22005 Ver8.00-EN.backup.fm Page 18 Thursday, October 25, 2001 4:59 PM Characteristics Contactors Contactors and reversing contactors types LCp-K and LPp-K Environment Conforming to standards IEC/EN 60947-1, IEC/EN 60947-4-1, NF C 63-110, VDE 0660 Approvals LCpppp and LPpppp-K06 to K12 UL, CSA, DEMKO, NEMKO, SEMKO, FI Operating positions Vertical axis Horizontal axis 2 Without derating Without derating Possible positions for LCp-K only. Contactor energisation voltage: 0.85 Uc Max to 2.2 Cabling Min Max IEC/EN 60947 2 Screw clamp connections Solid conductor mm 1 x 1.5 2 x 4 1 x 4 + 1 x 2.5 2 Flexible cable without cable end mm 1 x 0.75 2 x 4 2 x 2.5 2 Flexible cable with cable end mm 1 x 0.34 1 x 1.5 + 1 x 2.5 1 x 1.5 + 1 x 2.5 2 Spring terminal connections Solid conductor mm 1 x 0.75 1 x 1.5 2 x 1.5 2 Flexible conductor without cable end mm 1 x 0.75 1 x 1.5 2 x 1.5 Faston connectors Clip mm 2 x 2.8 or 1 x 6.35 Solder pins for With locating device between power printed circuit board and control circuits 4 mm x 35 microns Tightening torque Philips head n 2 and 6 N.m 0.81.3 Terminal referencing Conforming to standards EN 50005 and EN 50012 Up to 5 contacts Rated insulation voltage (Ui) Conforming to IEC/EN 60947-4-1 V 690 Conforming to VDE 0110 gr C V 750 Conforming to NF C 20-040 V 690 Conforming to CSA 22-2 n 14, UL 508 V 600 Rated impulse withstand voltage kV 8 (Uimp) Protective treatment Conforming to IEC 68 (DIN 50016) TC (Klimafest, Climateproof) Degree of protection Conforming to VDE 0106 Protection against direct nger contact Ambient air temperature Storage C - 50+ 80 around the device Operation C - 25+ 50 Maximum operating altitude Without derating m 2000 Vibration resistance Contactor open 2 gn 5 ... 300 Hz Contactor closed 4 gn Flame resistance Conforming to UL 94 Self-extinguishing materials V1 Conforming to NF F 16-101 and 16-102 Conforming to requirement 2 Shock resistance Contactor open 10 g (1/2 sine wave, 11 ms) Contactor closed 15 g Safe circuit separation Conforming to VDE 0106 and IEC 536 VLSV (Very Low Safety voltage), up to 400 V Selection: References: Dimensions: Schemes: pages 1/12 to 1/35 pages 2/22 to 2/35 pages 2/40 and 2/42 pages 2/41 and 2/43 Schneider Electric 2/18 0 8 1 22005 Ver8.00-EN.backup.fm Page 19 Thursday, October 25, 2001 4:59 PM Characteristics Contactors Contactors and reversing contactors types LCp-K and LPp-K Pole characteristics Conventional thermal current (Ith) For ambient temperature 50 C A 20 Rated operational frequency Hz 50/60 Frequency limits of operational current Hz Up to 400 Rated operational voltage (Ue) V 690 2 Rated making capacity I rms to NF C 63-110 and IEC/EN 60947-4-1 pp pp pp pp LCpp-K06, LPpp-K06, LCpp-K09, LPpp-K09 A 110 LCpppp-K12, LPpppp-K12 A 144 Rated breaking capacity V 220/ 380/ 415 440 500 660/ 240 400 690 I rms to NF C 63-110 and IEC/EN 60947-4-1 pp pp pp pp LCpp-K06, LPpp-K06, LCpp-K09, LPpp-K09 A 110 110 110 110 80 70 LCpppp-K12, LPpppp-K12 A 110 80 70 2.2 Permissible short time rating In free air for a time t 1 s 5 s 10 s 30 s 1 3 15 min min min from cold state ( 50 C) pp pp pp pp LCpp-K06, LPpp-K06, LCpp-K09, LPpp-K09 A 90 85 80 60 45 40 20 LCpppp-K12, LPpppp-K12 A 115 105 100 75 55 50 25 Short-circuit protection gG fuse U 440 V (aM fuse, see page 2/46) A 25 Average impedance per pole At Ith and 50 Hz m 3 Utilisation in category AC-1 Maximum rated operational current A 20 resistive circuits, heating, lighting for a temperature 50 C (Ue 440 V) Maximum rated operational current A 16 for Ue only for a temperature 70 C Rated operational current limits in relation A On-load factor 90% 60 % 30 % to on-load factor and operating frequency 300 op. cycles/hour 13 15 18 120 op. cycles/hour 15 18 19 30 op. cycles/hour 19 20 20 Increase in operational current Apply the following coefcients to the current values by paralleling of poles above. These take into account the often unbalanced current distribution between poles 2 poles in parallel: K = 1.60 3 poles in parallel: K = 2.25 4 poles in parallel: K = 2.80 Utilisation in category AC-3 Operational power squirrel cage motors according to the voltage Voltage 50 or 60 Hz V 115 220 220/ 380/ 440/ 500/ 660/ 240 415 480 600 690 1-ph 1-ph 3-ph 3-ph 3-ph 3-ph 3-ph LCpppp-K06, LPpppp-K06 kW 0.37 0.75 1.5 2.2 3 3 3 LCpppp-K09, LPpppp-K09 kW 0.55 1.1 2.2 4 4 4 4 LCpppp-K12, LPpppp-K12 kW 3 5.5 5.5/ 4 4 4 (480) % utilisation of operational power in relation Op. cycles/hr 600 900 1200 to the maximum operating rate Power 100% 75% 50% Selection: References: Dimensions: Schemes: pages 1/12 to 1/35 pages 2/22 to 2/35 pages 2/40 and 2/42 pages 2/41 and 2/43 Schneider Electric 2/19