Product data sheet ZBRA1 Characteristics Relay Antenna, AC/DC, 5m cable output Product availability: Stock - Normally stocked in distribution facility Main Range of product Harmony XB5R Product or component Wireless and batteryless range type Device short name ZBRA Product destination Wireless Schneider Electric ecosystem devices Control station applica- Transceiver (emission and reception) tion Colour of base of enclo- Black RAL 9011 sure Colour of cover Transparent Material Polycarbonate Frequency 2405 MHz for transmitter 2405 MHz for receiver Emission class 5M00G7W Antenna type Omnidirectional Complementary Communication port protocol Zigbee green power at 2.4 GHz conforming to IEEE 802.15.4 Antenna gain 0 dBi Maximum sensing distance 300 m transmitter in box type XAL D, receiver in metal enclosure and use re- lay-antenna Emission power <= 3 mW Us rated supply voltage 24...240 V AC/DC 50/60 Hz - 10...10 % Power consumption in W <= 4 W AC/DC Operating position Vertical Status LED 1 LED green power ON 1 LED green emission signal Overvoltage category III conforming to IEC 60664-1 Rated short-duration power frequency withstand volt- 4 kV 50 Hz conforming to EN/IEC 60947-5-1 age Uimp rated impulse withstand voltage 4 kV Electrical connection 2 conductors cable flexible with 16.4 ft (5 m) length, cross section: 0 in (0.34 mm) conforming to EN/IEC 60947-1 Tightening torque 5.31 lbf.in (0.6 N.m) conforming to EN/IEC 60947-1 Housing material Self-extinguishing plastic Short-circuit protection 0.4 A fuse fast blow Max power consumption in W 1 mW Number of channels 1 Modulation technique O-QPSK Bandwidth 5 MHz Product weight 0.44 lb(US) (0.2 kg) Environment Ambient air temperature for storage -40...158 F (-40...70 C) Relative humidity 90 % at -4...131 F (-20...55 C) without condensation conforming to ETSI EN 300 440-1 Electrical shock protection class Class II conforming to IEC 61140 IP degree of protection IP65 conforming to IEC 60529 at 131 F (55 C), 0.1 m Pollution degree 3 conforming to IEC 60664-1 Aug 11, 2019 1 The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.IK degree of protection IK03 conforming to EN 50102 Radio agreement RSS SRRC ANATEL, type III conforming to ETSI EN 301 489-3 ARIB T66, class 2 conforming to ETSI EN 301 489-3 FCC, category 2 conforming to ETSI EN 300 440-1 ICASA, category 1 conforming to ETSI EN 300 440-1 Product certifications GOST CCC C-Tick CE BT 2006/95/EC CSA UL Directives 1999/5/EC - R&TTE directive 2004/108/EC - electromagnetic compatibility Vibration resistance 6 gn (f = 55...150 Hz) conforming to IEC 60068-2-6 +/-0.5 mm (f = 10...55 Hz) conforming to IEC 60068-2-6 Shock resistance 25 gn (duration = 6 ms) 6000 shocks conforming to IEC 60068-2-27 15 gn (duration = 11 ms) half sine wave acceleration conforming to IEC 60068-2-27 Insulation resistance > 500 MOhm at 500 V DC conforming to NF C 20030 Ui rated insulation voltage 250 V conforming to IEC 60664-1 Electromagnetic compatibility Conducted emission conforming to EN 300-489-1 Conducted and radiated emissions, class B conforming to CISPR 22 Radiated emission conforming to ETSI EN 300 440-1 Conducted emission conforming to ETSI EN 300 489-3 Radiated emission conforming to ETSI EN 300 440-2 Electrostatic discharge immunity test (test level: 8 kV - in free air (in insulating parts)) conforming to IEC 61000-4-2 Electrostatic discharge immunity test (test level: 6 kV - on contact (on metal parts)) conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields (test level: 10 V/m - 80...2000 MHz) con- forming to IEC 61000-4-3 Susceptibility to electromagnetic fields (test level: 3 V/m - 80...2700 MHz, dis- tance = 20 m) conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test (test level: 2 kV conforming to IEC 61000-4-4 1.2/50 s shock waves immunity test (test level: 1 kV - differential mode) con- forming to IEC 61000-4-5 1.2/50 s shock waves immunity test (test level: 2 kV - common mode) conform- ing to IEC 61000-4-5 Conducted RF disturbances (test level: 10 V conforming to IEC 61000-4-6 Immunity for industrial environments conforming to EN/IEC 61000-6-2 Immunity to microbreaks and voltage drops conforming to IEC 61000-4-11 Ordering and shipping details Category 22470 - XB5R WIRELESS PUSH BUTTON Discount Schedule I GTIN 00785901461531 Nbr. of units in pkg. 1 Package weight(Lbs) 0.55000000000000004 Returnability Y Country of origin ID Offer Sustainability Sustainable offer status Green Premium product RoHS (date code: YYWW) Compliant - since 1129 - Schneider Electric declaration of conformity Schnei- der Electric declaration of conformity REACh Reference not containing SVHC above the threshold Product environmental profile Available Product end of life instructions Available California proposition 65 WARNING: This product can expose you to chemicals including: - - - - - - - Substance 1 Nickel compounds, which is known to the State of California to cause cancer, and - - - - - - - Substance 2 Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. - - - - - - - More information For more information go to www.p65warnings.ca.gov 2