Industrial Control Transformers
International Series Control Transformers: 50 - 750 VA
Electromagnetic control components demand inrush
currents up to 10 times the transformers nominal rating
without sacrificing secondary voltage stability beyond
practical limits. The International series transformers fully
comply with IEC and NEMA standards and are available
with IEC touchproof covers (IP20).
Features
Epoxy encapsulated for cooler operation
Interleaved copper windings to reduce impedence
50/60 Hz
55C Rise, 105C insulation system for harsh,
heavy duty applications
Exceeds IEC, NEMA, ANSI, NMTBA, JIC and
automotive standards
Certifications and Compliances
E77014
Listed: E77014 - Type SBE
- UL 5085-1, UL 5085-2
- CSA C22.2 No. 66.1, No. 66.2
- IEC/EN 61558-1, IEC/EN 61558-2-2
RoHS Compliant
FIELD INSTALLED OPTIONS
CATALOG NUMBER
DESCRIPTIONS
Related Products
DIN Circuit Breaker Mounting
DIN Rail Power Supplies
SBEDIN
Field installed IEC fuse holder adaptor
63 Series Power Conditioners
kit
Surge Protective Devices
Terminal Covers (Two Covers Per Kit)
IP20
Field installed primary and secondary
IEC Touch Proof Cover Kit.
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
194
January 2017Industrial Control Transformers
Selection Tables: International Series
Group 1 -/220/380 V Primary, 110/23 V Secondary, 50/60 Hz
208/240/415 V Primary, 120/24 V Secondary, 50/60 Hz
200/230/400 V Primary, 115/24 V Secondary, 50/60 Hz
Approx.
Continuous Instantaneous Catalog Height Width Depth Mtg Width Mtg Depth Slot Size
Ship Weight
VA VA Number in (mm) in (mm) in (mm) W1 / W2 - in (mm) D1 / D2 - in (mm) S1/S2 - in (mm)
lbs (kg)
2.96 3.39 4.36 2.81 / 2.50 2.10 / N/A .20 x .50 / .20 x .50
50 105 4.0 (1.82)
E050TC
(75.2) (86.1) (110.7) (71.4 / 63.5) (53.3 / N/A) (5.1 x 12.7 / 5.1 x 12.7)
3.89 4.50 4.48 3.74 / 3.12 2.56 / 2.87 .20 x .65 / .20 x .33
100 230 8.0 (3.67)
E100TC
(98.8) (114.3) (113.8) (95.0 / 79.3) (65.0 / 72.9) (5.1 x 16.5 / 5.1 x 8.4)
3.89 4.50 5.21 3.74 / 3.12 3.29 / 3.61 .20 x .65 / .20 x .33
150 420 E150TC 11.0 (5.00)
(98.8) (114.3) (132.3) (95.0 / 79.3) (83.6 / 91.7) (5.1 x 16.5 / 5.1 x 8.4)
4.53 5.25 5.07 4.38 / 3.75 3.54 / N/A .31 x .85 / .31 x .85
250 675 15.0 (6.82)
E250TC
(115.1) (133.4) (128.8) (111.3 / 95.3) (89.9 / N/A) (7.9 x 21.6 / 7.87 x 21.6
5.56 6.38 6.93 5.32 / 4.37 4.25 / 5.75 .31 x .03 / .31 x .85
500 1550 30.0 (13.64)
E500TC
(141.2) (162.1) (176.0) (135.1 / 111.0) (108.0 / 146.1) (7.9 x .85 / 7.9 x 21.6)
Group 2 208/240/415 V Primary, 24 V Secondary, 50/60 Hz
277/480 V Primary, 24 V Secondary, 60 Hz
200/230/400 V Primary, 24 V Secondary, 50/60 Hz
220/380 V Primary, 23 V Secondary, 50/60 Hz
Mtg Width Mtg Depth Approx.
Continuous Instantaneous Catalog Height Width Depth Slot Size
W1 / W2 D1 / D2 Ship Weight
VA VA Number in (mm) in (mm) in (mm) S1/S2 - in (mm)
in (mm) in (mm) lbs (kg)
2.96 3.39 4.36 2.81 / 2.50 2.10 / N/A .20 x .50 / .20 x .50
50 105 4.0 (1.82)
E050TE
(75.2) (86.1) (110.7) (71.4 / 63.5) (53.3 / N/A) (5.1 x 12.7 / 5.1 x 12.7)
3.89 4.50 4.48 3.74 / 3.12 2.56 / 2.87 .20 x .03 / .20 x .01
100 230 8.0 (3.67)
E100TE
(98.8) (114.3) (113.8) (95.0 / 79.3) (65.0 / 72.9) (5.1 x .65 / 5.1 x .33)
3.89 4.50 5.21 3.74 / 3.12 3.29 / 3.61 .20 x .03 / .20 x .01
150 420 11.0 (5.00)
E150TE
(98.8) (114.3) (132.3) (95.0 / 79.3) (83.6 / 91.7) (5.1 x .65 / 5.1 x .33)
4.53 5.25 5.07 4.38 / 3.75 3.54 / N/A .30 x .71 / .30 x .71
250 700 15.0 (6.82)
E250TE
(115.1) (133.4) (128.8) (111.3 / 95.3) (89.9 / N/A) (7.9 x 18.0 / 7.9 x 18.0)
5.56 6.38 6.93 5.32 / 4.37 4.25 / 5.75 .30 x .85 / .30 x .85
500 1550 E500TE 30.0 (13.64)
(141.2) (162.1) (176.0) (135.1 / 111.0) (108.0 / 146.1) (7.9 x 21.6 / 7.9 x 21.6)
Note: Instantaneous VA calculated at At 50% PF (Power Factor), 95% Nominal Secondary Voltage.
Design Style
Mounting Dimensions Profile Top View
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
195
January 2017