DIN Rail Mount DataSheet SeriesOne DR Dual Series ATEX Dual Output with Ratings of 6 Amps each channel Load voltage ratings of 24-280 VAC and 48-600 VAC Fits standard 35mm DIN Rail LED input status indicator DC control (4-32 V) Zero Voltage (resistive loads) or Instantaneous (inductive loads) turn-on output UL and cUL Listed, HP Rated (General Purpose and Motor Control) UL 508 Endurance Rating for Enhanced Reliability UL Class I and II, Division 2, for Hazardous Locations PRODUCT SELECTION Control Voltage 280 V, 6 A 600 V, 6 A 4-32 VDC DRD24D06X DRD48D06X AVAILABLE OPTIONS Operating Voltage Switching Type 24: 24-280 VAC Rated Load Current Blank: Zero Voltage Turn-On R: Instantaneous Turn-On Series 48: 48-600 VAC 06: 6 Amps DRD 24 D 06 X R Control Voltage Agency Approvals X: ATEX II 3G Ex nA IIC T4 Gc D: 4-32 VDC approved Required for valid part number For options only and not required for valid part number (1) OUTPUT SPECIFICATIONS AC Output Description DRD24D06X DRD48D06X Operating Voltage (47-63Hz) Vrms 24-280 48-600 Transient Overvoltage Vpk 600 1200 Maximum Load Current per channel, resistive mArms (2) 6 6 Minimum Load Current mArms 150 150 Maximum Off-State Leakage Current Rated Voltage mArms 0.1 0.25 Minimum Off-State dv/dt Maximum Rated Voltage V/sec (3) 500 500 Maximum On-State Voltage Drop Rated Current Vpk 1.3 1.3 Maximum Surge Current (50/60Hz, 1 cycle) Apk 715/750 715/750 Maximum It for Fusing (50/60 Hz, 1/2 cycle) A sec 2560/2330 2560/2330 HP Rating UL 508/IEC60947 HP (KW) 240V 1/2 (.37) 1/2 (.37) HP Rating UL 508/IEC60947 HP (KW) 380V N/A 1 (.75) HP Rating UL 508/IEC60947 HP (KW) 480V N/A 2 (1.5) Minimum Power Factor (at Maximum Load) 0.5 0.5 Min/Max stranded wire 22/14 AWG 22/14 AWG Min/Max solid wire 22/14 AWG 22/14 AWG FDE-07-01 REV. A Do not forget to visit us at: www.crydom.com Copyright 2017 Crydom Inc. Specifications subject to change without notice.DIN Rail Mount DataSheet (1) INPUT SPECIFICATIONS Description DRDxxD06X Control Voltage Range Vdc (4) 4.0-32 Minimum Turn-On Voltage Vdc 1.0 Must Turn-Off Voltage Vdc 4.0 Minimum Input Current for mA (5) 9 Maximum Input Current for mA (5) 11 Maximum Turn-on Time msec (6) 1/2 Cycle Maximum Turn-off Time msec 1/2 Cycle Min/Max stranded/solid wire 22/16 AWG (1) GENERAL SPECIFICATIONS Description Parameters Dielectric Strength, Input/Output/Base (50/60Hz) 2500 Vrms 9 10 Ohm Minimum Insulation Resistance ( 500 VDC) Maximum Capacitance, Input/Output 10 pF Ambient Operating Temperature Range -20 to 40 C Ambient Storage Temperature Range -30 to 100 C Recommended Terminal Screw Torque Range 4.4-7.0 in-lb (0.5-0.8Nm) Weight (Typical) 3.17 oz (90g) GENERAL NOTES (1) All parameters at 25C unless otherwise specied. (2) See Derating curves (3) Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1 (4) DC control includes reverse polarity protection. (5) Input circuitry incorporates active current limiter. (6) Turn-on time for DC control random turn-on versions is 0.1 msec. Standards of Compliance IEC 62314 LC A, Resistive or Slightly Inductive Load Ratings: 6 A per channel 40C ambient for DRD24D06X, 6 A per channel 40C ambient for DRD48D06X LC B, Motor Loads Ratings: 0.375KW 240 VAC for DRD24x06X and 1.5KW 480VAC DRD48x06X Shock and Vibration (Applies to all part numbers) Vibration Resistence according to IEC 60068-2-6: 0.35mm and 0.75mm Amplitude over 10-55 Hz Shock Resistance according to IEC 60068-2-27: 15g/11ms EMC (Applies to all part numbers) IEC 61000-4-2: Electrostatic Discharge- Level 3 IEC 61000-4-4: Electrically Fast Transients- Level 3 IEC 61000-4-5: Electrical Surges- Level 3 ANSI / ISA 12.12.01-2013 Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Division 1 and 2 Hazadous (classied) locations This equipment is open-type device and is meant to be installed in an enclosure suitable for the enviroment such that the equipment is only accesible with the use of a tool suitable for use in Class 1, Division 2, Group A,B,C and Hazardous locations, or Nonhazardous locations only WARNING-Explosion Hazard- Do not disconnect equipment while the circuit is live or unless the area is known to be free of ignitable concentrations WARNING-Explosion Hazard- Substitution of any component may impair suitability for class I, Division 2 ATEX Compliance with Essential Health and Safety Requirements has been assessed by reference to Standards EN 60079-0:2012+A11:2013 and EN 60079-15-:2012 Do not forget to visit us at: www.crydom.com Copyright 2017 Crydom Inc. Specifications subject to change without notice.