DATA SHEET G4 Digital Dry Contact Output Modules Form 364-140306 G4 Digital Dry Contact Output Modules Features Contact switching voltage of 100 VDC or 130 VAC maximum Contact resistance of 200 milli-ohms maximum Mechanical life of 5 million cycles Coil 5 VDC at 14 mA Operating temperature: -30 C to 70 C CE approved Passes NEMA Showering Arc Test (ICS 2-230) G4 Dry Contact Output Modules Meets IEEE Surge Withstand Specification (IEEE-472) NOTE: The application of the dry contact module must not exceed 10 VA under steady state or momentary in-rush conditions. For voltages at or below 20 volts, the current limit is 0.5 amps. For voltages above 20 volts, the maximum allowable current is determined by the following equation: Maximum Current = 10 VA / Voltage Description Opto 22s G4 family of modules includes two dry-contact, low- contact-resistance DC output modules, the G4ODC5R and the G4ODC5R5. The G4ODC5R is a single-pole, single-throw, normally open mechanical relay (Form A, SPST-NO). The G4ODC5R5 is a single-pole, single-throw, normally closed mechanical relay (Form B, SPST-NC). Typical applications for these modules include analog signal and communication line multiplexing.* Part Numbers Part Description G4 Dry Contact Output, 5 VDC Logic, G4ODC5R Normally Open G4 Dry Contact Output, 5 VDC Logic, G4ODC5RFM Normally Open, Factory Mutual Approved G4 Dry Contact Output, 5 VDC Logic, G4ODC5R5 Normally Closed G4 Dry Contact Output, 5 VDC Logic, G4ODC5R5FM Normally Closed, Factory Mutual Approved Opto 22 43044 Business Park Drive Temecula, CA 92590-3614 www.opto22.com PAGE SALES 800-321-6786 951-695-3000 FAX 951-695-3095 sales opto22.com SUPPORT 800-835-6786 951-695-3080 FAX 951-695-3017 support opto22.com 1 2011 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations.G4 Digital Dry Contact Output Modules Specifications Units G4ODC5R G4ODC5R5 G4ODC5RFM* G4ODC5R5FM* Form A SPST Form B SPST Contact form mechanical relay mechanical relay Normal position Open Closed Contact rating VA 10 10 VDC 100 100 Maximum switching voltage (see Note) VAC 130 130 Maximum switching current A 0.5 (see Note) 0.5 (see Note) NOTE: The application of the dry contact module Contact resistance Milliohms 200 200 must not exceed 10 VA Turn-on time microseconds 500 500 under steady-state or momentary in-rush condi- Turn-off time microseconds 500 500 tions. Contact bounce microseconds 250 250 For voltages at or below 20 Mechanical life cycles 5 million 5 million volts, the current limit is 0.5 amps. For voltages above Logic voltage range VDC 4.86 4.86 20 volts, the maximum Logic OFF voltage range VDC 0.00.8 0.00.8 allowable current is deter- mined by the following Logic ON voltage range VDC 3.86 3.86 equation: Indeterminate range VDC 0.83.8 0.83.8 Maximum Current = Logic input current at 10 VA / Voltage milliamps 14 14 nominal logic voltage Isolation voltage (transient) VDC 1,500 1,500 input-to-output Ambient temperature: Operating C 0 to 70 0 to 70 Storage C -60 to +105 -60 to +105 *Part numbers ending in FM are Factory Mutual approved. 10 VA Rating for Reed Relay (Dry Contact) Modules Current Limit at Key Voltages: VmA 5 500 12 500 24 416 1 100 100 120 83 2 130 76 1 Maximum DC voltage is 100 VDC. 2 Maximum AC voltage is 130 VAC. Opto 22 43044 Business Park Drive Temecula, CA 92590-3614 www.opto22.com PAGE SALES 800-321-6786 951-695-3000 FAX 951-695-3095 sales opto22.com SUPPORT 800-835-6786 951-695-3080 FAX 951-695-3017 support opto22.com 2 2011 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations. DATA SHEET G4 Digital Dry Contact Output Modules Form 364-140306