Panel Mount
Datasheet
H16WD Series
Ratings from 25A to 90A @ 48-690 VAC DC control
1600 Volts Blocking Direct Bond Copper substrate
SCR output for heavy industrial loads EMC Compliant to Level 3
Zero voltage or instantaneous turn-on outputs Direct Power Lead Frame
UL/CSA/VDE Approved, CE Compliant to EN60950-1 Epoxy Free Design
Improved SEMS screw and washer
Redesigned housing with anti-rotation barriers
For Generation 3 datasheet click here
PRODUCT SELECTION
Control Voltage 25A 50A 75A 90A
4-32 Vdc H16WD6025 H16WD6050 H16WD6075 H16WD6090
AVAILABLE OPTIONS
Rated Load Current
25: 25 Amps
50: 50 Amps Input Status LED Switching Type
Transient Overvoltage 75: 75 Amps Blank: Not Included Blank: Zero Voltage Turn-On
Series 6WD: 1600 Vpk 90: 90 Amps G: Included -10: Instantaneous Turn-On
(3)
H1 6WD 60 25 K G H -10
Operating Voltage Termination Thermal Pad
60: 48-690 VAC Blank: Screw Blank: Not Included
F: Quick Connect (1) H: Included
Required for valid part number
(Up to 50 Amps models)
For options only and not required for valid part number
(2)
K: Hex standoffs
* Not all part number combinations are available.
Contact Crydom Technical Support for informacion on
the availability of a specific part number.
(4)
OUTPUT SPECIFICATIONS
Description 25A 50A 75A 90A
Operating Voltage (47-440Hz) [Vrms] 48-690 48-690 48-690 48-690
Transient Overvoltage [Vpk] 1600 1600 1600 1600
Rated Load Current [Arms] (5)(2) 25 50 75 90
Rated Load Current {UL508 Motor Controller} [Arms] (5) 10 20 30 45
Minimum Load Current [mArms] 150 150 150 150
Maximum Off-State Leakage Current @ Rated Voltage [mArms] 1.0 1.0 1.0 1.0
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/sec] 500 500 500 500
Maximum 1 Cycle Surge Current (50/60Hz) [Apk] 239/250 597/625 954/1000 1145/1200
Maximum It for Fusing (50/60Hz) [A sec] 285/259 1779/1621 4555/4150 6560/5976
Thermal Resistance Junction to Case (Rjc) [C/W] 0.8 0.45 0.3 0.27
Maximum On-State Voltage Drop @ Rated Current [Vrms] 1.3 1.3 1.2 1.2
HP rating UL 508/IEC60947[HP (KW)]: 240 VAC 1.5 (1.1) 3 (2.2) 5 (3.7) 7.5 (5.6)
HP rating UL 508/IEC60947[HP (KW)]: 380 VAC 2 (1.5) 5 (3.7) 7.5 (5.6) 15 (11.2)
HP rating UL 508/IEC60947[HP (KW)]: 480 VAC 3 (2.2) 5 (3.7) 10 (7.4) 20 (14.9)
HP rating UL 508/IEC60947[HP (KW)]: 600 VAC 3 (2.2) 10 (7.4) 15 (11.2) 25 (18.6)
Minimum Power Factor (at Maximum Load) 0.5 0.5 0.5 0.5
Do not forget to visit us at: www.crydom.com
Copyright 2016 Crydom Inc. Specifications subject to change without notice.Panel Mount
Datasheet
(4)
INPUT SPECIFICATIONS
Description DC Control
Control Voltage Range 4-32 VDC
Minimum Turn-On Voltage (6) 4.0 VDC
Must Turn-Off Voltage 1.0 VDC
Maximum Reverse Voltage -32 VDC
Minimum Input Current @ Minimum Voltage (for on-state) 7mA
Maximum Input Current @ Maximum Voltage 12mA
Nominal Input Impedance Current Regulated
Maximum Turn-On Time [msec] (7) 1/2 Cycle
Maximum Turn-Off Time [msec] 1/2 Cycle
(4)
GENERAL SPECIFICATIONS
Description Parameters
Dielectric Strength, Input/Output/Base (50/60Hz) 4000 Vrms
9
Minimum Insulation Resistance (@ 500 VDC)
10 Ohm
Maximum Capacitance, Input/Output 8 pF
Ambient Operating Temperature Range -30 to 80 C
Ambient Storage Temperature Range -40 to 125 C
Weight (typical) 2.6 oz (74.9 g)
Housing Material UL 94 V-0
SSR Mounting Torque Range [in lbs/Nm] 18-20 (2-2.2)
Baseplate Material Aluminum
Input Terminal Screw Torque Range [in-lb/Nm] 13-15 /1.5-1.7
Output Terminal Screw Torque Range [in lb/Nm] 18-20 (2-2.2)
SSR Mounting Screw Torque Range [in-lb/Nm] 18-20 / 2.0-2.2
Input/Load Terminal Screw Torque Range [in-lb/Nm] (2) w/K option 8-10 / 0.9-1.13
Input/Output Terminal Screw Thread Size #6-32 UNC / #8-32 UNC
Humidity per IEC60068-2-78 93% non-condensing
LED Input Status Indicator w/G option (green)
11,641,553 hours (1,328 years)
MTBF (Mean Time Between Failures) at 40C ambient temperature (8)
7,210,376 hours (823 years)
MTBF (Mean Time Between Failures) at 60C ambient temperature (8)
WIRING DIAGRAM
AC
Input Current vs Input Voltage
Recommended Wire Sizes
V
Standard Regulated DC Input
Wire Size Wire Pull-Out
25
Terminals
(Solid / Stranded) Strength (lb)[N]
Load (9)
20
2
24 AWG (0.2 mm ) / 0.2 [minimum]
10 [44.5]
Input
1 ( ) 2 ( )
2 15
2 x 12 AWG (3.3 mm ) / 3.3 [maximum] 90 [400]
2
10
20 AWG (0.5 mm ) / 0.518 [minimum] 30 [133]
Output 2
2 2 x 10 AWG (5.3 mm ) / 5.3
1 OUTPUT 110 [490] 5
S OL I D S T A T E R EL A Y
2
2 x 8 AWG (8.4 mm ) / 8.4 [maximum] 90 [400]
0
0 5 10 15 20 25 30
4 INPUT 3
DC Input Voltage
4 () 3 (+)
EQUIVALENT CIRCUIT BLOCK DIAGRAM
4 1
-DC AC
(10)
Trigger
Circuit
+DC 3 2 AC
Current
Limiter
Do not forget to visit us at: www.crydom.com
Copyright 2016 Crydom Inc. Specifications subject to change without notice.
Input Current (mA)