Data sheet 6EP3310-6SB00-0AY0 LOGO POWER 5 V/3 A LOGO POWER 5 V / 3 A stabilized power supply input: 100-240 V AC output: 5 V / 3 A DC Input Input 1-phase AC or DC Rated voltage value Vin rated 100...240V Voltage range AC 85...264V Input voltage 110...300V at DC Wide-range input Yes Mains buffering at Iout rated, min. 40ms at Vin = 187 V Rated line frequency 1 50Hz Rated line frequency 2 60Hz Rated line range 47...63Hz Input current 0.36A at rated input voltage 120 V 0.22A at rated input voltage 230 V Switch-on current limiting (+25 C), max. 26A It, max. 0.8As Built-in incoming fuse internal Protection in the mains power input (IEC 898) Recommended miniature circuit breaker: from 6 A characteristic B or from 2 A characteristic C 6EP3310-6SB00-0AY0 Subject to change without notice 11/08/2017 Copyright Siemens Page 1/4Output Output Controlled, isolated DC voltage Rated voltage Vout DC 5V Total tolerance, static 3% Static mains compensation, approx. 0.1% Static load balancing, approx. 0.1% Residual ripple peak-peak, max. 100mV Residual ripple peak-peak, typ. 30mV Spikes peak-peak, max. (bandwidth: 20 MHz) 100mV Spikes peak-peak, typ. (bandwidth: 20 MHz) 50mV Adjustment range 4.6...5.4V Product function Output voltage adjustable Yes Output voltage setting via potentiometer Status display Green LED for output voltage OK On/off behavior No overshoot of Vout (soft start) Startup delay, max. 0.5s Voltage rise, typ. 100ms Rated current value Iout rated 3A Current range 0...3A +55 ... +70 C: Derating 2%/K Note Supplied active power typical 15W Parallel switching for enhanced performance Yes Numbers of parallel switchable units for enhanced 2 performance Efficiency Efficiency at Vout rated, Iout rated, approx. 76% Power loss at Vout rated, Iout rated, approx. 5W Power loss W during no-load operation maximum 0.3W Closed-loop control Dynamic mains compensation (Vin rated 15 %), 0.2% max. Dynamic load smoothing (Iout: 10/90/10 %), Uout 5% typ. Load step setting time 10 to 90%, typ. 1ms Load step setting time 90 to 10%, typ. 1ms Protection and monitoring Output overvoltage protection Yes, according to EN 60950-1 Current limitation, typ. 3.8A Property of the output Short-circuit proof Yes Short-circuit protection Constant current characteristic Enduring short circuit current RMS value 3.8A maximum 6EP3310-6SB00-0AY0 Subject to change without notice 11/08/2017 Copyright Siemens Page 2/4