Introducing
DPC Series
Definite Purpose ContactorsDPC Series
Definite Purpose
Contactors
KEY FEATURES DESCRIPTION
Three and four pole definite purpose contactors offer ratings from 20
Three or four pole switching
to 40 full load amps (FLA), 30 to 50 amps resistive.
Factory-installed or user-installable auxiliary switches are optional
(main contacts) plus
optional auxiliary contacts
APPLICATIONS
Ratings from 20-40 full load
AC motor control and resistive element control in industrial machinery,
amps, 30-50 amps resistive
HVAC equipment, elevators, commercial appliances and other systems.
Fully enclosed, efficient
MECHANICAL
50/60 Hz. coils
Three pole models without auxiliary switches measure approximately
Standard arc cover
1.95 x 3.76 x 2.99 in. (49.7 x 95.6 x 76.0mm), with narrow base; 2.38 x
3.76 x 2.99 (60.3 x 95.6mm x 76.0mm) , with standard base.
Four pole models without auxiliary switches measure approximately
Integrated mounting plate
2.58 x 3.75 x 2.99 in. (65.5 x 95.2 x 76.0mm), including base.
Space-saving plate available
on three pole models
STANDARDS AND SPECS
UL Recognized for the US and Canada, File E75492.
Quieter operation and less
CSA Certified, File LR49598.
S Marked, Intertek ETL SEMKO Certificate 811687.
contact bounce than
CE Marked
similar products
Max sealed VA of 6.5 for
ELECTRICAL
three pole, 7.0 for four pole
MMaaiinn CCoonnttaacctt RRaattiinnggss
Full Number Line Locked Resistive Maximum Horsepower
Various termination options
Load of Voltage Rotor Amps Single Three
Amps Poles Amps Rating Phase Phase
120 120 30 1.5
240 120 30 3 7.5
20 3 or 4
480 100 30 7.5
600 80 30 7.5
120 150 35 2 -
240 150 35 5 10
25 3 or 4
480 125 35 15
600 100 35 20
120 180 40 2 -
240 180 40 5 10
30 3 or 4
480 150 40 15
RoHS
600 120 40 20
Ready
120 240 50 3
240 240 50 7.5 10
40 3 or 4
480 200 50 20
600 160 50 25