DLP Series
75 to 240W, 24V Output DIN Rail Mount Power Supplies
Features
u UL508 Listed, NEC NFPA70 Class 2(1) (/C2 Models)
u Conducted and Radiated EMI, Class B
u Input Transient Protection, IEC61000-4
u Semi F47 Compliant (DLP180 & 240 only)
Key Market Segments & Applications
Speci cations
Model DLP75-24-1/E DLP100-24-1/E DLP120-24-1/E DLP180-24-1/E DLP240-24-1/E
DLP75-24-1/C2EJ DLP100-24-1/C2EJ
Output Voltage V 24 24 24 24 24
Output Current (/C2 models) A 3.1 (2.5) 4.1 (3.7) 5.0 7.5 10
Output Power (/C2 models) W 75 (60) 98.4 (88.8) 120 180 240
Output Voltage Adjustment V 21.6 - 28 ( xed for /C2 models)
Load Regulation - 192mV
Line Regulation - 120mV
Ripple/Noise (0-600C) mV 240
AC Input Voltage & Frequency - 85-132/170-265VAC, 47-63Hz Auto select 85-265VAC (47-63Hz)
(2)
or 120-370VDC
Input Current 100/230VAC A 1.7/0.8 2.3/1.2 2.4/1.3 2.3/1.0 3.0/1.3
/C2 A 1.4/0.7 2.0/1.0 -
Ef ciency 100/230VAC % 81/83 82/85 83/85 84/87 82/86
Power Factor - Meets EN61000-3-2 (DLP180, 240: >0.95)
Inrush Current (Typ) 100/230VAC A 20/45
Leakage Current mA Less than 0.75mA
Hold-up Time 100/230VAC ms 20/30 (Semi F47 Compliance, DLP 180 & 240 only)
Overcurrent Protection - >105%,Fold Back >105%, Constant Current
/C2 - ~2.6A ~3.75A -
Overvoltage Protection - 30-35V, latching, cycle AC line to reset (26-30V DLP75-24-1/C2EJ)
LED Indicators - Green LED = DC ok Red LED = overcurrent
Operating Temperature (3) - Convection cooled, -10C to 60C, derate linearly to 60% load from 50 to 60C
Storage Temperature - -30C~+85C
Humidity (Non-Condensing) %RH 30-90% operating 10-95% non operating
Withstand Voltage - Input - Ground 2kVAC, Input to Output 3kVAC, Output - Ground 500VAC
2 2
Vibration - 9.8m/s (1.0G) at DIN rail; (10-55Hz: 9.8m/s Constant, X,Y, Z each 1 hour)
2
Shock - 196m/s (20G)
(1)
Safety Agency Approvals - UL508, NEC Class 2 (/C2 models), UL60950-1, CSA60950-1, EN60950-1, CE, EN50178 Cat III (Pri)
Conducted EMI - FCC-B, EN55011/EN55022-B, VCCI-B; Meets IEC61000-4-1
Radiated EMI - EN55011/EN55022-B, FCC-Class B, VCCI-B
ESD - IEC61000-4-2 10kV (Air), 5kV (Contact)
Radiated RFI - IEC61000-4-3 80-1000MHz,12V/m 80% AM 1kHz
Fast Transient Burst - IEC61000-4-4 2.4kV 5kHz
Lightning Surge - IEC61000-4-5 4.4kV, 1.2x50s (Common Mode) 2.4kV 1.2x50s (Normal)
Conducted RFI - IEC61000-4-6 150kHz-80MHz, 12V, 80% AM 1kHz
Magnetic Field - IEC61000-4-8 36A/m
Voltage Dips - IEC61000-4-11 70% 10ms, 40% 100ms, 0% 5s
Size mm 50 x 97 x 110 60 x 97 x 110 60 x 97 x 110 80 x 97 x 110 120 x 97 x 110
Weight g 470 540 540 780 1000
Warranty - 3 Years
(1) Evaluated to NEC NFPA70 Class 2 output per UL1310
(2) DC input is not safety approved
(3) DLP240-24-1/E, 170-265VAC: -10C~+70C, derated linearly to 60% load from 50 to 70C. DLP75-24-1/C2EJ: -10C~+70C,
derated linearly to 75% load from 50 to 60C. DLP100-24-1/C2EJ: -10C~+70C, derated linearly to 80% load from 50 to 60C.
1-800-526-2324 www.us.tdk-lambda.com/lp/ 1DLP Series
DLP75 Outline DLP100/120 Outline
+V -V
+V -V
V.ADJ
V.ADJ H
H
DC ON
DC ON
ALM ALM
L N
L N
+V -V
+V -V
V.ADJ
H V.ADJ
H
DC ON
DC ON
ALM
ALM
L N
L N
DLP180 Outline DLP240 Outline
DC ON +V +V -V -V
Output Details
DC ON +V +V -V -V H
ALMV.ADJ Continuous Loading 24VDC/10A
Output Details
H
ALMV.ADJ Continuous Loading 24VDC/7.5A
IND.CONT.EQ.
45JB Made in China
Input Details
100-240VAC 3.5A Maximum
Power Factor Corrected
Frequency : 50/60Hz
Made in China
L N
Input Details
100-240VAC 2.7A Maximum
Power Factor Corrected
Frequency : 50/60Hz
L N
DC ON +V +V -V -V
Output Details
DC ON +V +V -V -V H
V.ADJ Continuous Loading 24VDC/10A
ALM
Output Details
H
Continuous Loading 24VDC/7.5A
ALMV.ADJ
IND.CONT.EQ.
45JB
Made in China
Input Details
100-240VAC 3.5A Maximum
Power Factor Corrected
Frequency : 50/60Hz
Made in China
L N
Input Details
100-240VAC 2.7A Maximum
Power Factor Corrected
Frequency : 50/60Hz
L N
Derating Curve Other Industrial Products
DPP/DSP 10W to 480W Single Output DIN Rail
100
HWS 15W to 1800W Single Output
Snap-on Mounting: snap onto DIN Rail TS35/7.5 or
80
TS35/15. (no tools required)
75
60
For Additional Information, please visit
us.tdk-lambda.com/lp/products/dlp-series.htm
40
20
0
-10 0 10 20 30 40 50 60 70
Ta (C)
85~170VAC DLP240 DLP75/C2
85~265VAC all models
170~265VAC DLP240 only DLP100/C2
1-800-526-2324 www.us.tdk-lambda.com/lp/ 2 Revision B1: Nov 2011
Load (%)