60W Single Output with Battery Charger(UPS Function) PSC-60 series %%& ( Bauart gepruft Sicherheit egelma ge od os be wac g www.tuv.com ID 2000000000 SPECIFICATION 9% C 8. C 8. D D 8C 8C . . C C MODEL PSC-60A PSC-60B OUTPUT NUMBER CH1 CH2 CH1 CH2 DC VOLTAGE 13.8V 13.8V 27.6V 27.6V RATED CURRENT 2.8A 1.5A 1.4A 0.75A CURRENT RANGE 0 ~ 4.3A -------- 0 ~ 2.15A -------- RATED POWER 59.34W 59.34W RIPPLE & NOISE (max.) Note.2 120mVp-p -------- 240mVp-p -------- OUTPUT VOLTAGE ADJ. RANGE CH1: 12 ~ 15V CH1: 24 ~ 29V VOLTAGE TOLERANCE Note.3 1.0% -------- 1.0% -------- LINE REGULATION 0.5% -------- 0.5% -------- LOAD REGULATION 0.5% -------- 0.5% -------- SETUP, RISE TIME Note.4 800ms, 50ms/230VAC 1600ms, 50ms/115VAC at full load HOLD UP TIME (Typ.) 50ms/230VAC 10ms/115VAC at full load VOLTAGE RANGE 90 ~ 264VAC 127 ~ 370VDC FREQUENCY RANGE 47 ~ 63Hz 84% EFFICIENCY (Typ.) 84% INPUT AC CURRENT (Typ.) 1.6A/115VAC 1A/230VAC INRUSH CURRENT (Typ.) COLD START 30A/115VAC 60A/230VAC LEAKAGE CURRENT <1mA / 240VAC 105 ~ 150% rated output power OVERLOAD Protection type : Hiccup mode, recovers automatically after fault condition is removed CH1:14.49 ~ 18.63V CH1:28.98 ~ 37.26V PROTECTION OVER VOLTAGE Protection type : Hiccup mode, recovers automatically after fault condition is removed 10.50.5V 211V BATTERY CUT OFF TTL open collector output, ON : AC OK OFF : AC Fail Ice : max. 30mA 50VDC AC OK FUNCTION TTL open collector output, ON : Battery Low OFF : Battery OK Ice : max. 30mA 50VDC BATTERY LOW Battery low voltage : < 11V Battery low voltage : < 22V -20 ~ +70 (Refer toDerating Curv) WORKING TEMP. 20 ~ 90% RH non-condensing WORKING HUMIDITY -20 ~ +85, 10 ~ 95% RH ENVIRONMENT STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT 0.03%/ (0~50) on CH1 output VIBRATION 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes UL60950-1, TUV EN60950-1 approved SAFETY STANDARDS SAFETY & WITHSTAND VOLTAGE I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC EMC ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25/ 70% RH (Note 7) EMC EMISSION Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3 EMC IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, light industry level, criteria A MTBF 589.7K hrs min. MIL-HDBK-217F (25) PCB:101.6*50.8*29mm (L*W*H) Enclosed type:103.4*62*37mm (L*W*H) OTHERS DIMENSION PACKING PCB:0.13Kg 96pcs/13.5Kg/0.89CUFT Enclosed type:0.29Kg 45pcs/14Kg/0.67CUFT ) * + (,%- . (/ ) NOTE () 0 1 (% 23 (4 %) 1 56 ) ,) + . ) 5) 7 ) + * ) /) 2 8 2 .2 ( ) 9) 2 8 2 ) 6) + : ) < ,9 =,9 8 ) + : ) . > ) A ) B File Name:PSC-60-SPEC 2015-08-06103.4 2-M3 L=4 24.2 55 4.2 2-M3 12.7 2-M3 L=4 95 2-3.5 78 60W Single Output with Battery Charger(UPS Function) PSC-60 series MechanicalMechanical Specification Specification Unit:mmUnit:mm 101.6 Cover: 95.25 3.175 No.998A -T M2 HS2 FS1 AC FUSE SVR1 T2.5A/250V 3 1 2 2 1 3 CN1 4 5 6 CN2 M1 HS1 4-3.3 Mylar film )2 .2 ( ) ()2 ) ,) ) . . ( ) AC Input Connector (CN1) : JST B3P-VH or equivalent Pin No. Assignment Mating Housing Terminal L-Bracket: 1 AC/N No.998A -D JST VHR JST SVH-21T-P1.1 2 No Pin or equivalent or equivalent 3 AC/L DC Output Connector (CN2) : JST B6P-VH or equivalent Pin No. Assignment Pin No. Assignment Mating Housing Terminal 1 Bat. Low 4 Battery + JST VHR JST SVH-21T-P1.1 2 AC OK 5 DC Output + or equivalent or equivalent 36Battery - DC Output COM : Grounding Required Block Diagram AC OK ALARM Bat. Low CIRCUIT RECTIFIERS RECTIFIERS POWER +V EMI I/P & & SWITCHING FILTER -V FILTER FILTER Bat. + Bat. - DETECTION FG CIRCUIT Battery Charger O.L.P. CONTROL & O.V.P. Back Up Control File Name:PSC-60-SPEC 2015-08-06 30.85 62 50.8 3 max. 29 44.45 3.175 18 14.5 37