Solid State Relay G3NA A Wide Range of Models with 5- to 40-A Output Currents and Up to 480-VAC/200-VDC Output Voltages All models feature the same compact dimensions to provide a uniform mounting pitch Built-in MOV effectively absorbs external surges Operation indicator (red LED) enables monitoring operation Protective cover for greater safety Standard models approved by UL/CSA AC and DC input versions available Ordering Information To Order: Select the part number and add the desired rated input voltage, (e.g., G3NA-240B-100 to 120 VAC). Isolation Zero cross Indicator Rated output load Rated input voltage Part number function (Applicable output load) Phototriac Yes Yes 5 A at 24 to 240 VAC* 5 to 24 VDC G3NA-205B Photocoupler (19 to 264 VAC) 100 to 120 VAC 200 to 240 VAC 10 A at 24 to 240 VAC* 5 to 24 VDC G3NA-210B (19 to 264 VAC) 100 to 120 VAC 200 to 240 VAC Photocoupler Yes Yes 10 A at 200 to 480 VAC* 5 to 24 VDC G3NA-410B (180 to 528 VAC) 100 to 240 VAC 10 A at 5 to 200 VDC* 5 to 24 VDC G3NA-D210B (4 to 220 VDC) 100 to 240 VAC Phototriac Yes 20 A at 24 to 240 VAC* 5 to 24 VDC G3NA-220B (19 to 264 VAC) 100 to 120 VAC 200 to 240 VAC Photocoupler Yes Yes 20 A at 200 to 480 VAC* 5 to 24 VDC G3NA-420B (180 to 528 VAC) 100 to 240 VAC Photocoupler Yes Yes 25 A at 24 to 240 VAC* 5 to 24 VDC G3NA-225B (19 to 264 VAC) 100 to 120 VAC 200 to 240 VAC 25 A at 200 to 480 VAC* 5 to 24 VDC G3NA-425B (180 to 528 VAC) 100 to 240 VAC Phototriac Yes Yes 40 A at 24 to 240 VAC* 5 to 24 VDC G3NA-240B (19 to 264 VAC) 100 to 120 VAC 200 to 240 VAC Photocoupler Yes Yes 40 A at 200 to 480 VAC* 5 to 24 VDC G3NA-440B (180 to 528 VAC) 100 to 240 VAC * Loss time increases under 75 VAC. NOTE: When ordering a TV-approved model, add -UTU to the model number as shown below: Example: G3NA-210B-UTUG3NA G3NA ACCESSORIES Heat Sinks Types Applicable solid-state relays Part number Standard mount G3NA-205B, G3NA-210B, G3NA-D210B, G3NA-220B, G3NA-410B, G3NA-420B Y92B-A100 G3NA-225B, G3NA-240B, G3NA-425B, G3NA-440B Y92B-A150N G3NA-440B Y92B-A250 Track mount G3NA-205B, G3NA-210B, G3NA-D210B, G3NA-410B Y92B-N50 G3NA-220B, G3NA-420B Y92B-N100 G3NA-225B, G3NA-240B, G3NA-425B, G3NA-440B Y92B-N150 Mounting Track and Accessories Description Part number Mounting bracket for G3NA-240B. Changes pitch to 56 mm (2.21 in.) from 47.5 mm (1.73 in.), R99-11 the same pitch as G3N-240B. DIN Rail Track, 50 cm (1.64 feet) length use with Y92B-N heat sinks PFP-50M DIN Rail Track, 1 m (3.28 feet) length use with Y92B-N heat sinks PFP-100M Spacer PFP-S End cap PFP-M Specifications INPUT RATINGS (Ambient temperature: 25C 77F ) Rated Operating Voltage Level Type voltage voltage range Impedance Must operate voltage Must release voltage G3NA-2 B 5 to 24 VDC 4 to 32 VDC 7 mA max. (see note 2) 4 VDC max. 1 VDC min. 100 to 120 VAC 75 to 132 VAC 36 k 20% 75 VAC, max. (see note 3) 20 VAC min. (see note 3) 200 to 240 VAC 150 to 264 VAC 72 k 20% 150 VAC max. (see note 3) 40 VAC min. (see note 3) G3NA-4 B 5 to 24 VDC 4 to 32 VDC 5 mA max. (see note 2) 4 VDC max. 1 VDC min. 100 to 240 VAC 75 to 132 VAC 72 k 20% 75 VAC max. 20 VAC min. G3NA-D210B 5 to 24 VDC 4 to 32 VDC 5 mA max. (see note 2) 4 VDC max. 1 VDC min. 100 to 240 VAC 75 to 132 VAC 72 k 20% 75 VAC max. 20 VAC min. Note: 1. The input impedance is measured at the maximum value of the rated supply voltage (for example, with the model rated at 100 to 120 VAC, the input impedance is measured at 120 VAC). 2. With constant current input circuit system. 3. Refer to theCharacteristic Dat for further details. OUTPUT RATINGS Applicable load Rated Load Load current Type load voltage voltage range With heat sink* Without heat sink Surge current G3NA-205B 24 to 240 VAC 19 to 264 VAC 0.1 to 5 A 0.1 to 3 A 60 A (60 Hz, 1 cycle) G3NA-210B 24 to 240 VAC 19 to 264 VAC 0.1 to 10 A 0.1 to 4 A 150 A (60 Hz, 1 cycle) G3NA-410B 200 to 480 VAC 180 to 528 VAC 0.2 to 10 A 0.2 to 4 A 150 A (60 Hz, 1 cycle) G3NA-220B 24 to 240 VAC 19 to 264 VAC 0.1 to 20 A 0.1 to 4 A 220 A (60 Hz, 1 cycle) G3NA-420B 200 to 480 VAC 180 to 528 VAC 0.2 to 20 A 0.2 to 4 A 220 A (60 Hz, 1 cycle) G3NA-225B 24 to 240 VAC 19 to 264 VAC 0.1 to 25 A 0.1 to 4 A 220 A (60 Hz, 1 cycle) G3NA-425B 200 to 480 VAC 180 to 528 VAC 0.1 to 25 A 0.1 to 4 A 220 A (60 Hz, 1 cycle) G3NA-240B 24 to 240 VAC 19 to 264 VAC 0.1 to 40 A 0.1 to 6 A 440 A (60 Hz, 1 cycle) G3NA-440B 200 to 480 VAC 180 to 528 VAC 0.2 to 40 A 0.2 to 6 A 440 A (60 Hz, 1 cycle) G3NA-D210B 5 to 200 VDC 4 to 220 VDC 0.1 to 10 A 0.1 to 4 A 20 A (10 ms) *When the appropriate size OMRON heat sink is used. 2