Power Protection and Conditioning
1
MCR Hardwired Series Power Line Conditioning with Voltage Regulation
The MCR Hardwired Series provides excellent noise
filtering and surge protection to safeguard connected
equipment from damage, degradation or misoperation.
Combined with the excellent voltage regulation inherent to
SolaHDs ferroresonant design, the MCR can increase the
actual Mean Time Between Failure (MTBF) of protected
equipment. The MCR is a perfect choice where dirty power,
caused by impulses, swell, sags, brownouts and waveform
distortion can lead to costly downtime because of damaged
E47379
LR044950
equipment.
Certifications and Compliances
Applications
All Models
Industrial automation and control equipment PLCs
RoHS Compliant
Machine tools
Selection Table: Group 2
Computer loads and electronic equipment
Listed (120VA-5kVA Units)
Robotics
- UL 1012, CSA C22.2 No. 107.1
Semiconductor fabrication equipment
Listed (7.5kVA-15kVA Units)
Features
- UL 1012
3% output voltage regulation
Selection Table: Group 3
Noise attenuation
- 120 dB common mode Listed (500VA-3kVA Units)
- 60 dB transverse mode
- UL 1012, CSA C22.2 No. 107.1
Surge protection tested to ANSI/IEEE
Certified (5kVA-15kVA Units)
C62.41 Class A & B Waveform:
- CSA C22.2 No. 107.1
- <10 V let through typical
Selection Table: Group 4
Acts as a step-up or step-down transformer
Harmonic filtering
Listed
Hardwired
- UL 1012, CSA C22.2 No. 107.1
Galvanic isolation provides exceptional circuit protection
Related Products
25 year typical MTBF On-line UPS (S4K Industrial)
No maintenance required Surge Protection
Three Phase Power Conditioners
Selection Tables: Single Phase
Active Tracking Filters
Group 2 MCR Series, 60 Hz Only
Height Width Depth Ship Weight Design Elec
VA Catalog Number Voltage Input Voltage Output
in (mm) in (mm) in (mm) lbs (kg) Style Conn
120 63-23-112-4 120, 208, 240, 480 120 9.00 (228.6) 4.00 (101.6) 5.00 (127.0) 15.0 (6.80) 1 D
250 120, 208, 240, 480 120 10.00 (254.0) 6.00 (152.4) 8.00 (203.2) 27.0 (12.25) 1 D
63-23-125-4
500 120, 208, 240, 480 120, 208, 240 13.00 (330.2) 9.00 (228.6) 7.00 (177.8) 37.0 (16.78) 1 E
63-23-150-8
750 120, 208, 240, 480 120, 208, 240 14.00 (355.6) 9.00 (228.6) 7.00 (177.8) 52.0 (23.60) 1 E
63-23-175-8
1000 * 120, 208, 240, 480 120, 208, 240 17.00 (431.8) 9.00 (228.6) 7.00 (177.8) 62.0 (28.12) 1 E
63-23-210-8
1500 * 120, 208, 240, 480 120, 208, 240 17.00 (431.8) 13.00 (330.2) 9.00 (228.6) 95.0 (43.10) 1 E
63-23-215-8
2000 * 120, 208, 240, 480 120, 208, 240 18.00 (457.2) 13.00 (330.2) 9.00 (228.6) 109.0 (49.44) 1 E
63-23-220-8
3000 * 120, 208, 240, 480 120, 208, 240 19.00 (482.6) 13.00 (330.2) 9.00 (228.6) 142.0 (64.41) 1 E
63-23-230-8
5000 * 120, 208, 240, 480 120, 208, 240 28.00 (711.2) 13.00 (330.2) 9.00 (228.6) 222.0 (100.70) 1 E
63-23-250-8
7500 208, 240, 480 120, 208, 240 27.00 (685.8) 26.00 (660.4) 9.00 (228.6) 362.0 (164.20) 2 F
63-28-275-8
10000 208, 240, 480 120, 208, 240 28.00 (711.2) 26.00 (660.4) 9.00 (228.6) 446.0 (202.30) 2 F
63-28-310-8
15000 208, 240, 480 120, 208, 240 28.00 (711.2) 38.00 (965.2) 10.00 (254.0) 710.0 (322.05) 3 F
63-28-315-8
* Canadian option: units must be ordered by changing -8 (UL only) to -C8.
Contact Technical Services at (800) 377-4384 with any questions.
44
Visit our website at www.solahd.com. Power Protection and Conditioning
1
Selection Tables: Single Phase
Group 3 MCR Series, 60 Hz Only
Height Width Depth Ship Weight Design Elec
VA Catalog Number Voltage Input Voltage Output
in (mm) in (mm) in (mm) lbs (kg) Style Conn
500 600 120, 208, 240 13.00 (330.2) 9.00 (228.6) 7.00 (177.8) 38.0 (17.24) 1 B
63-31-150-8
1000 600 120, 208, 240 17.00 (431.8) 9.00 (228.6) 7.00 (177.8) 62.0 (28.12) 1 B
63-32-210-8
2000 600 120, 208, 240 18.00 (457.2) 13.00 (330.2) 10.00 (254.0) 109.0 (49.44) 1 B
63-32-220-8
3000 600 120, 208, 240 19.00 (482.6) 13.00 (330.2) 10.00 (254.0) 142.0 (64.41) 1 B
63-32-230-8
5000 208, 240, 480, 600 120, 208, 240 28.00 (711.2) 13.00 (330.2) 10.00 (254.0) 221.0 (100.24) 1 A
63-29-250-8
7500 208, 240, 480, 600 120, 208, 240 27.00 (685.8) 25.00 (635.0) 10.00 (254.0) 360.0 (163.30) 2 A
63-29-275-8
10000 208, 240, 480, 600 120, 208, 240 28.00 (711.2) 25.00 (635.0) 10.00 (254.0) 441.0 (200.03) 2 A
63-29-310-8
15000 208, 240, 480, 600 120, 208, 240 28.00 (711.2) 38.00 (965.2) 10.00 (254.0) 706.0 (320.24) 3 A
63-29-315-8
Group 4 MCR Series, 50 Hz Only (5% output voltage regulation)
Height Width Depth Ship Weight Design Elec
VA Catalog Number Voltage Input Voltage Output
in (mm) in (mm) in (mm) lbs (kg) Style Conn
120 110, 120, 220, 240, 380, 415 110, 120, 220, 240 9.00 (228.6) 6.00 (152.4) 8.00 (203.2) 24.0 (10.90) 1 C
63-23-612-8
250 110, 120, 220, 240, 380, 415 110, 120, 220, 240 11.00 (279.4) 6.00 (152.4) 8.00 (203.2) 27.0 (12.25) 1 C
63-23-625-8
500 110, 120, 220, 240, 380, 415 110, 120, 220, 240 13.00 (330.2) 9.00 (228.6) 7.00 (177.8) 40.0 (18.14) 1 C
63-23-650-8
1000 110, 120, 220, 240, 380, 415 110, 120, 220, 240 18.00 (457.2) 9.00 (228.6) 7.00 (177.8) 64.0 (29.03) 1 C
63-23-710-8
2000 110, 120, 220, 240, 380, 415 110, 120, 220, 240 18.00 (457.2) 13.00 (330.2) 10.00 (254.0) 113.0 (51.26) 1 C
63-23-720-8
3000 110, 120, 220, 240, 380, 415 110, 120, 220, 240 27.00 (685.8) 13.00 (330.2) 10.00 (254.0) 162.0 (73.48) 1 C
63-23-730-8
5000 110, 120, 220, 240, 380, 415 110, 120, 220, 240 30.00 (762.0) 13.00 (330.2) 10.00 (254.0) 266.0 (120.66) 1 C
63-23-750-8
7500 220, 240, 380, 415 110, 120, 220, 240 28.00 (711.2) 26.00 (660.4) 10.00 (254.0) 393.0 (178.26) 2 C1
63-28-775-8
10000 220, 240, 380, 415 110, 120, 220, 240 30.00 (762.0) 26.00 (660.4) 10.00 (254.0) 490.0 (222.26) 2 C2
63-28-810-8
15000 220, 240, 380, 415 110, 120, 220, 240 30.00 (762.0) 38.00 (965.2) 10.00 (254.0) 776.0 (352.00) 3 C2
63-28-815-8
Specifications
Parameter Condition Value
Input
Continuous at full load (lower input voltage possible at lighter load) +10% to -20% of nominal
Voltage
For temporary surge or sags +20% to -35% of nominal
1
at Full Load & 80% of nominal input voltage I (VA/.89)/(V x 80%)
Current
in in
See Operating Characteristics section for details. 50 Hz or 60 Hz depending on model
Frequency
2
Output
V >80% and <110% of nominal 5% for 50 Hz units, 3% for 60 Hz units
Line Regulation
in
At Nominal Input Voltage Current limited at 1.65 times rated current
Overload Protection
At full load within input range 3% total RMS content
Output Harmonic Distortion
Common Mode 120 dB
Noise Attenuation
Transverse Mode 60 dB
General
At Full Load Up to 92%
Efficiency
Humidity <95% non-condensing -20 to +85C
Storage Temperature
Humidity <95% non-condensing -20 to 50C
Operating Temperature
Full Resistive Noise 35 dBA to 65 dBA
Audible Noise
10 + 2 year limited warranty
Warranty
Notes: 1 - Consult user manual for fuse sizing.
2 - It is recommended that the unit run at a minimum of 40-50% load.
Contact Technical Services at (800) 377-4384 with any questions.