Product data sheet RXM4AB1BDPVM Characteristics Harmony, Miniature plug-in relay pre- assembled, 6 A, 4 CO, with lockable test button, mixed terminals socket, 24 V DC Main Range of Product Harmony Electromechanical Relays Series name Miniature Product or Component Pre-assembled plug-in relay with socket Type Device short name RXM Contacts type and 4 C/O composition Uc control circuit 24 V DC voltage Ithe conventional 6A -40131F (-4055C) enclosed thermal current Status LED Without Control Type Lockable test button Utilisation coefficient 20 % Complementary Ui rated insulation voltage 250V IEC Uimp rated impulse withstand voltage 2.5kV 1.2/50 s Contacts material AgNi Ie rated operational current 3A 28 V DC) NC IEC 3A 250 V AC) NC IEC 6A 28 V DC) NO IEC 6A 250 V AC) NO IEC 6A 277 V AC) UL 8A 30 V DC) UL Minimum switching current 10mA Maximum switching voltage 250V Minimum switching voltage 17V Resistive rated load 6A 250 V AC 6A 28 V DC Maximum switching capacity 1500 VA/168 W AC/DC Minimum switching capacity 170 mW 10mA, 17V Operating rate <= 1200 cycles/hour under load <= 18000 cycles/hour no-load Mechanical durability 10000000cycles Electrical durability 100000cycles resistive Average coil consumption in W 0.9W, DC Drop-out voltage threshold >= 0.1 Uc DC Operate time 20 ms Release time 20ms Average coil resistance 650Ohm 20 C +/- 10 % Rated operational voltage limits 19.2...26.4 V DC Safety reliability data B10d = 100000 Protection category RT I Test levels Level A Operating position Any position Sale per indivisible quantity 30 CAD overall width 1.06in (26.9mm) Jan 23, 2022 1 The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.CAD overall height 3.11in (79mm) CAD overall depth 3.09in (78.45mm) Connections - terminals Connector, 1 x 0.25...1 x 2.5 mm AWG 22...AWG 14) flexible with cable end Connector, 2 x 0.25...2 x 1 mm AWG 22...AWG 17) flexible with cable end Connector, 1 x 0.5...1 x 2.5 mm AWG 20...AWG 14) solid without cable end Connector, 2 x 0.5...2 x 1.5 mm AWG 20...AWG 16) solid without cable end Torque Value 8.85lbf.in (1N.m) Net Weight 0.21lb(US) (0.096kg) Device presentation Complete product Environment Dielectric strength 1300V AC between contacts with micro disconnection 2000V AC between coil and contact 2000V AC between poles Product Certifications CE UL CSA EAC Lloyd s Standards UL 508 EN/IEC 61810-1 CSA C22.2 No 14 IEC 61984 Ambient Air Temperature for Storage -40185F (-4085C) Ambient air temperature for operation -40131F (-4055C) Vibration resistance 3 gn +/- 1 mm 10150Hz)5 cycles in operation 5 gn +/- 1 mm 10150Hz)5 cycles not operating IP degree of protection IP20 conforming to EN/IEC 60529 Shock resistance 10 gnin operation 30 gnnot operating Pollution degree 2 Ordering and shipping details Category 21127 - ZELIO ICE CUBE RELAYS Discount Schedule CP2 GTIN 3606489563127 Nbr. of units in pkg. 1 Package weight(Lbs) 3.25oz (92g) Returnability No Packing Units Unit Type of Package 1 PCE Package 1 Height 3.15in (8cm) Package 1 width 0.98in (2.5cm) Package 1 Length 3.15in (8cm) Offer Sustainability Sustainable offer status Green Premium product California proposition 65 WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov REACh Regulation REACh Declaration REACh free of SVHC Yes EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope) EU RoHS Declaration Toxic heavy metal free Yes Mercury free Yes 2