Bulletin No. PSDRW-D Drawing No. LP0954 Released 08/14 Tel +1 (717) 767-6511 Fax +1 (717) 764-0839 www.redlion.net MODEL PSDR - 24 V POWER SUPPLY z 30 W, 60 W OR 95 W MODELS z ADJUSTABLE OUTPUT VOLTAGE z PARALLEL OR SERIES USE CAPABILITY (30 & 60 ONLY) z MOUNT ON 35 MM DIN RAILS U R C L US LISTED IND. CONT. EQ. 18WM Degree of pollution in acc. with EN 50178, IEC 62103: 2 DESCRIPTION Degree of protection in acc. with EN 60529: IP20 The compact PSDR power supplies are industrial input voltage supplies Class of protection in acc. with IEC 61140: 1, PE connection required with primary switched-mode regulator technology and low output ripple. The (ground) supplies all have adjustable output voltages from 24 to 28 VDC and the 10. CERTIFICATIONS AND COMPLIANCES: outputs are electronically protected against overloads and short circuits. CE Marking CE mark is in conformance with EMC directive 2004/108/EC, the low- SPECIFICATIONS voltage directive (LVD) 2006/95/EC and the RoHS directive 2011/65/ 1. POWER REQUIREMENTS EU. PSDR030W AND PSDR060W: EMC Immunity: EN 61000-6-1, EN 61000-6-2 AC Input Voltage: 100 to 240 VAC (-15% / +10%), 50/60 Hz EMC Emission: EN 61000-6-3, EN 61000-6-4, FC Part 15 Class B DC Input Voltage: 110 to 300 VDC (-20% / +25%) Safety: EN 60950-1 Current Consumption: UL Listed: File E171375 PSDR030W: 0.54 120 VAC, 60 Hz / 0.3 A 230 VAC, 50 Hz 11. ISOLATION VOLTAGE: Input/Output PSDR060W: 0.98 120 VAC, 60 Hz / 0.58 A 230 VAC, 50 Hz PSDR030W and PSDR095W: 3 kVAC Maximum Voltage L or N to Earth: 264 VAC, 375 VDC PSDR060W: 4 kVAC PSDR095W: 12. INSTALLATION: Use DIN-rails acc. to EN 60715 or EN 50022 with a AC Input Voltage: 100 - 120 VAC / 220 to 240 VAC (-15% / +10%), height of 7.5 or 15mm. 50/60 Hz (auto select input) 13. MOUNTING: DC Input Voltage: 290 VDC (-25% / +30%) Clearance Left/Right: 0 mm, or 15 mm if adjacent device is a heat source. Current Consumption: 1.63 120 VAC, 60 Hz / 0.95 A 230 VAC, 50 Clearance Top: 40 mm Hz Clearance Bottom: 20 mm Maximum Voltage L or N to Earth: 264 VAC / 375 VDC 14. CONNECTIONS: 2. FUSE: Internally fused for use in branch circuits supplying up to 20A. If Use appropriate copper cable, designated for a minimum operating less than 20A breaker is used, a minimum value of 10A B- or 6A C- (60 W temperature of: and 95 W) or 6A B- or 3A C- (30 W) breaker should be used to avoid 60 C for ambient temperatures up to 45 C nuisance tripping. 75 C for ambient temperatures up to 60 C 3. INPUT INRUSH CURRENT: (Peak at 40 C ambient and cold start) PSDR030W AND PSDR060W: PSDR030W: 18 A 120 VAC, 35 A 230 VAC Terminals: Screw clamp. All unused terminals must be closed. 2 2 PSDR060W: 16 A 120 VAC, 32 A 230 VAC Wire: 20 to 10 AWG 0.5-6 mm solid wire, 0.5-4 mm stranded wire. PSDR095W: 22 A 120 VAC, 37 A 230 VAC Max wire diameter at terminal: 0.11 (2.8 mm), Ferrules are acceptable 4. OUTPUT VOLTAGE: 24 to 28 VDC, adjustable via potentiometer Wire stripping length 0.28 inch (7 mm). 5. OUTPUT POWER: Terminal Torque: 9 lb.inch (1 Nm) PSDR030W: 30 W (1.3 A 24 VDC, 1.1 A 28 VDC) PSDR095W: PSDR060W: 60 W (2.5 A 24 VDC, 2.1 A 28 VDC) Terminals: Spring clamp. All unused terminals must be closed. 2 2 PSDR095W: 95 W (3.9 A 24 VDC, 3.4 A 28 VDC) Wire: 28 to 12 AWG 0.3-2.5 mm solid wire, 0.3-2.5 mm stranded wire. 6. OUTPUT RIPPLE & NOISE: 50 mVp-p (50 ohm measurement, 20 MHz Max wire diameter at terminal: 0.088 (2.25 mm), Ferrules are acceptable bandwidth) Wire stripping length 0.25 inch (6 mm). 7. OUTPUT OVERVOLTAGE PROTECTION: 15. CONSTRUCTION: Case body is black, high impact plastic. IP20 touch PSDR030W: 38 VDC safe. Protection Class I, PE connection required (ground). PSDR060W: 32.5 VDC 16. WEIGHT: PSDR095W: 36 VDC PSDR030W: 4.9 oz. (140 g) 8. EFFICIENCY: (At 120 VAC, 60Hz / 230 VAC, 50Hz) PSDR060W: 8.8 oz. (250 g) PSDR030W: 88.5% / 89.4% PSDR095W: 12.3 oz. (360 g) PSDR060W: 87.8% / 89.7% PSDR095W: 89% / 90.0% 9. ENVIRONMENTAL CONDITIONS: Operating Temperature Range: -10 to 60 C ORDERING INFORMATION Storage Temperature: -40 to 85 C MODEL NO. DESCRIPTION PART NUMBER Humidity: 5 to 95 % RH, non-condensing Vibration in acc. with IEC 60068-2-6: 2 g 24 VDC 30 W 1.25 A Power Supply PSDR030W Shock in acc. with IEC 60068-2-27: 30 g 6 ms, 20 g 11 ms PSDR 24 VDC 60 W 2.5 A Power Supply PSDR060W 24 VDC 95 W 3.9 A Power Supply PSDR095W PU-372.010.20-XXB 1 DIMENSIONS In inches (mm) PSDR030W PSDR060W 1.02 0.37 (26.0) (9.5) + 24V 1.3A ++ 24V 2.5A DC on DC on 24-28V 2.95 24-28V 2.95 (75.0) (75.0) PSDR060W PSDR030W Power Supply Power Supply AC 100-240V AC 100-240V N L N L 0.47 0.82 DIN-Rail (12.1) 3.58 (91.0) (20.8) Depth DIN-Rail 0.89 3.58 (91.0) 1.77 (45.0) Depth (22.5) DIMENSIONS In inches (mm) 2.85 (72.5) PSDR095W 0.92 1.02 4.06 (103) (23.3) (26.0) ++ 24V 3.9A NEC Class 2 DC on 24-28V 2.95 (75.0) PSDR095W Power Supply AC 100-120 / 220-240V N L CONNECTION AND OPERATION INSTRUCTIONS Before operating this unit please read this manual thoroughly and retain this manual for future reference This device may only be installed and put into operation by qualified personnel. If damage or malfunction should occur WARNING during operation, immediately turn power off and send unit to the factory for Risk of electrical shock, fire, personal injury or death. inspection. The unit does not contain serviceable parts. The tripping of an internal fuse (if included) is caused by an internal defect. The information Do not use the power supply without proper grounding (Protective Earth). presented in this document is believed to be accurate and reliable and may Turn power off before working on the device. Protect against inadvertent change without notice. re-powering. Intended Use: This device is designed for installation in an enclosure and is Make sure that the wiring is correct by following all local and national intended for general use such as in industrial control, office, communication, codes. and instrumentation equipment. Do not use this device in equipment, where Do not modify or repair the unit. malfunction may cause severe personal injury or threaten human life. Do not open the unit as high voltages are present inside. Use caution to prevent any foreign objects from entering the housing. INSTALLATION Do not use in wet locations or in areas where moisture or condensation Mounting orientation must be output terminals on top and input terminals can be expected. on the bottom. Do not obstruct air flow as the unit is convection cooled. Do not touch during power-on, and immediately after power-off. Hot Ventilation grid must be kept free of any obstructions. Maintain specified surfaces may cause burns. installation clearances when power supplies are permanently fully loaded: TERMINALS AND WIRING Use the appropriate copper cables as listed in the specifications and follow national installation codes and regulations Ensure that all strands of a stranded wire enter the terminal connection Ferrules are allowed. Unused terminal must be closed. 2