Identification/Classification 1 High-voltage contactor
(header 1 + top left bar):
Identification/Classification 2 Gas-filled contactor for high-voltage DC switching
(header 2 + bottom left header bar):
Ordering code: (top right header bar) B88269X1030C 11
Series/Type: (bottom right header bar)
HVC135A-24
Preliminary data (optional):
Department: PPD AB PD / PPD AB PM
Date: 2018-04-20
Version: 05
EPCOS AG 2018. Reproduction, publication and dissemination of this publication, enclosures hereto and the information
contained therein without EPCOS' prior express consent is prohibited.
EPCOS AG is a TDK Group Company. High-voltage contactor B88269X1030C 011
Gas-filled contactor for high-voltage DC switching HVC135A-24
Product description
The HVC series has been especially designed to meet the requirements of high-voltage DC switching
applications. The optimized hermetically sealed design exhibits excellent reliability performance
against harsh environments. HVC series can be used in a wide range of applications.
Features Applications
Gas-filled and hermetically sealed Battery charge/ discharge systems
No EMI, no inrush current phase at start-up Renewable energy storage systems
No polarity of contact terminals DC high-voltage/ high-current applications
RoHS compatible
DC fast charging stations
Characteristics
Height width depth 94 89 44 mm
Weight ~ 500 g
Inner contact material Cu alloy
Contact arrangement 1A
Internal contact gap (full disconnection) 3.0 (2 1.5) mm
a)
Recommended connection cable cross section > 50 mm
Coil wires
- length 300 mm
2
- cross section 0.5 mm
- material Cu
Vibration in xyz-axis
- shock, 11 ms sine, peak 20 g
- vibration, sine 100 2000 Hz, peak 20 g
b)
- wideband random vibration, 10 ... 1000 Hz 5 g
eff
c)
Operation and storage
- temperature 40 ... +85 C
- humidity 5 85 %
- air pressure 69 106 kPa
Climatic category (IEC 60068-1) 40/085/21
Label, black positive
HVC135A-24
[type name]
[ordering code]
B88269X1030C 11
[ser.no.] [internal code]
1234567890 J_ _ _
[certifications]
Designed in GermanyMade in Malaysia
Certifications UL 60947-4-1 (E491412)
Notes
a)
The diameter must be matched to actual current and operation temperature (see: Cautions and warnings, page 7).
b)
Acc. to IEC 60068-2-64
c)
Freezing or condensing must be avoided.
PPD AB PD / PPD AB PM Version: 05 / 2018-04-20
Please read Cautions and warnings and Page 2 of 8