PANDUCT Hinged Cover Wiring Duct
Wire Fill Capacity
Electrical Communication
8 10 12 14 16 18 22 23 23/24 24 Fiber
AWG AWG AWG AWG AWG AWG AWG AWG AWG AWG Cable
Nominal Duct
.216 .164 .130 .141 .152 .111 .124 .133 .096 .111 .118 .084 .100 .106 .085 .330 .250 .190 .118
Size Nominal
(W x H) Area Cat. Cat. Cat. 3.0
In. In. THHN THHN THHN MTW MTW THHN MTW MTW TFFN MTW MTW TFFN MTW MTW MTW 6A 6 5e mm
1.50 x 2.00 3.000 34 60 95 81 70 131 105 91 175 131 116 229 162 144 224 14 25 44 116
PANDUCT Hinged Cover
1.50 x 3.00 4.500 52 90 143 122 105 197 158 137 263 197 174 344 243 216 336 22 38 67 174
2.00 x 2.00 4.000 46 80 127 108 93 175 140 122 234 175 155 306 216 192 299 19 34 59 154
Wiring Duct
2.00 x 3.00 6.000 69 120 191 163 140 263 210 183 351 263 232 459 324 288 448 29 51 89 232
2.00 x 4.00 8.000 92 160 255 217 187 350 281 244 469 350 310 612 432 384 598 39 69 119 309
PANDUIT innovative dual-sided hinged wiring duct
3.00 x 3.00 9.000 104 180 287 244 210 394 316 275 527 394 349 689 486 432 673 44 77 134 348
delivers improved wire management and aesthetics
3.00 x 4.00 12.000 139 241 383 326 280 526 421 366 703 526 465 919 648 577 897 59 103 179 464
4.00 x 4.00 16.000 185 321 511 435 374 701 562 488 938 701 621 1225 864 769 1197 79 138 239 619
for electrical control panel and communication
2
Table shows maximum wire fill based on 50% of duct internal cross sectional area. Formula = nominal area/1.85 x D . See EG Catalog SA-ELCB04 page C1.48
applications. The unique push-on hinged cover is
for wiring duct color and size availability. AWG dimensions represent typical outer cable diameter in inches.
easier to install and remove than traditional wiring
Material Specifications
duct covers and once installed can be opened from
either side of the duct. Hinged cover wiring duct
Properties PVC Material Test Method
Properties PVC Material Test Method
provides faster access to wiring, prevents cover
General Flammability
loss, reduces maintenance costs and
Specific Gravity 1.47 g/cc ASTM D 792
Limited Oxygen Index (LOI) 35 ASTM D 2863
promotes safety.
Rockwell Hardness 111 R ASTM D 785
Smoke Density (Flaming) 538 ASTM E 662
at 4 min.
Flammability Class V-0 UL94 Type HN hinged cover wiring duct features a
Mechanical
Tensile Strength at Yield 5,600 psi ASTM D 638
narrow slot design for high-density applications.
Agency Approvals
UL Recognized file E147128
Tensile Modulus 330,000 psi ASTM D 638
CSA Certified file 016446-0-00
Type H hinged cover wiring duct features a wide
CE Information slot design for general purpose use.
Flexural Strength at Yield 9,100 psi ASTM D 790
ENC50085 cable trunking system and
Type HN Narrow Slot Wiring Duct
cable ducting systems for electrical
installations:
Flexural Modulus 412,000 psi ASTM D 790
CDS (cable ducting system) for impact 2 J
Type HS solid wall raceway contains cables and
Minimum storage and transport
temperature -5C
cord sets for surface mount routing applications.
Notched Izod Impact 2.6 ft.-lbs./in. ASTM D 256 Minimum installation and application
temperature -5C
Strength at 23C (73F)
Maximum application temperature 60C
Heat Deflection 169F ASTM D 648 Non-flame propagating
Without electrical continuity
Temperature at 264 psi
Cover removable without a tool
Installation Tools
KeyFeatures Benefits
DFCT Duct Finger TNR Nylon Rivet
Delivers optimal alignment between slots and termination points in high density electrical
Type HN narrow slots and fingers
Cutting Tool Installation Tool
applications; multiple slot restrictors hold wiring at the device termination point to reduce
installation time and improve wire label identification
Easily removes duct Hand held tool for easy
fingers in tight places
rivet installation
Type H wide slots and fingers Provides flexibility by allowing use with a variety of wire sizes in electrical and
communication applications
DCT Duct DNT-100 Duct
Cutting Tool Notching Tool
Type HS solid wall raceway Fully encloses cables and cord sets for maximum protection in on-machine applications that
Notches duct sidewalls
Provides a smooth do not require frequent breakouts
burr-free cut on both to bottom scoreline for
wiring duct and cover
tees and corners Integrated hinged cover design Retains cover during maintenance for up to 20% faster wiring changes and reduced labor
costs; prevents lost covers for a neater panel appearance
WORLDWIDE SUBSIDIARIES AND SALES OFFICES
Dual-sided hinge Cover hinges open up to 100 from either sidewall of duct for easier wire access during
PANDUIT CANADA PANDUIT EUROPE LTD. PANDUIT SINGAPORE PTE. LTD. PANDUIT JAPAN PANDUIT LATIN AMERICA PANDUIT AUSTRALIA PTY. LTD. maintenance, to reduce labor costs
Markham, Ontario London, UK Republic of Singapore Tokyo, Japan Jalisco, Mexico Victoria, Australia
cs-cdn@panduit.com cs-emea@panduit.com cs-ap@panduit.com cs-japan@panduit.com cs-la@panduit.com cs-aus@panduit.com
Phone: 800.777.3300 Phone: 44.20.8601.7200 Phone: 65.6379.6700 Phone: 81.3.3767.7011 Phone: 52.333.777.6000 Phone: 61.3.9794.9020 Cover retention flange Saves time with simple push-on cover installation; full engagement between cover and
base results in cover retention up to 2 times greater than conventional wiring ducts;
For a copy of PANDUIT product warranties, log on to www.panduit.com/warranty
prevents cover slip when exposed to vibration
For more information
2007 PANDUIT Corp.
Cover removal tab
Provides gripping surface to ease cover opening or removal to reduce labor costs during wire
ALL RIGHTS RESERVED.
Visit us at www.panduit.com/
installation or maintenance
Printed in the U.S.A.
Contact Customer Service by email: cs@panduit.com Product Bulletin Number WW-WDCB11
or by phone: 800-777-3300 and reference WDCB11 12/2007
wwwwww..ppaanndduuiitt..ccoomm
PANDUCT Hinged Cover Wiring Duct
PANDUCT Hinged Cover Wiring Duct
Ordering Information
Control Panel Application Communication Application
Type HN: Narrow Slot Type H: Wide Slot Type HS: Solid Wall
Standard Carton
Duct Nominal Size Quantity
Type HN Duct Part Type H Duct Part Type HS Duct Part W X H W X H Cover Part Duct Cover
Numbers Numbers Numbers (inches) (mm) Numbers (Ft.) (Ft.)
Frequent moves, adds, changes or equipment
High visibility and high traffic areas require a
HN1.5X2LG6 H1.5X2LG6 HS1.5X2LG6NM 1.5 x 2.0 37 x 50 HC1.5LG6 120 120
upgrades require repeated, easy, and quick access
neat appearance
HN1.5X3LG6 H1.5X3LG6 HS1.5X3LG6NM 1.5 x 3.0 37 x 75 HC1.5LG6 120 120
to duct channel
HN2X2LG6 H2X2LG6 HS2X2LG6NM 2.0 x 2.0 50 x 50 HC2LG6 120 120
HN2X3LG6 H2X3LG6 HS2X3LG6NM 2.0 x 3.0 50 x 75 HC2LG6 60 120
HN2X4LG6 H2X4LG6 HS2X4LG6NM 2.0 x 4.0 50 x 100 HC2LG6 60 120
Labor Savings
HN3X3LG6 H3X3LG6 HS3X3LG6NM 3.0 x 3.0 75 x 75 HC3LG6 60 120
By eliminating the time involved in removing and replacing covers with hinged cover wiring duct, simple wiring
HN3X4LG6 H3X4LG6 HS3X4LG6NM 3.0 x 4.0 75 x 100 HC3LG6 60 120
changes can be made up to 20% faster compared to conventional wiring duct installations*
HN4X4LG6 H4X4LG6 HS4X4LG6NM 4.0 x 4.0 100 x 100 HC4LG6 60 60
Note: Base and cover are sold separately.
% of Wiring Duct Cost
Prevent Cover Replacement Costs
Product shown in LG (Light Gray). Type HN also available in WH (White), Type H and Type HS also available in BL (Black) and WH (White)
Covers represent 20% of the cost of the wiring
Technical Information
duct purchase
Misplaced covers are a common occurrence after
Dimensions Inches (mm)
Base Cover
Duct Size
years of use
100
(W x H) ABCD E1 F1 E2 F2 HK T
Hinged cover wiring duct eliminates lost covers 1.5 x 2 1.75 1.98 1.88 1.63 0.20 0.50 0.31 .80 1.92 .08
C
(38.1) x (50.8) (44.5) (50.3) (47.8) (41.4) (5.0) (12.7) (7.9) (20.3) (48.8) (2.0)
1.5 x 3 1.75 3.06 1.88 2.63 0.20 0.50 0.31 1.00 3.00 .10
(38.1) x (76.2) (44.5) (77.7) (47.8) (66.8) (5.0) (12.7) (7.9) (25.4) (76.2) (2.5)
2 x 2 2.17 1.98 2.29 1.57 0.20 0.50 0.31 .80 1.92 .50 .08
0% 40% 60% 80%
20% 100%
B (50.8) x (50.8) (55.1) (50.3) (58.2) (39.9) (5.0) (12.7) (7.9) (20.3) (48.8) (12.7) (2.0)
2 x 3
2.17 3.06 2.29 2.63 0.20 0.50 0.31 1.00 3.00 .50 .10
T
(50.8) x (76.2) (55.1) (77.7) (58.2) (66.8) (5.0) (12.7) (7.9) (25.4) (76.2) (12.7) (2.5)
2 x 4 2.17 4.1 4.38 3.63 0.20 0.50 0.31 1.00 4.00 .50 .10
Ease of Installation and Access
(50.8) x (101.6) (55.1) (104.1) (111.3) (92.2) (5.0) (12.7) (7.9) (25.4) (101.6) (12.7) (2.7)
OR
A
3 x 3 3.25 3.06 3.38 2.63 0.20 0.50 0.31 1.00 3.00 1.00 .10
Cover retention flanges guide duct fingers into cover for simple
(76.2) x (76.2) (82.6) (77.7) (85.9) (66.8) (5.0) (12.7) (7.9) (25.4) (76.2) (25.4) (2.5)
push-on cover installation
3 x 4 3.25 4.1 3.38 3.63 0.20 0.50 0.31 1.00 4.00 1.00 .11
E1
Cover hinges open to 100 from either sidewall to allow full (76.2) x (101.6) (82.6) (104.1) (85.9) (92.2) (5.0) (12.7) (7.9) (25.4) (101.6) (25.4) (2.8)
4 x 4 4.25 4.1 4.38 3.63 0.20 0.50 0.31 1.00 4.00 1.50 .11
channel access
(101.6) x (101.6) (108.0) (104.1) (111.3) (92.2) (5.0) (12.7) (7.9) (25.4) (101.6) (38.1) (2.8)
D
H
100
C F2
For 2", 3", and 4" wide duct.
Type H 2", 3", and 4" wide duct.
Durability and Performance
F1
Cover fully engages fingers limiting sidewall flex for greater
Type HN: Multiple slot restrictors
K
D
B
present with 3" and greater duct H C
L
rigidity and durability*
T K
wall height.
Cover retention is up to 2 times greater than conventional
For 2", 3", and 4" wide duct.
Type HN 2", 3" and 4" wide duct.
wiring ducts**
4.0 [101.6] TYP 2.0
A E2
[50.8]
Type H
K
C
L
K
2.0 TYP 2.0
*Based on mock panel installations of Type H Hinged Cover Wiring Duct and other commonly available wiring ducts adding a single component with four wires.
[50.8] [50.8]
**Based on test and measurements comparing Type H Hinged Cover Wiring Duct to other commonly available wiring ducts.
On CL