Product data sheet GS1DU3 Characteristics TeSys GS, disconnect switch, fuse, 3 P, 600 V, UL 30 A, Type J fuse Product availability: Stock - Normally stocked in distribution facility Main Range TeSys Product name TeSys GS Device short name GS1D Product or component Switch-disconnector-fuse type Device application Protection Design Compact Poles description 3P Protected poles descrip- 3t tion Contacts type and com- 3 NO position Ith conventional free 30 A at 104 F (40 C) air thermal current Ie rated operational 30 A current Fuse type UL Fuse size J Network type DC AC Network frequency 50/60 Hz Complementary Type of operating handle External frontal Mounting support Rail Plate Ui rated insulation voltage 690 V Uimp rated impulse withstand voltage 8 kV Rated operational power in W 15 kW at 400 V 25 kW at 690 V 18.5 kW at 500 V Short-circuit withstand 5.5 kA Mechanical durability 10000 cycles Electrical durability 6000 cycles Connections - terminals Power circuit: lugs-ring terminals cable 2...6 mm Tightening torque Power circuit: 26.55 lbf.in (3 N.m) Environment Standards CSA C22.2 No 4 UL98 Product certifications ASEFA LROS (Lloyds register of shipping) LOVAG IP degree of protection IP20 with terminal cover conforming to IEC 60529 Ambient air temperature for operation -4...158 F (-20...70 C) Ambient air temperature for storage -40...176 F (-40...80 C) Fire resistance 1760 F (960 C) body conforming to IEC 60695-2-1 Height 4.57 in (116 mm) Width 4.13 in (105 mm) Aug 11, 2019 1 The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.Depth 3.9 in (99 mm) Product weight 1.54 lb(US) (0.7 kg) Ordering and shipping details Category 22640 - IEC DISCONNECT-GS1,LK3 Discount Schedule I11 GTIN 00785901367529 Nbr. of units in pkg. 1 Package weight(Lbs) 1.4199999999999999 Returnability Y Country of origin FR Offer Sustainability RoHS (date code: YYWW) Compliant - since 1610 - Schneider Electric declaration of conformity Schnei- der Electric declaration of conformity REACh Reference not containing SVHC above the threshold California proposition 65 WARNING: Cancer - www.P65Warnings.ca.gov Contractual warranty Warranty period 18 months 2