www.emea.tdk-lambda.com/hws-me Limited Lifetime Warranty Medical Approvals Universal Input (85 - 265VAC) High Efficiency Broad 30W to 1500W product range RoHS Compliant Design Key Market Segments & Applications HWS-/ME Series Single Output Medical Industrial Test Broadcast Comm LED Cots Medical Power Supplies HWS-/ME Features and Benefits Features Benefits Limited Lifetime Warranty Lower Cost of Ownership Medical Approvals Reduces System Approval Times Wide Range AC Input Supports Global Use Specifications MODELS HWS30A HWS100A HWS300 HWS600 HWS1000 HWS1500 ITEM HWS50A HWS150A Input Voltage range 85-265VAC (47-63Hz) 85-265VAC (47-63Hz) 85-265VAC (47-63Hz) 0.65 / 0.4 1.3 / 0.65 Input Current (Typ) (1) A 0.65 / 0.35 1.9 / 0.95 4.1 / 2.1 8.1 / 3.9 13.5/7.0 19/10 Inrush Current (1) A 14 / 28 20 / 40 Power Factor / Flicker Meets EN61000-3-2, EN61000-3-3 Temperature Coefficient - <0.02%/C Overcurrent Protection - >104% Overvoltage Protection V Yes (See table on page 2) Hold Up Time (Typ) ms 20 Leakage Current (60Hz) (2) mA <0.5mA Remote Sense No Yes Indicator - Green LED = ON Remote On/Off - No Yes (Isolated from output) Parallel operation - No Single wire conn. (5 units max) DC Good - No Yes Voltage Programming No Yes Operating Temperature - HWS30A-150A: -10C to +70C, (derating applies above 50C please refer to individual model specification for derating graph) and Derating HWS300-1500: -10C to +70C, (-10 to +50C: 100%, derate linearly to 50% load from +50C to +70C) Storage Temperature C -30C to +85C Humidity (non condensing) - Operating: 30 - 90%RH (10 -90% on HWS300-1500), Non operating 10 - 95%RH Cooling - Convection Internal fan Withstand Voltage (3) - Input to Ground 2kVAC, Input to Output 3kVAC, Output to Ground 500VAC for 1 min. Isolation Resistance - >100M at 25C & 70%RH, Output to Ground 500VDC, >10M Output to remote on/off 100VDC 2 Vibration (non operating) - 10 - 55Hz (1 min sweep), 19.6m/s constant, X, Y, Z axis, one hour each 2 Shock (in packaging) - < 196.1m/s Safety Agency Approvals (2) - ES60601-1, EN60601-1, CSA-C22.2 No6011-M90 (C-UL) (basic insulation), CE Mark Line Dip - Complies with SEMI F47 (200VAC line only) Conducted & Radiated EMI - EN55011 / EN55022-B, FCC-B, VCCI-B (HWS600 & 1500 Class A) Immunity - IEC61000-4-2, -3, -4, -6, -8, -11, IEC61000-6-2 220 450 Weight (Typ) g 280 500 1000 1600 3200 3800 Size (WxHxD) 26 x 82 x 95 33 x 82 x 160 (with cover except 30 & 50W) mm 26 x 82 x 120 42 x 82 x 160 61 x 82 x 165 100 x 82 x 165 126.5 x 82 x 240 280 x 82 x 126.5 Warranty Limited Lifetime Warranty (See TDK-Lambda terms & conditions) Notes: (1) 100/200VAC input (2) See clause 19.5DV.2 of UL60601 for equipment in proximity of patient (3) HWS300-600 2.5kVAC Input to ground 1 HWS-/ME SeriesModel Selector Adjust Max Max Load Line Ripple Overvoltage Efficiency 4 1 Model Voltage Range Curr(A) Power(W) Reg(mV) Reg(mV) Noise(mV) (V) (typ)% HWS30A-5/ME 5V 4.0 - 6.0 6 30 40 20 120 6.25-7.25 77/80 HWS50A-5/ME 5V 4.0 - 6.0 10 50 40 20 120 6.25-7.25 82/84 HWS100A-5/ME 5V 4.0 - 6.0 20 100 40 20 120 6.25-7.25 83/86 HWS150A-5/ME 5V 4.0 - 6.0 30 150 40 20 120 6.25-7.25 83/86 HWS600-5/ME 5V 4.0 - 6.0 120 600 30 20 120 6.25-7.25 80/83 HWS30A-12/ME 12V 9.6 - 14.4 2.5 30 96 48 150 15-17.4 81/83 HWS50A-12/ME 12V 9.6 - 14.4 4.3 51.6 96 48 150 15-17.4 81/83 HWS100A-12/ME 12V 9.6 - 14.4 8.5 102 96 48 150 15-17.4 83/86 HWS150A-12/ME 12V 9.6 - 14.4 13 156 96 48 150 15-17.4 83/86 HWS300-12/ME 12V 9.6 - 14.4 27 324 72 48 150 15-17.4 80/83 HWS600-12/ME 12V 9.6 - 14.4 53 636 72 48 150 15-17.4 80/83 HWS30A-15/ME 15V 12.0 - 18.0 2 30 120 60 150 18.8-21.8 81/83 HWS50A-15/ME 15V 12.0 - 18.0 3.5 52.5 120 60 150 18.8-21.8 81/83 HWS100A-15/ME 15V 12.0 - 18.0 7 105 120 60 150 18.8-21.8 83/86 HWS150A-15/ME 15V 12.0 - 18.0 10 150 120 60 150 18.8-21.8 83/86 HWS300-15/ME 15V 12.0 - 18.0 22 330 90 60 150 18.8-21.8 82/85 HWS600-15/ME 15V 12.0 - 18.0 43 645 90 60 150 18.8-21.8 81/84 HWS30A-24/ME 24V 19.2 - 28.8 1.3 31.2 192 96 200 30-34.8 83/86 HWS50A-24/ME 24V 19.2 - 28.8 2.2 52.8 192 96 150 30-34.8 82/84 HWS100A-24/ME 24V 19.2 - 28.8 4.5 108 192 96 150 30-34.8 84/87 HWS150A-24/ME 24V 19.2 - 28.8 6.5 156 192 96 150 30-34.8 85/88 HWS300-24/ME 24V 19.2 - 28.8 14 (16.5 pk) 336 144 96 150 30-34.8 82/85 HWS600-24/ME 24V 19.2 - 28.8 27 (31 pk) 648 144 96 150 30-34.8 82/85 HWS1000-24/ME 24V 19.2 - 28.8 46 (58.5 pk) 1104 150 96 150 30-34.8 85/87 (7) (1) (1) HWS1500-24/ME 24V 4.8 - 28.8 65/70 1560/1680 144 96 200 30-34.8 84/88 (5) (5) (105pk ) (2520 pk ) HWS1000-36/ME 36V 28.8 - 43.2 30.7 (39 pk) 1104 150 144 200 45-49.7 85/88 (6) (1) (1) HWS1500-36/ME 36V 7.2 - 43.2 42/46.5 1512/1674 150 144 200 34-49.7 84/88 (5) (5) (70 pk) (2520 pk ) HWS30A-48/ME 48V 38.4 - 52.8 0.65 31.2 384 192 200 55.2-64.8 82/83 HWS50A-48/ME 48V 38.4 - 52.8 1.1 52.8 384 192 200 55.2-64.8 83/85 HWS100A-48/ME 48V 38.4 - 52.8 2.1 100.8 384 192 200 55.2-64.8 84/87 HWS150A-48/ME 48V 38.4 - 52.8 3.3 158.4 384 192 200 55.2-64.8 85/88 HWS300-48/ME 48V 38.4 - 52.8 7 336 288 192 350 55.2-64.8 82/85 HWS600-48/ME 48V 38.4 - 52.8 13 624 288 192 350 55.2-64.8 83/86 HWS1000-48/ME 48V 38-4 - 52.8 23 1104 300 192 200 55.2-60 86/88 (6) HWS1500-48/ME 48V 9.6- 52.8 32 1536 288 192 200 55.2-64.8 86/90 (4) Peak load for 10s maximum on time, 35% duty cycle (5) 200-265AC Input (6) Using voltage programming input - see installation manual for details Options Suffix Description Blank No cover (except HWS300-1500 cover fitted) as standard /A Cover fitted (egHWSA100-24/MEA) option available for HWSA100 & HWSA150 only 22 HWS-/ME Series