VDE
20
approved thru 6.3 amps. BSI approved 0.08-6.3 amps. Recognized under 40
5 22.5 MAX
5.25
(.787")
(1.58")
(.197") (.886)
the Components Program of Underwriters Laboratories and recognized (.207")
by CSA. 0213 series METI approved 1-5A.
Average Time Current Curves for 218/228
VOLTAGE RATING: 250 VAC
INTERRUPTING RATINGS: 35 amperes or 10 x rated current;
whichever is greater.
ORDERING INFORMATION:
100
For axial leaded change 218 to 228 and 213 to 223.
218/228 213/223 Surge Withstand
Cartridge Nominal Nominal Cartridge Nominal Nominal
2
Ampere Catalog Resistance Melting I t Catalog Resistance Melting
2 2 2
Rating Number Cold Ohmns A Sec. Number Cold Ohms I t A Sec.
10
.032 218.032 58.45 0.00305
8
.040 218.040 35.70 0.0055
.050 218.050 23.30 0.0071
.063 218.063 18.1 0.012
.080 218.080 12.6 0.0265
.100 218.100 8.95 0.0495 1
.125 218.125 4.41 0.150
.160 218.160 2.44 0.225
.200 218.200 1.60 0.350 0213.200 1.60 0.350
.250 218.250 1.05 0.555 0213.250 1.05 0.555
.315 218.315 0.848 1.14 0213.315 0.848 1.14
0.1
.400 218.400 0.535 1.35 0213.400 0.535 1.35
.500 218.500 0.370 2.90 0213.500 0.370 2.90
.630 218.630 0.275 4.80 0213.630 0.275 4.80
.800 218.800 0.073 1.99 0213.800 0.165 9.42
1 218 001 0.055 3.33 0213 001. 0.117 19.20
1.25 218 1.25 0.042 5.80 0213 1.25 0.081 27.15
0.01
1.6 218 01.6 0.032 10.61 0213 01.6 0.055 44.2
2 218 002 0.029 14.80 0213 002. 0.044 92.7
2.5 218 02.5 0.022 23.85 0213 02.5 0.030 138.0
3.15 218 3.15 0.017 39.20 0213 3.15 0.022 226.5
4 218 004 0.013 70.95 0213 004. 0.017 202
5 218 005 0.010 114.0 0213 005. 0.011 314
0.001
6.3 218 06.3 0.0075 204.0 0213 06.3 0.008 600 0.05 0.1 1 10 100 500
CURRENT IN AMPERES
8 218 008 0.0059 350.5
10 218 010 0.0045 583.0
15 218 015 0.0030 1441.0
Please contact Littelfuse for Average Time Current Curve
* IEC Standards for 5 x 20 fuses do not include ratings above 6.3A, but are
under consideration.
for 213/223 surge withstand.
1
228 and 223 Series are used for North American ordering.
295
www.littelfuse.com
TIME IN SECONDS
.032A
.040A
.050A
.063A
.080A
.100A
.125A
.160A
.200A
.250A
.315A
.400A
.500A
.630A
.800A
1A
1.25A
1.6A
2A
2.5A
3.15A
4A
5A
6.3A
8A
10A
15A
AXIAL LEAD AND
CARTRIDGE FUSESX-ON Electronics
Largest Supplier of Electrical and Electronic Components
Click to view similar products for Littelfuse manufacturer:
Other Similar products are found below :
V130LA10A 1SMB33AT3G 1SMA24AT3G 0362030.V 59022-3-S-02-F 46213150000 59022-3-T-02-F 59022-3-U-02-F MDRR-DT-30-
35-F SK225RDTP GTCA28-231M-R05 SMBJ5.0 00970019XP LX5090 0217.500HXP 02181.25TXP 0224006.HXUP 740GN 815.650
FLA2.25 FLSR400 FLSR600 900-1535-012RN 901-134 970699013 971-670A-92WCN 153.5631.5601 155100 157.5701.6101
1.5KE110A-B 1.5KE220A 1.5SMC150CA BLF006 BLF008 JLLS-250 235.200 901-152C-042RN 920-401X-330BN 282007
LFC600602CID LFR600303CID LJCA030.X SE-GRM024 SE-TA6ASF-WL 2N6509G 980-788A-070 FLNR100 FLNR400 FLSR200
211RT