Product data sheet HJL26015 Characteristics PowerPact H Circuit Breaker,ThermMagn,15A,2P,600V,25kA Product availability : Stock - Normally stocked in distribution facility Main Product or component type Circuit breaker Range of product PowerPact H Trip unit technology Thermal-magnetic Breaking capacity code J Complementary Line Rated Current 15 A Poles description 2P Breaking capacity 65 kA at 480 V AC 25 kA at 600 V AC 100 kA at 240 V AC 20 kA at 250 V DC System Voltage 250 V DC 600 V AC Ics rated service short-circuit 80 % breaking capacity Mounting mode Unit mount Electrical connection Lugs load Lugs line AWG gauge AWG 14...AWG 3/0 (aluminium/copper) Magnetic hold current 350 A Magnetic tripping current 750 A Environment Product certifications IEC CSA CE UL listed Nov 09, 2017 1 Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applicationsAmbient air temperature for operation 104 F (40 C) Ordering and shipping details Category 01115 - HG,HJ,JG,JJ UNIT MT BREAKER/SWITCH Discount Schedule DE2 GTIN 00785901839439 Nbr. of units in pkg. 1 Package weight(Lbs) 3.96 Returnability Y Country of origin MX Offer Sustainability Sustainable offer status Green Premium product RoHS (date code: YYWW) Compliant - since 0832 - Schneider Electric declaration of conformity Schneider Electric declaration of conformity REACh Reference not containing SVHC above the threshold Reference not containing SVHC above the threshold Product environmental profile Available Product end of life instructions Need no specific recycling operations Contractual warranty Warranty period 18 months 2