Catalog 1308242
Issued 3-03 P&B
CB series
CMOS IC Time Delay Relay
Choice of timing modes
Delay on operate
Delay on release
Interval on with or without control switch
Knob adjustable
10A output relay with SPDT or DPDT contacts
Various models time from 0.1 sec. to 100 min.
File E22575
File LR15734
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Timing Modes Contact Data @ 25C
Delay on operate Delay period begins when input voltage is applied. At Arrangements: 2 Form C (DPDT), except 8-pin delay on release model
the end of the delay period, the relay will operate and will not release until has 1 Form C (SPDT).
input voltage is removed. Reset occurs when input voltage is reapplied. Material: Silver-cadmium oxide alloy.
Rating: 10A @ 30VDC or 277VAC, resistive; 1/2 HP @ 250VAC;
INPUT ON
1/3 HP @ 120VAC.
VOLTAGE OFF
Expected Mechanical Life: 10 million operations.
Expected Electrical Life: 100,000 operations, min., at rated load.
N.O. RELAY ON
TIME
CONTACTS OFF
Delay on release Input voltage must be applied continuously to operate
the internal relay. When the control switch is closed, the relay energizes.
Initial Dielectric Strength
When the control switch is opened, timing begins. When timing is
complete, the relay will de-energize. Time may be reset to zero during
Between Open Contacts: 500V rms, 60 Hz.
timing by closing the control switch. Between All Other Conductors: 500V rms, 60 Hz.
CONTROL ON
SWITCH OFF
N.O. RELAY ON
TIME
CONTACTS OFF
Input Data @ 25C
Interval on (without control switch) The relay energizes and timing
begins when input voltage is applied. At the end of the time delay period
Voltage: 24 and 120VAC, and 12 and 24VDC.
the relay will de-energize. Reset is accomplished by removing, then
Power Requirement: AC Types: Typically less than 3 VA.
reapplying, the input voltage.
DC Types: Typically less than 3 W.
Transient Protection: Yes.
INPUT ON
Reverse Voltage Protection: Yes.
VOLTAGE OFF
Input Voltages & Limits @ 25C
Voltage Nominal Minimum Maximum
N.O. RELAY ON
TIME
CONTACTS OFF Type Voltage Voltage Voltage
Interval on (with control switch) Input voltage must be applied
AC 24 20 28
continuously to operate the internal relay. The relay energizes and timing
120 105 130
begins when the external switch is closed. At the end of the time delay
DC 12 11 13
period the relay will de-energize. Reset is accomplished by opening and
24 20 32
reclosing the control switch.
Note: DC voltage must be filtered (5% p-p ripple max. at nom. voltage).
CONTROL ON AC models will operate on 50 or 60 Hz.
SWITCH
OFF
N.O. RELAY
ON
TIME
CONTACTS OFF
Environmental Data
Temperature Range: Storage: -55C to +85C.
Timing Specifications
Operating: -10C to +55C.
Timing Ranges: From 0.1 to 1.0 sec. through 10 to 100 min.
Timing Adjustment: Knob adjustable.
Tolerance (for AC units add 1/2 cycle 60 Hz.):
Knob Adj. Types: 0, +30% of max. specified at high end of timing range;
Mechanical Data
min. specified, or less, at low end.
Fixed Types: 10%.
Termination: 8- or 11-pin octal style plug.
Res. Adj. Types: 10% at high end of timing range; min. specified, or less,
Enclosure: White plastic case. Knob adjustable types have dial scale for
at low end.
reference only.
Delta Time (for AC units add 1 cycle 60 Hz.): 10%.
Sockets: Models with 8-pin base fit either 27E122 or 27E891 (snap-on)
Repeatability (for AC units add 1 cycle 60 Hz.): 2%.
screw terminal sockets. 11-pin types fit either 27E123 or
Release Time: 60 ms, typ.; 100 ms, max.
27E892 (snap-on) screw terminal sockets.
Recycle Time: 60 ms, typ.; 100 ms, max.
Weight: 6 oz. (170g) approximately.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
reference purposes only. (millimeters) unless otherwise subject to change. Technical support:
1228
specified. Refer to inside back cover.Catalog 1308242
Issued 3-03 P&B
Ordering Information Authorized distributors are more likely to stock boldface items listed below.
Delay on Operate Models Delay on Release Models
Voltage Time Adjustment Wiring Dia. Part Number Voltage Time Adjustment Wiring Dia. Part Number
24VAC 0.1 to 10 Sec. Knob 1 CB-1041B-30 24VAC 0.1 to 10 Sec. Knob 3 CB-1045B-38
1.8 to 180 Sec CB-1042B-30 1.8 to 180 Sec CB-1046B-38
0.1 to 1 Sec. CB-1001B-70 0.1 to 10 Sec. 3 CB-1021B-78
0.1 to 5 Sec. CB-1002B-70 120VAC 0.1 to 10 Sec. Knob 5 CB-1022B-78
0.1 to 10 Sec. CB-1003B-70 0.6 to 60 Sec. 3 CB-1023B-78
120VAC 0.6 to 60 Sec. Knob 1 CB-1004B-70 1.8 to 180 Sec. 3 CB-1024B-78
1.8 to 180 Sec. CB-1005B-70
24VDC 0.1 to 10 Sec. Knob 3 CB-1038D-38
1 to 10 Min. CB-1006B-70
1.8 to 180 Sec. CB-1039D-38
10 to 100 Min. CB-1007B-70
Interval on Models
12VDC 0.1 to 10 Sec. Knob 1 CB-1047D-20
Voltage Time Adjustment Wiring Dia. Part Number
0.1 to 1 Sec. CB-1026D-30
24VDC 0.1 to 10 Sec. Knob 1 CB-1028D-30 24VAC 0.1 to 10 Sec. Knob 1 CB-1043B-39
0.6 to 60 Sec. CB-1029D-30
0.1 to 5 Sec. 1 CB-1011B-79
1.8 to 180 Sec. CB-1030D-30
120VAC 0.1 to 10 Sec. Knob 1 CB-1014B-79
1 to 10 Min. 1 CB-1018B-79
24VDC 0.1 to 5 Sec. Knob 1 CB-1034D-39
1.8 to 180 Sec. CB-1036D-39
Outline Dimensions
2.406 MAX.
(61.1)
.60 2.937 MAX. 1.781 MAX.
.56
(15.2) (74.6) (45.2)
(14.2)
Wiring Diagrams - Bottom Views (pins numbered clockwise from keyway)
EXTERNAL
EXTERNAL
CONTROL
CONTROL
SWITCH*
SWITCH*
_ _
+ +
_
CONTINUOUS CONTINUOUS
+
SUPPLY SUPPLY
INPUT (DC POLARITY INPUT INPUT
INDICATED)** (DC POLARITY INDICATED)** (DC POLARITY INDICATED)**
Fig. 3 Fig. 5
Fig. 1
11 Pin 8 Pin
8 Pin
* If control switch is closed when power is applied, relay will immediately energize. A 50 millisecond minimum switch closure is required. IMPORTANT: A dry circuit switch is recommended. A
dry circuit switch is one rated to reliably switch currents of less than 50mA. Use of a switch rated for other than dry circuit may result in failure of the time delay relay to function properly.
** Note: Input polarity for DC operation. For most reliable operation on AC, connect high side to + and low side to .
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
reference purposes only. (millimeters) unless otherwise subject to change. Technical support: