20.04.2011 Print - Create PDF - Create EXCEL file - 17:44:58h Datasheet - AES 1135 Guard door monitors and Safety control modules for Emergency Stop applications / Monitoring of electromechanical and non-contact switchgear / AES 113x Monitoring of BNS range magnetic safety sensors 1 safety contact, STOP 0 2 Signalling outputs (Minor differences between the printed image and the original product may exist ) Ordering details Product type description AES 1135 Article number 1170036 EAN code 4030661296920 Approval Approval BG USA/CAN Classification Standards EN ISO 13849-1, IEC 61508 PL up d Control category up 3 PFH value 1.0 x 10-7/h SIL up 2 Mission time 20 Years Global Properties Product name AES 113xStandards IEC/EN 60204-1, IEC 60947-5-3, EN 954-1, BG-GS-ET-14, BG-GS-ET-20 Compliance with the Directives (Y/N) Yes Climatic stress EN 60068-2-3, BG-GS-ET-14 Mounting snaps onto standard DIN rail to EN 60715 Terminal designations IEC/EN 60947-1 Materials - Material of the housings Plastic, glass-fibre reinforced thermoplastic, ventilated - Material of the contacts Ag-Ni, 0,2 m gold flashed Weight 155 g Start conditions Automatic Start input (Y/N) No Feedback circuit (Y/N) No Start-up test (Y/N) No Reset after disconnection of supply voltage (Y/N) Yes Automatic reset function (Y/N) Yes Reset with edge detection (Y/N) No Pull-in delay - ON delay with automatic start adjustable 0,1 / 1.0 s Drop-out delay - Drop-out delay in case of emergency stop < 50 ms Mechanical data Connection type Screw connection Cable section - Min. Cable section 0,25 mm - Max. Cable section 2.5 mm Pre-wired cable rigid or flexible Tightening torque for the terminals 0,6 Nm Detachable terminals (Y/N) No Mechanical life 20.000.000 operations Electrical lifetime 150.000 operations for 230 VAC, 5 A (cos = 1) restistance to shock 30 g / 11 ms Resistance to vibration To EN 60068-2-6 10...55 Hz, Amplitude 0,35 mm, 15 % Ambient conditions Ambient temperature - Min. environmental temperature 0C - Max. environmental temperature + 55C Storage and transport temperature - Min. Storage and transport temperature - 25C - Max. Storage and transport temperature + 70C Protection class - Protection class-Enclosure IP40 - Protection class-Terminals IP20 - Protection class-Clearance IP54 Air clearances and creepage distances To IEC/EN 60664-1 - Rated impulse withstand voltage Uimp 4.8 kV - Overvoltage category III To VDE 0110 - Degree of pollution 2 To VDE 0110 Electromagnetic compatibility (EMC)