Product data sheet RM17UAS16 Characteristics voltage control relay RM17-U - range 20..80 V AC Product availability: Non-Stock - Not normally stocked in distribution facility Main Range of product Zelio Control Product or component Modular measurement and control relays type Relay type Voltage control relay Product specific applica- For single-phase and DC supply tion Relay name RM17UAS Relay monitored para- Self-powered meters Overvoltage or undervoltage detection Time delay Adjustable 0.1...10 s, 0 + 10 % on crossing the threshold Switching capacity in 1250 VA VA Minimum switching cur- 10 mA at 5 V DC rent Maximum switching cur- 5 A AC/DC rent Power consumption in 0...3.9 VA AC VA Measurement range 20...80 V voltage AC 50/60 Hz 20...80 V voltage DC Utilisation category AC-12 conforming to IEC 60947-5-1 AC-13 conforming to IEC 60947-5-1 AC-14 conforming to IEC 60947-5-1 AC-15 conforming to IEC 60947-5-1 DC-12 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 DC-14 conforming to IEC 60947-5-1 Complementary Reset time 1500 ms time delay Maximum switching voltage 250 V AC/DC Us rated supply voltage 24...48 V AC/DC, 50/60 Hz +/- 10 % Supply voltage limits 15...100 V AC/DC Power consumption in W <= 1.6 W DC Immunity to microbreaks 20 ms Control circuit frequency 50...60 Hz +/- 10 % Output contacts 1 C/O Nominal output current 5 A Measuring cycle <= 150 ms measurement cycle as true rms value Hysteresis 5...20 % of threshold setting Measurement accuracy +/- 10 % of the full scale value Repeat accuracy +/- 0.5 % input and measurement circuit +/- 1 % time delay Measurement error < 1 % over the whole range with voltage variation 0.2 %/C with temperature variation Polarity Non reversible polarity on DC supply Quality labels CE Overvoltage category III conforming to IEC 60664-1 Insulation resistance > 500 MOhm at 500 V DC conforming to IEC 60255-5 Aug 11, 2019 1 The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. Ui rated insulation voltage 250 V conforming to IEC 60664-1 400 V conforming to IEC 60664-1 Operating position Any position without Connections - terminals Screw terminals 1 x 0.5...1 x 4 mm - AWG 20...AWG 11, solid cable without ca- ble end Screw terminals 2 x 0.5...2 x 2.5 mm - AWG 20...AWG 14, solid cable without cable end Screw terminals 2 x 0.2...2 x 1.5 mm - AWG 24...AWG 16, flexible cable with ca- ble end Screw terminals 1 x 0.2...2 x 2.5 mm - AWG 24...AWG 12, flexible cable with ca- ble end Tightening torque 5.31...8.85 lbf.in (0.6...1 N.m) conforming to IEC 60947-1 Housing material Self-extinguishing plastic Local signalling LED green power ON LED yellow relay ON Mounting support 35 mm symmetrical DIN rail conforming to EN/IEC 60715 Electrical durability 100000 cycles Mechanical durability 30000000 cycles Operating rate <= 360 operations/hour under full load Width 0.69 in (17.5 mm) Product weight 0.18 lb(US) (0.08 kg) Environment Electromagnetic compatibility Emission standard for industrial environments conforming to EN/IEC 61000-6-4 Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3 Immunity for industrial environments conforming to NF EN/IEC 61000-6-2 Standards EN/IEC 60255-6 Product certifications GOST C-Tick GL UL CSA Directives 73/23/EEC - low voltage directive 89/336/EEC - electromagnetic compatibility Ambient air temperature for storage -40...158 F (-40...70 C) Ambient air temperature for operation -4...122 F (-20...50 C) Relative humidity 95 % at 131 F (55 C) conforming to IEC 60068-2-30 Vibration resistance 0.35 mm (f = 5...57.6 Hz) conforming to IEC 60068-2-6 1 gn (f = 57.6...150 Hz) conforming to IEC 60255-21-1 Shock resistance 5 gn conforming to IEC 60068-2-27 IP degree of protection IP20(Terminals) conforming to IEC 60529 IP30 (casing) conforming to IEC 60529 Pollution degree 3 conforming to IEC 60664-1 Dielectric test voltage 2 kV AC 50 Hz, 1 min conforming to IEC 60255-5 2 kV AC 50 Hz, 1 min conforming to IEC 60664-1 Non-dissipating shock wave 4 kV conforming to IEC 60255-5 4 kV conforming to IEC 60664-1 4 kV conforming to IEC 61000-4-5 Ordering and shipping details Category 22380 - RELAYS-MEASUREMENT (RM17-RM35) Discount Schedule CP2 GTIN 003389119405119 Nbr. of units in pkg. 1 Package weight(Lbs) 0.19 Returnability N Country of origin ID 2