Product data sheet XPSAR371144P Characteristics module XPSAR - Emergency stop - 230 V AC Product availability: Non-Stock - Not normally stocked in distribution facility Main Range of product Preventa Safety automation Product or component Preventa safety module type Safety module name XPSAR Safety module applica- For emergency stop, switch and safety light curtain tion monitoring Function of module Monitoring of electro-sensitive protection equipment (ESPE) Emergency stop with 2 NC contacts monitoring 2- channel wiring Monitoring of a movable guard associated with 2 switches and automatic start Monitoring of a movable guard Emergency stop monitoring 1-channel wiring Multiple emergency stop monitoring 2-channel wiring Safety level Can reach PL e/category 4 conforming to EN/ISO 13849-1 Can reach SILCL 3 conforming to EN/IEC 62061 Safety reliability data DC > 99 % conforming to EN/ISO 13849-1 MTTFd = 277.8 years conforming to EN/ISO 13849-1 PFHd = 2.22E-9 1/h conforming to EN/IEC 62061 Type of start Configurable Connections - terminals Captive screw clamp terminals, removable terminal block, clamping capacity: 2 x 0.5...2 x 1.5 mm flexi- ble cable with cable end, with double bezel Captive screw clamp terminals, removable terminal block, clamping capacity: 1 x 0.2...1 x 2.5 mm flexi- ble cable with cable end, with double bezel Captive screw clamp terminals, removable terminal block, clamping capacity: 1 x 0.2...1 x 2.5 mm solid cable with cable end, with double bezel Captive screw clamp terminals, removable terminal block, clamping capacity: 1 x 0.25...1 x 2.5 mm flexi- ble cable with cable end, with double bezel Captive screw clamp terminals, removable terminal block, clamping capacity: 2 x 0.2...2 x 1 mm solid cable with cable end, with double bezel Captive screw clamp terminals, removable terminal block, clamping capacity: 2 x 0.2...2 x 1.5 mm flexi- ble cable with cable end, with double bezel Captive screw clamp terminals, removable terminal block, clamping capacity: 2 x 0.25...2 x 1 mm flexi- ble cable with cable end, with double bezel Output type Relay instantaneous opening 7 NO, volt-free Number of additional 2 NC + 4 solid state outputs circuits Us rated supply volt- 230 V AC (- 15...10 %) age 24 V DC (- 15...10 %) Complementary Synchronisation time between inputs 100 ms Supply frequency 50/60 Hz Power consumption in W <= 4 W DC Power consumption in VA <= 9 VA AC Input protection type Internal, electronic Time delay range 0...30 s Uc control circuit voltage 24 V DC Aug 10, 2019 1 The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.Line resistance 50 Ohm Breaking capacity C300: 360 VA, AC-15 (holding) relay output C300: 3600 VA, AC-15 (inrush) relay output Breaking capacity 20 mA at 24 V 2 A at 24 V (DC-13) time constant: 50 ms for relay output Output thermal current 10 A per relay relay output Ith conventional free air thermal current 40 A Associated fuse rating 10 A fuse type fast blow for relay output conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 200 6 A fuse type gG or gL for relay output conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 200 Minimum output current 170 mA for relay output Minimum output voltage 17 V relay output Response time on input open <= 20 ms Ui rated insulation voltage 300 V (degree of pollution: 2) conforming to DIN VDE 0110 part 1 300 V (degree of pollution: 2) conforming to IEC 60947-5-1 Uimp rated impulse withstand voltage 4 kV overvoltage category III conforming to IEC 60947-5-1 4 kV overvoltage category III conforming to DIN VDE 0110 part 1 Local signalling 4 LEDs Current consumption 30 mA at 24 V DC (on power supply) Mounting support 35 mm symmetrical DIN rail Product weight 0.88 lb(US) (0.4 kg) Environment Standards EN/ISO 13850 EN/IEC 60947-5-1 EN 1088/ISO 14119 EN/IEC 60204-1 Product certifications TV UL CSA IP degree of protection IP20 (terminals) conforming to EN/IEC 60529 IP40 (enclosure) conforming to EN/IEC 60529 Ambient air temperature for operation 14...131 F (-10...55 C) Ambient air temperature for storage -13...185 F (-25...85 C) Ordering and shipping details Category 22477 - SAFETY MODULES (PREVENTA) Discount Schedule SAF2 GTIN 00785901672159 Nbr. of units in pkg. 1 Package weight(Lbs) 0.88 Returnability N Country of origin ID Offer Sustainability California proposition 65 WARNING: This product can expose you to chemicals including: - - - - - - - Substance 1 Lead and lead compounds, which is known to the State of California to cause can- cer and birth defects or other reproductive harm. - - - - - - - More information For more information go to www.p65warnings.ca.gov Contractual warranty Warranty period 18 months 2