Basic-type Digital Temperature Controller E5AN/E5EN (96 x 96 mm and 48 x 96 mm) CSM E5AN E5EN DS E 4 1 New 96 x 96-mm and 48 x 96-mm Basic Temperature Controllers with Enhanced Functions and Performance. Improved Indication Accuracy and Preventive Maintenance Function. Indication Accuracy Thermocouple input: 0.3% of PV (previous models: 0.5%) Pt input: 0.2% of PV (previous models: 0.5%) Analog input: 0.2% FS (previous models: 0.5%) A PV/SV-status display function can be set to automatically alternate between displaying the status of the Temperature Controller (auto/manual, RUN/STOP, and alarms) and the PV or SV. 96 96 mm 48 96 mm Preventive maintenance for relays in the Temperature Controller E5AN E5EN using a Control Output ON/OFF Counter. Three-level display that simultaneously displays the PV, SV, and Refer to Safety Precautions for E5 N/E5 N-H. MV. One-touch operation with PF Key that can be assigned to auto/ Refer to Operation for E5 N/E5 N-H for operating procedures. manual, RUN/STOP, or other functions. Main I/O Functions E5AN E5EN 3-level Display * Simultaneously displays set items, Event Inputs such as the PV, SV, and MV. * A 2-level display when shipped from the factory. A None 3-level display is activated if parameters are Two initialized. For details on the third display level, refer to the Users Manual, Basic Type (Cat. No. H156). Sensor Inputs 4-digit Display Universal thermocouple/Pt inputs Auto/manual switching (Models with temperature inputs) Temperature Controller Analog current/voltage inputs status display Auxiliary Outputs (Models with analog inputs) Simple program function Three Control Output 2 Control output ON/OFF Indication Accuracy count alarm Voltage output Thermocouple input: 0.3% of PV PV change rate alarm (for driving SSR) Pt input: 0.2% of PV Long-life relay Models also available with Analog input: 0.2% FS RS-485 or RS-232C output (hybrid) communications Sampling Period 250 ms Control Output 1 Relay output PF Key Voltage output (for driving SSR) Current output (Programmable function key) This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions and other information required for operation before attempting to use the product. E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User s Manual Basic Type (Cat. No. H156) E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers Communications Manual Basic Type (Cat. No. H158) 1E5AN/E5EN Lineup 3 auxiliary outputs 1 control output Temperature input 3 auxiliary outputs 2 control outputs E5AN/E5EN Terminal block Basic Type 1 control output 3 auxiliary outputs Analog input 2 control outputs 3 auxiliary outputs Note: Models with one control output or two control outputs can be used for heating/cooling control. Model Number Structure Model Number Legend Controllers Option Units E53- E5AN/E5EN- 3 M - -500-N 1 1 23 456 7 8 9 1. Control Output 1 1. Function R: Relay output EN01: RS-232C communications Q: Voltage output (for driving SSR) EN03: RS-485 communications C: Current output AKB: Event input 2. Auxiliary Outputs 3: Three outputs 3. Heater Burnout/SSR Failure, Control Output 2, or External Power Supply for ES1B Blank: None Q: Control output 2 (voltage output for driving SSR) Y: Long-life relay output (hybrid) H: Heater burnout/SSR failure/Heater overcurrent detection (CT1) HH: Heater burnout/SSR failure/Heater overcurrent detection (CT2) P: Power supply for sensor 4. Option M: Option Unit can be mounted. 5. Input Type T: Universal thermocouple/platinum resistance thermometer input L: Analog current/voltage input 6. Power Supply Voltage Blank: 100 to 240 VAC D: 24 VAC/VDC 7. Case Color Blank: Black W: Silver 8. Terminal Cover -500: With terminal cover 9. Version N: Available only to models released after January 2008. Note: Estimates can be provided for coatings and other specifications that are not given in the datasheet. Ask your OMRON representative for details. 2