DPP Series 15-100W, 5-48V Output DIN Rail Mount Power Supplies Features Low Cost Universal Input (2) NEC NFPA70 Class 2 UL508 Listed (3) Class 1, Division 2 (ISA 12.12) -10 to +71C Operation Key Market Segments & Applications Speci cations Model DPP15 DPP25/30 DPP50 DPP100 AC Input Voltage range VAC 85 - 264VAC 85 - 132VAC 176 - 264VAC Input Frequency Hz 47 - 63Hz DC Input Voltage range - 90 - 375VDC* 210 - 375VDC* Inrush Current (115 / 230VAC) A <35A 35 / 45A 35 / 50A 35 / 55A Power Factor - Meets EN61000-3-2 Class A Input Current (230VAC) A 0.25 0.4 0.7 1.2 Leakage Current mA <0.75mA, 265VAC, 63Hz Output Voltage Accuracy % 1% (24V outputs preset at 24.5V) Line Regulation % < 0.5% Load Regulation % < 0.5% Ripple and Noise mV 50mV Overcurrent Protection (Typ) - >110% (fold forward type) Overvoltage Protection V 120 - 137.5% Hold Up Time (115VAC input) ms > 20ms Parallel switch - No Yes LED Indicator - Green LED = On Operating Temperature C -10* to +71C (Derate linearly 5%/C from 61 to 71C) * -25C start up, DPP25-50 only Storage Temperature C -25 to +85C Operating Humidity - 20 - 90% RH (non condensing) Cooling (1) - Convection Withstand Voltage - Input to Output 3kVAC for 1 min. Shock - Half sine wave, 4G, 22ms, 3 times per face, X, Y, Z 2 Vibration - 10-500Hz (20 min sweep) 0.002G /Hz, 1 Grms acceleration X, Y, Z, 1 hour Isolation Resistance - >100M at 25C & 70%RH, Output to Ground 500VDC Safety Agency Approvals - IEC/UL/CSA/EN62368-1, 60950-1, UL508, NEC Class 2(2), ISA 12.12(3), CE Mark Emissions - EN55011, EN55032 class B Radiated & Conducted, EN61000-6-3 Immunity - EN61000-6-2, EN61000-4-2 Level 4, EN61000-4-3, EN61000-4-6 Level 3, EN61000-4-4 Level 4 (I/P) Level 3 (O/P), EN61000-4-5 Level 3 L-N, Level 4 L/N-PE, EN61000-4-8, EN61000-4-11 Weight (Typ) g 130 260 390 Size (LxWxH) mm 96.8 x 22.9 x 75mm 91 x 45 x 75mm 96.8 x 72.6 x 75mm Size (LxWxH) in 3.81 x 0.9 x 2.95 3.58 x 1.77 x 2.95 3.81 x 2.86 x 2.95 Case material - Flame Retardant Polycarbonate (UL94 V-0) MTBF (MIL-HDBK-217F, GF25) Hours 287,000 >288,000 269,000 239,000 Warranty yrs Three years (1) Recommend 1 clearance on all sides. *Safety certi ed for AC input only (2) See model selector. Evaluated to NEC NFPA70 Class 2 output per UL1310. (3) See model selector.DPP Series Model Selector Voltage Voltage Current Power E c. UL1310 ISA12.12 Model (V) Adjust (V) (A) (W) (typ) % Class 2 Class 1 Div 2 DPP25-5 5 5-6 5.0 25 78 - Yes DPP30-12 12 9.9-12.1 2.5 30 83 Yes Yes DPP50-15 15 11.9-15.1 3.4 50 85 Yes Yes DPP15-24 24 22.5-28.5 0.63 15 81 Yes - DPP30-24 24 22.5-28.5 1.3 30 84 Yes Yes DPP50-24 24 22.5-28.5 2.1 50 86 Yes Yes DPP100-24 24 22.5-28.5 4.2 100 87 - - DPP50-48 48 48-56 1.05 50 87 Yes Yes DPP15 Outline DPP100 Outline Installation: DPP25-DPP50 Outline Snap-on Mounting - snap onto DIN Rail TS35/7.5 or TS35/15. (No tools required) Cooling - Normal Convection Clearance - 25mm all sides Connection - Use copper wire 0.5-2.5mm2 (AWG24-12) Other DIN Rail Products DSP/DPP 10W to 480W power supplies DLP 75W to 240W power supplies DLP-PU Redundancy Module (20A) R Series 3A to 30A single & three phase EMI Filters For additional information, please visit