D1U86P-W-1600-12-HBxDC Series 86mm 1U Front End AC-DC Power Supply PRODUCT OVERVIEW The D1U86P-W-1600-12-HBxDC products are high efciency 1600 watt, power factor corrected front end supplies with a 12V main output and a 12V (30W) standby. They have current sharing and up to 8 supplies may be operated in parallel. The supplies may be hot plugged, they recover from over-temperature faults, and have logic and PMBus monitoring and control. Their low prole 1U package and >38.6W/cubic inch power density make them ideal for delivering reliable, efcient power to servers, workstations, storage systems and other 12V distributed power systems. NB: D1U86P-W-1600-12-HB3DC Model Shown ORDERING GUIDE FEATURES Power Output AC Line Main Standby Handle 1600W output power Part Number Airflow Output Output Colour (90-264V) (108-264V) (180-264V) 94% minimum efciency at 50% load Back to 12V main output D1U86P-W-1600-12-HB4DC Red Front 1200W 1350W 1600W 12V 12V 12V standby output of 30W Front to D1U86P-W-1600-12-HB3DC Blue 1U height: 3.4 x 7.78 x 1.59 Back 38.6 Watts per cubic inch density INPUT CHARACTERISTICS N+1 redundancy, including hot plugging (up to 8 Parameter Conditions Min. Nom. Max. Units in parallel) Input Voltage Operating Range 90 115/230 264 Vac Droop Current sharing both outputs Frequency 47 50/60 63 Hz Overvoltage, overcurrent, overtemperature Turn-on Voltage Ramp up 81 89 Vac Turn-off Voltage Ramp down 70.5 73 78 protection Maximum Input Current 1200W, 100Vac 14.1 Arms Internal cooling fan (variable speed) Inrush Current At 264Vac at 25C cold start 35 Apk Power Factor At 230Vac, half load 0.98 PMBus / IC interface monitoring and control 20% load 90 RoHS compliant Efficiency (230Vac) excluding fan 50% load 94 % load Two Year Warranty 100% load 91 OUTPUT VOLTAGE CHARACTERISTICS Output Parameter Conditions Min. Typ. Max. Units Voltage Voltage Set Point 50% load 12.17 12.2 12.23 Vdc Line and Load Regulation 11.4 12.6 Droop 3.10 mV/A www.murata-ps.com/en/3d/acdc.html 1 Ripple Voltage & Noise 20MHz Bandwidth 120 mV p-p www.murata-ps.com/en/3d/acdc.html 12V 2 Output Current (230 Vac) 0 133.4 A www.murata-ps.com/en/3d/acdc.html 2 0 112.5 A Output Current (120 Vac) www.murata-ps.com/en/3d/acdc.html 2 Output Current (100 Vac) 0 100.0 A www.murata-ps.com/en/3d/acdc.html Load Capacitance 10,000 F www.murata-ps.com/en/3d/acdc.html Voltage Set Point 50% load 11.97 12.0 12.02 Vdc 1 12VSB Ripple Voltage & Noise 20MHz Bandwidth 120 mV p-p Output Current 0 2.5 A Available now at: 1 Ripple and noise measured with a parallel combination of a 1.0F ceramic and 10F tantalum capacitor on each of the D1U86P-W-1600-12-HBxDC Series 86mm 1U Front End AC-DC Power Supply OUTPUT CHARACTERISTICS Parameter Conditions Min. Typ. Max. Units Output Rise Monotonicity No voltage excursion Startup Time AC ramp up 1.5 3 s 12V, 50% load step, 1.0As di/dt 600 Transient Response mV 12VSB, 50% load step,1.0As di/dt 600 3 Current sharing accuracy (up to 8 in parallel) At 100% load 5 % Hot Swap Transients All outputs remain in regulation 5 % Holdup Time At full load 12 ms 3 Load current of 100% applies to each power module max load connected in an N+1 conguration therefore the total load will be N x 100%. The share accuracy of 5% is a xed percentage irrespective of total loading and number of units connected in parallel. ENVIRONMENTAL CHARACTERISTICS Parameter Conditions Min. Typ. Max. Units Storage Temperature Range -40 85 C Operating Temperature Range 0 55 Operating Humidity Noncondensing 5 90 % Storage Humidity 5 95 Altitude (without derating at 45C) 3000 m Shock 30G non-operating Vibration 10-500Hz, 0.5G (non-operational) MTBF Per Telcordia SR-322 M1C1 40C 559K hrs Acoustic 65 dBA/ 1m CSA 60950-1-07+A1:2011 ANSI/UL 60950-1-2011, Second Edition Safety Approvals IEC 60950-1:2005 (2nd Edition) + A1:2009 EN 60950-1:2006 +A11+A1+A2 Input Fuse Power Supply has internal 16A/250V fast blow fuse on the AC line input Weight 2.33/1.06 lbs/Kg PROTECTION CHARACTERISTICS Output Parameter Conditions Min. Typ. Max. Units Voltage An OTP warning will be issued via the PMBus interface when the air inlet exceeds 65C however the power module shall not Overtemperature (intake) 65 shut down until critical internal hotspot C temperatures are exceeded. 13.2 14.4 Overvoltage Latching V Shutdown of the output followed by auto- Overcurrent at 220Vac recovery after one second. The output shall 140 153 12V attempt three such auto-recovery attempts and then enter a permanent latched state. A Recovery of the permanent latched state shall Overcurrent at 120Vac 118 129 require cycling of the incoming AC source or toggling of the PSON signal. Overvoltage Latching 13.2 14.4 V 12VSB Overcurrent Auto-recovery 2.75 3 A ISOLATION CHARACTERISTICS Parameter Conditions Min. Typ. Max. Units Input to Output - Reinforced 3000 Vrms Insulation Safety Rating / Test Voltage Input to Chassis - Basic 1500 Vrms Isolation Output to Chassis 500 Vdc Leakage Current 1.5mA at 264Vac, 50/60Hz www.murata-ps.com/support D1U86P-W-1600-12-HBXDC.A03 Page 2 of 7