Product data sheet RMCV60BD Characteristics Analog Converter - 0..50 V - for Zelio Analog Product availability: Non-Stock - Not normally stocked in distribution facility Main Range of product Zelio Analog Product or component Voltage/current converter type Analogue input type Voltage 0...300 V AC/DC 50/60 Hz Voltage 0...50 V AC/DC 50/60 Hz Voltage 0...500 V AC/DC 50/60 Hz Analogue output type Current 0...20 mA <= 500 Ohm switchable Current 4...20 mA <= 500 Ohm switchable Voltage 0...10 V >= 100 kOhm switchable Complementary Protection type Reverse polarity protection on output Overvoltage protection on output (+/- 30 V) Short-circuit protection on output Abnormal analogue output voltage -15...0 V, when no input or input wire broken Abnormal analogue output current 0...-30 mA, output selected 0...20 mA, when no input or input wire broken 4...-30 mA, output selected 4...20 mA, when no input or input wire broken Us rated supply voltage 24 V DC +/- 20 %, isolated Current consumption <= 70 mA voltage output <= 90 mA current output Local signalling LED green (power ON) Measurement error +/- 5 % of full scale at 20 C +/- 10 % of full scale at 20 C (electromagnetic interference of 10 V/m) Repeat accuracy +/- 0.2 % full scale at 20 C +/- 0.6 % full scale at 60 C Temperature coefficient 200 ppm/C Clamping connection capacity 1 x 2.5 mm 2 x 1.5 mm Tightening torque 5.31...9.73 lbf.in (0.6...1.1 N.m) Marking CE Surge withstand 0.5 kV 1.2/50 s conforming to IEC 61000-4-5 Ui rated insulation voltage 2 kV Fixing mode By screws, mounting plate Clip-on, 35 mm symmetrical DIN rail Safety reliability data B10d = 20000 MTTFd = 21.6 years Product weight 0.33 lb(US) (0.15 kg) Environment Standards IEC 60947-1 IEC 60584-1 Product certifications GL CSA UL IP degree of protection IP20 terminal block IP50 housing Fire resistance 1562 F (850 C) conforming to IEC 60695-2-1 1562 F (850 C) conforming to UL Shock resistance 50 gn 11 ms conforming to IEC 60068-2-27 Vibration resistance 5 gn (f = 10...100 Hz) conforming to IEC 60068-2-6 Aug 11, 2019 1 The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.Resistance to electrostatic discharge 6 kV (in contact) conforming to IEC 61000-4-2 level 3 8 kV (in air) conforming to IEC 61000-4-2 level 3 Resistance to fast transients 1 kV on input-output conforming to IEC 61000-4-4 2 kV on power supply conforming to IEC 61000-4-4 Disturbance radiated/conducted CISPR 22 group 1 - class B CISPR 11 Ambient air temperature for storage -40...185 F (-40...85 C) Ambient air temperature for operation 32...122 F (0...50 C) (mounting side by side) 32...140 F (0...60 C) (2 cm spacing) Pollution degree 2 conforming to IEC 60664-1 Ordering and shipping details Category 22375 - INTERFACE MODULE(ABA,R,S) Discount Schedule CP2 GTIN 00785901839286 Nbr. of units in pkg. 1 Package weight(Lbs) 0.26000000000000001 Returnability N Country of origin ID Offer Sustainability California proposition 65 WARNING: This product can expose you to chemicals including: - - - - - - - Substance 1 Nickel compounds, which is known to the State of California to cause cancer, and - - - - - - - Substance 2 Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. - - - - - - - More information For more information go to www.p65warnings.ca.gov Contractual warranty Warranty period 18 months 2