SC-ISOSLICE-1 ISOLATED BUS I/O MODULE 2 off Universal Isolated Analogue I/O Communicates to Ethernet / RS232 or RS485 network via an SC-E-100 unit Inter-channel & Input/Output Isolation Automatic Bus & Power Connection Via DIN Rail Bus Connector Robust System with High MTBF Very High Accuracy, Low Cost Input Types for SC-ISOSLICE-1 Outputs DC/AC Current & Voltage For Output Modules see SC-ISOSLICE-6 or 0-20mA, 4-20mA, 0-10mA into 15 SC-ISOSLICE-8 0-1V, 0-10V, 1-5V into 1M Min & Max Full Scale Ranges are: DC Current 0 - 1mA 0 - 20mA DC Voltage 0 - 25mV 0 - 30V Bipolar DC Voltage 25mV 10V 3 Wire Pot 0 - 10k 0 - 100k The SC-ISOSLICE-1 isolated Bus I/O module combines full three-port isolation with Thermocouples access to an industrial bus. This bus Types E,J,K,N,R,S,T,B linearised or non-linearised. Ranges: Wide range of inputs. Cold junction connects to the SC-E-100 modules which compensation. Upscale or downscale t/c burnout options. For 4-channel t/c input specify SC- are then used to transmit the process ISOSLICE-4 values via either an Ethernet or a RS232/485 wired communications network. Technical Specifications Full 3-port isolation is standard as is an Parameter Min Typ Max Comments isolated transmitter supply which can be Supply Voltage 12V 24V 36Vdc used to power any standard 2-wire 4-20mA Supply Current (mA) 45 90 For 24Vdc supply (260mA for 50ms on start-up) transmitter. Bus Connection 16-bit bus connection Volt Drop (mA input) 0.3 At 20mA Input The input type and range can be user Input Impedance (Volt) 1M Dependant on range (typ=10V) selected using simple DIL switches inside Input Impedance (mA) 15 Dependant on range (typ=20mA) the unit. All Thermocouple inputs are fully Output Linearity Error 0.01% 0.05% linearised. Temp Coefficient 50ppm/C Time Constant (10-90%) 200mS Non-interactive zero and span controls Operating Ambient 0C 55C make adjustment and calibration of the Relative Humidity 0% 90% unit quick and simple. see note Isolation Voltage 1kV Surge Voltage 2.5kV for 50S Transient of 10kV/S The units have a wide ranging 12 to 36 Vdc. Notes Absolute maximum ratings indicate sustained limits beyond which damage to the device may occur. This supply can either be wired to the Device is protected against reverse polarity connection. appropriate terminals or picked up Accuracy figures based on 24Vdc supply, 4-20mA output with 250 load and an ambient 20C. automatically from the Bus connector. Installation Data Mounting DIN Rail TS35 Orientation Any Universal mAorV Analogue Digital Digital Connections Screw Clamp with pressure plate Part Number Inputs RTDInputs T/CInputs Outputs Inputs Outputs Inputs Conductor Size 0.5-4.0mm SC-ISOSLICE-1 2 Insulation Stripping 12mm SC-ISOSLICE-2 8 SC-ISOSLICE-3 4 Weight Approx 95g SC-ISOSLICE-4 4 Ordering Information SC-ISOSLICE-5 8 Part No.: SC-ISOSLICE-1 SC-ISOSLICE-6 4 SC-ISOSLICE-7 2xfreqin Cynergy3 Components Ltd. SC-ISOSLICE-8 4 SC-ISOSLICE-9 4xACI/V 7 Cobham Road Ferndown Industrial Estate Wimborne, Dorset BH21 7PE Telephone +44 (0) 1202 897969 Email:sales cynergy3.com ISO9001CERTIFIED SC-ISOSLICE-1 2017 www.cynergy3.com Made in the UK 2017 Cynergy3 Components, All Rights Reserved. Specifications are subject to change without prior notice. Cynergy3 Components and the Cynergy3 Components logo are trademarks of Cynergy3 Components Limited.X-ON Electronics Largest Supplier of Electrical and Electronic Components Click to view similar products for I/O Modules category: Click to view products by Sensata manufacturer: Other Similar products are found below : 70L-IDC5S 70L-OAC-L 70Z3289-4 G21960000700 G21960002700 G34960002700 OACU C4SWOUT PB16H G34960001700 G3TA- OA101SZ-1 DC24 G77-S 5607189 DA5 ODC-24A IDC5P FC6A-N16B1 6421 70MRCQ32-HL G3TAOD201SDC24 C200H-LK201-V1 G3TA-OA202SZ-US DC12 GT1-OD16 GT1-AD04CST B7AM-6BS 70GRCQ24-HS 6422 84110410 GT1-OD16MX G7VC-OC16-B7 70MRCK24-DIN 6202 6402 PI/NI-2D/24 FC6A-J2C1 FC6A-KC1C FC6A-R081 FC6A-J8CU1 GP32900003700 641-480-5022 PB16H 84145010 84110210 FRUSB1601 PCL-720+-BE FRRJ451601 AP24MX3DB25F ADAM-5053S-AE WISE-S614-A C200H-OD211