Product data sheet PM710MG Characteristics power meter PM710 - basic readings, THD + min/ max + RS485 Main Range of product PowerLogic PM700 Device short name PM710 Product or component type Power meter Complementary Power quality analysis Total harmonic distortion Type of measurement Energy Power factor (total) Apparent power (total) Apparent power (per phase) Active power (total) Active power (per phase) Reactive power (total) Reactive power (per phase) Voltage Current Frequency Us rated supply voltage 125...250 V DC 115...415 V AC (45...65 Hz) Network frequency 45...65 Hz Power consumption in VA 5 VA Display type Backlit LCD Display resolution 6 lines Sampling rate 32 samples/cycle Measurement current 1 A 5 A Analogue input type Current 0.005...6 A (impedance <= 0.1 Ohm) Measurement voltage 10...480 V AC 45...65 Hz phase to phase 10...277 V AC 45...65 Hz phase to neutral Measurement accuracy 1 % power 0.5 % current (1...6 A) 0.5 % voltage (50...227 V) Mar 09, 2017 1 Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications 0.02 Hz frequency (45...65 Hz) 0.0034 power factor (1A to 6A and from -0.5 to +0.5) Accuracy class Class 2 (reactive energy according to IEC 62053-23) Class 1 (active energy according to IEC 62053-21) Communication port protocol Modbus: 19.2 kbauds, Communication port support RS485 Data recording Min/Max of instantaneous values Environment Electromagnetic compatibility Limits for harmonic current emissions, conforming to IEC 61000-3-2 Conducted and radiated emissions, conforming to EN 55011 class B Susceptibility to electromagnetic fields class class III, conforming to IEC 61000-4-3 Conducted RF disturbances class class III, conforming to IEC 61000-4-6 Electrostatic discharge immunity test class class III, conforming to IEC 61000-4-2 Electrical fast transient/burst immunity test class class III, conforming to IEC 61000-4-4 1.2/50 s shock waves immunity test class class III, conforming to IEC 61000-4-5 Immunity to impulse waves class class III, conforming to IEC 61000-4-8 Immunity to microbreaks and voltage drops class class III, conforming to IEC 61000-4-11 Limitation of voltage changes, voltage fluctuations and flicker in low-voltage, conforming to IEC 61000-3-3 Mounting mode Flush-mounted Mounting support Panel Type of installation Indoor installation Overvoltage category III IP degree of protection IP30 (back) conforming to IEC 60529 IP52 (front face) conforming to IEC 60529 Relative humidity 95 % 50 C Pollution degree 2 Ambient air temperature for operation -5...50 C Ambient air temperature for storage -40...85 C Operating altitude 0...3000 m Standards CSA C22.2 No 14 UL 508 IEC 61010-1 Product certifications CE cULus Width 96 mm Depth 69 mm Height 96 mm Product weight 0.37 kg Offer Sustainability Sustainable offer status Green Premium product RoHS (date code: YYWW) Compliant - since 0951 - Schneider Electric declaration of conformity Schneider Electric declaration of conformity REACh Reference not containing SVHC above the threshold Reference not containing SVHC above the threshold Product environmental profile Available End of life manual Product end of life instructions Available Contractual warranty Warranty period 18 months 2