Product data sheet XPSATR3953C Characteristics module XPSATR - Emergency stop and protective guard - 115-230V AC, time delay 3s Product availability: Non-Stock - Not normally stocked in distribution facility Main Range of product Preventa Safety automation Product or component Preventa safety module type Safety module name XPSATR Safety module applica- For emergency stop and protective guard applica- tion tions Function of module Emergency stop monitoring 1-channel wiring Emergency stop monitoring 2-channel wiring Protective guard monitoring Safety level Can reach SILCL 3 conforming to EN/IEC 62061 time delay safety outputs Can reach PL e/category 4 conforming to EN/ISO 13849-1 instantaneous safety outputs Safety reliability data MTTFd = 85 years conforming to EN/ISO 13849-1 PFHd = 2E-9 1/h conforming to EN/IEC 62061 DC > 99 % conforming to EN/ISO 13849-1 Type of start Automatic Manual Connections - terminals Cage clamp terminals, removable terminal block Cage clamp terminals, removable terminal block, clamping capacity: 1 x 0.25...1 x 2.5 mm flexible ca- ble with cable end, with bezel Cage clamp terminals, removable terminal block, clamping capacity: 1 x 0.25...1 x 2.5 mm flexible ca- ble with cable end, without bezel Cage clamp terminals, removable terminal block, clamping capacity: 1 x 0.2...1 x 2.5 mm solid or flexi- ble cable without cable end Cage clamp terminals, removable terminal block, clamping capacity: 2 x 0.5...2 x 1 mm flexible cable with cable end, with bezel Output type Relay instantaneous opening 3 NO, volt-free Relay time delay opening 3 NO, volt-free Number of additional 1 NC circuits Us rated supply volt- 115...230 V AC (- 15...10 %) age Complementary Synchronisation time between inputs 1 s Supply frequency 50/60 Hz Power consumption in W 3.2 W AC Power consumption in VA <= 6.3 VA Input protection type Internal, electronic Time delay range 0.1...3 s Uc control circuit voltage 24 V DC Breaking capacity 3 A at 24 V (DC-13) for relay output Output thermal current 6 A instantaneous and time delay outputs Ith conventional free air thermal current 8 A Associated fuse rating 6 A fuse type gG for instantaneous and time delay outputs conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 200 Minimum output current 10 mA relay output Minimum output voltage 17 V relay output Response time on input open <= 20 ms Aug 10, 2019 1 The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. Ui rated insulation voltage 300 V Uimp rated impulse withstand voltage 4 kV overvoltage category III conforming to EN/IEC 60947-5-1, DIN VDE 0110 parts 1 & 2 Local signalling 5 LEDs Mounting support 35 mm symmetrical DIN rail Environment Standards EN 60204-1 EN/IEC 60947-5-1 EN/IEC 61496-1 EN/ISO 13849-1 EN 62061 EN 50156-1 Product certifications CSA TV UL IP degree of protection IP20 (terminals) conforming to EN/IEC 60529 IP40 (enclosure) conforming to EN/IEC 60529 Ambient air temperature for operation -13...131 F (-25...55 C) Ambient air temperature for storage -13...167 F (-25...75 C) Ordering and shipping details Category 22477 - SAFETY MODULES (PREVENTA) Discount Schedule SAF2 GTIN 003389119061513 Nbr. of units in pkg. 1 Package weight(Lbs) 0.77000000000000002 Returnability N Country of origin DE Offer Sustainability California proposition 65 WARNING: This product can expose you to chemicals including: - - - - - - - Substance 1 Lead and lead compounds, which is known to the State of California to cause can- cer and birth defects or other reproductive harm. - - - - - - - More information For more information go to www.p65warnings.ca.gov Contractual warranty Warranty period 18 months 2