DC Filters Catalog: 1654001 Corcom Product Guide Issue Date: 06.2011 RFI Power Line Filters for DC Applications DC Series EN 60 950 UL Recognized CSA Certied TUV Certied 60DCF6B 15DCF10 DC Series Specications General purpose line lters for DC applications up Hipot rating (one minute): to 125VDC Line to Ground: 2250 VDC LIne to Line: 1450 VDC Available with or without a circuit breaker Rated Voltage (max): 80 VDC Available with feedthrough capacitors for added high frequency performance Rated Current: 15 to 125A Available in both ange mound (DCF) and Operating Ambient Temperature Range bulkhead mount (DCB) conguration (at rated current I ): -10C to +55C r In an ambient temperature (T ) higher than +55C a the maximum operating current (I ) is calculated as o follows: I = I (85-Ta)/30 o r 4 Ordering Information 60 DC B 6 B Electrical Schematics Options B Circuit breaker Standard Performance F Feedthrough capacitors BF Circuit breaker and Note 2 Note 3 LOAD LINE feedthrough F and BF available only in Note 1 Note 1 bulkhead (B) mounting style Omit for none Note 4 Input / Output Styles 6 Redundant stud High Frequency Performance (F & BF Styles) 10 Phoenix terminal Note 2 LINE LOAD Mounting Style F = Flange Note 3 Note 1 B = Bulkhead and rack Required for F or BF options Note 4 DC Series Current Rating 15, 30, 60, 100 or 125A 217 Dimensions are in inches and millimeters unless otherwise specied. Values in italics For email, phone or live chat, please go to te.com/help are metric equivalents. Dimensions are shown for reference purposes only. corcom.com Specications subject to change.Catalog: 1654001 Corcom Product Guide Issue Date: 06.2011 RFI Power Line Filters for DC Applications (continued) DC Series Available Part Numbers Standard Performance High Performance 15DCF6 15DCF10 15DCB10F 15DCB6F 30DCF6 30DCF10 30DCB10F 30DCB6F 60DCF6 60DCF10 60DCB10F 60DCB6F 100DCF6 100DCF10 100DCB10F 100DCB6F 125DCF6 125DCF10 125DCB10F 125DCB6F 15DCF6B 15DCF10B 15DCB6BF 30DCF6B 30DCF10B 30DCB6BF 60DCF6B 60DCF10B 60DCB6BF 100DCF6B 100DCF10B 100DCB6BF 125DCF6B 125DCF10B 125DCB6BF 15DCB6 15DCB10 15DCB10BF 30DCB6 30DCB10 30DCB10BF 60DCB6 60DCB10 60DCB10BF 100DCB6 100DCB10 100DCB10BF 125DCB6 125DCB10 125DCB10BF 15DCB6B 15DCB10B 30DCB6B 30DCB10B 60DCB6B 60DCB10B 100DCB6B 100DCB10B 125DCB6B 125DCB10B Termination Options Style 6 (15, 30 & 60A) Style 6 (100 & 125A) Supplied with 10-32 redundant studs Supplied with 1/4-20 redundant studs 0.625 15.88 spacing like polarity 0.750 19.05 spacing like polarity 0.750 19.05 spacing opposing polarity 1.00 25.4 spacing opposing polarity Torque specication: 27 3 in-lb. Torque specication: 45 2 in-lb Style 10 (15 & 30A) Style 10 (60A) PHOENIX CONTACT* part number: VDFK4 PHOENIX CONTACT* part number: HDFK 16-VP Accepts 12 AWG stranded wire Accepts 6 AWG stranded wire Wire strip length: 0.315 8.0 Wire strip length: 0.630 16.0 Torque specication: 5.5 7.0 in-lb. Torque specication: 17.7 21.2 in-lb. Ground stud: 8-32 Ground stud: 10-32 Style 10 (100A) Style 10 (125A) PHOENIX CONTACT* part number: HDFK 25-VP PHOENIX CONTACT* part number: HDFK 50-VP Accepts 4 AWG stranded wire Accepts 1 AWG stranded wire Wire strip length: 0.748 19.0 Wire strip length: 0.945 24.0 Torque specication: 35.4 39.9 in-lb. Torque specication: 35.4 39.9 in-lb. Ground stud: 1/4-20 Ground stud: 1/4-20 218 Dimensions are in inches and millimeters unless otherwise specied. Values in italics For email, phone or live chat, please go to te.com/help are metric equivalents. Dimensions are shown for reference purposes only. corcom.com Specications subject to change.