Catalog 1308242 Potter & Brumfield Issued 3-03 (PDF Rev. 2-14) SSR series Hockey Puck Solid State Relay With Paired SCR Output File E81606 Users should thoroughly review the technical data before selecting a product part number. It is recommended that users also seek out the pertinent approvals files of the agencies/laboratories and review them to ensure the product meets the requirements for a given application. Features Engineering Data Standard hockey puck package. Form: 1 Form A (SPST-NO). Enhanced noise immunity (designed to meet level 3 requirements of Duty: Continuous. European EMC Directive). Isolation: 4,000V rms minimum. LED indicator. Capacitance: 8 pf typical (input to output). Inverse parallel SCR output. Temperature Range: 25, 50, & 125A rms versions. Storage: 40C to +100C 120/240VAC & 480VAC output types. Operating: 20C to +80C. Zero voltage and random voltage turn-on versions. NOTE: Operation to 40C is permitted for DC input types at an AC & DC input versions. increased minimum input voltage of 4VDC (240V line 4,000V rms optical isolation. voltage models) or 5VDC (480V line voltage models). Floating terminal design. Case Material: Plastic, UL rated 94V-0. Case and Mounting: Refer to outline dimension. Termination: Refer to outline dimension. Approximate Weight: 3.5 oz. (98g). Ordering Information Sample Part Number SSR -240 D 25 1. Basic Series: SSR =hockey puc inverse parallel SCR output solid state relay 2. Line Voltage: 240 = 24 - 240VAC 480 = 48 - 660VAC 3. Input Type & Voltage: A = 90 - 280VAC D = 3 - 32VDC (240V line voltage model) / 4 - 32VDC (480V line voltage model) 4. Maximum Switching Rating/Output: 25 = .1 - 25A rms, mounted to heatsink 50 = .1 - 50A rms, mounted to heatsink 125 = .1 - 125A rms, mounted to heatsink 5. Options: Leave Blank = Zero voltage turn-on R = Random voltage turn-on (phase controllable) Our authorized distributors are more likely to maintain the following items in stock for immediate delivery. SSR-240A25 SSR-240D25 SSR-240D50 SSR-240A50 SSR-240D25R SSR-480D125 Input Specifications AC Input DC Input Parameter Zero V Turn-on Units Zero and Random V Turn-on Units 240VAC Rated Models 480VAC Rated Models Control Voltage Range V 90 - 280VAC 3 - 32VDC 4 - 32VDC IN Must Operate Voltage V (Min.) 3VDC 4VDC 90VAC IN(OP) Must Release Voltage V (Min.) 10VAC 1VDC 1VDC IN(REL) Input Current (Max.) 15mA 15mA 15mA Dimensions are shown for Dimensions are shown for Dimensions are in inches over Dimensions are in inches over Specifications and availabilitySpecifications and availability www.te.comwww.te.com reference purposes only.reference purposes only. (millimeters) unless otherwise (millimeters) unless otherwise subject to change.subject to change. 1.850 (47.0) 1.700 LED INDICATOR (43.18) .875 (22.23) 1.100 1.000 .470 (27.94) (25.4) (11.9) 1.750 (44.45) 2.250 (57.15) Catalog 1308242 Potter & Brumfield Issued 3-03 (PDF Rev. 2-14) Output Specifications ( 25 C, unless otherwise specified) Parameter Nom. Line Voltage Conditions Units 25A Models 50A Models 125A Models 120/240V Model 24 - 280 V rms Load Voltage Range V L 480V Model V rms 48 - 660 600 120/240 Model V peak Repetitive Blocking Voltage (Min.) 480V Model V peak 1200 A rms Load Current Range I * 120/240 & 480V Models Resistive .05 - 25 .1 - 50 .1 - 125 L Single Cycle Surge Current (Min.) A peak 120/240 & 480V Models 250 750 1,700 f = 60 Hz. V = 240V rms 120/240V Model mA rms .1 L Leakage Current (Off-State) (Max.) 480V Model f = 60 Hz. V = 480V rms .25 L On-State Voltage Drop (Max.) 120/240 & 480V Models I = Max. 1.35 L V/s Static dv/dt (Off-State) (Min.) 120/240 & 480V Models 500 Thermal Resistance, Junction to Case 120/240 & 480V Models C/W 0.4 0.25 .15 (R ) (Max.) J-C 8.3 for Zero Voltage Turn-On DC input types, 120/240 & 480V Models ms Turn-On Time (Max.) f = 60 Hz. 20 for Zero Voltage Turn-On AC input types, 0.02 for Random Voltage Turn-On Models 120/240 & 480V Models 8.3 for DC input types, 30 for AC input types Turn-Off Time (Max.) f = 60 Hz. ms 2 2 I T Rating 120/240 & 480V Models t = 8.3 ms A Sec. 937 2,458 12,000 I = Max. Load Power Factor Rating 120/240 & 480V Models 0.5 - 1.0 L *See Derating Curves Electrical Characteristics (Thermal Derating Curves) 50A Units 25A Units 125A Units Heatsink Recommendations We recommend that solid state relay modules be mounted to a heatsink sufficient to maintain the modules base temperature at less than 85C under worst case ambient temperature and load conditions. The heatsink mounting surface should be a smooth (30-40 micro-inch finish), flat (30-40 micro-inch flatness across mating area), un-painted surface which is clean and free of oxidation. An even coating of thermal compound (Dow Corning DC340 or equivalent) should be applied to both the heatsink and module mounting surfaces and spread to a uniform depth of .002 to eliminate all air pockets. The module should be mounted to the heatsink using two 10 screws. Operating Diagrams Outline Dimensions 1 -4 CONSTANT ZERO .870 VOLTAGE CURRENT OUTPUT (22.1) CIRCUIT DC INPUT +3 2 EQUIVALENT CIRCUIT ONLY 4 1 ZERO VOLTAGE OUTPUT AC INPUT CIRCUIT 3 2 EQUIVALENT CIRCUIT ONLY Random Turn-on Units have a Random Turn-on circuit .250 instead of Zero Voltage Circuit (6.35) .785 (19.94) Dimensions are shown for Dimensions are shown for Dimensions are in inches over Dimensions are in inches over Specifications and availabilitySpecifications and availability www.te.comwww.te.com reference purposes only.reference purposes only. (millimeters) unless otherwise (millimeters) unless otherwise subject to change.subject to change.