General Purpose Relays Product Sets SCHRACK Relay Package RT n Relay package consisting of RT relay, DIN-rail socket, plastic retaining clip, module and marking tag n 1 CO with 12 A or 2 CO with 8 A rated load n Sensitive DC- or AC coil n Reinforced insulation (protection class II / VDE 0700), safe separation to VDE 0160 n Jumper bars for interconnection n Further accessories see Accessories RT Approvals F0287-C Relay: VDE Cert. No. 40007571, cULus E214025 Socket: VDE Cert. No. 4007571, cULus E135149 Z Technical data of approved types on request Contact data 1-pole 2-pole Contact configuration 1 CO 2 CO Contact set single contact Type of interruption micro disconnection Rated voltage/max. switching voltage AC 240/400VAC Rated current 16 A*) 8 A Limiting continous current 16 A*) 8 A, UL: 10 A Maximum breaking capacity AC 4000 VA 2000 VA Limiting making capacity, max. 4 ms, df 10% 30 A 15 A Contact material AgNi90/10, AgNi90/10 gold plated Rated frequency of operation -1 with/without load 6 / 1200 min *) for full load current (16 A) the relay terminals 11-21, 12-22 and 14-24 have to be bridged. Contact ratings For contact ratings see datasheet Interface Power Relay RT Coil data Rated coil voltage range DC coil 24 VDC AC coil 24, 115, 230 VAC Insulation 1-pole 2-pole Operative range to IEC 61810 2 Dielectric strength coil-contact circuit 5000 V rms open contact circuit 1000 V rms Coil versions, DC coil adjacent contact circuits 2500 V rms Coil Rated Operate Release Coil Rated coil Clearance / creepage code voltage voltage voltage resistance power coil-contact circuit 10/10 mm VDC VDC VDC 10% mW Material group of insulation parts IIIa LC4 24 16.8 2.4 1440 400 Tracking index of relay base PTI 250 V Insulation to IEC 60664-1 Coil versions, AC coil 50 Hz Type of insulation Coil Rated Operate Release Coil Rated coil coil-contact circuit reinforced code voltage voltage voltage resistance power open contact circuit micro disconnection 50 Hz 50 Hz 50 Hz adjacent cont. circuits functional VAC VAC VAC VA Rated insulation voltage 250 V R24 24 18.0 3.6 35010% 0.76 Pollution degree 3 2 S15 115 86.3 17.3 810015% 0.76 Rated voltage system 240 V 230/240 V T30 230 172.5 34.5 3250015% 0.74 Overvoltage category III All figures are given for coil without preenergization, at ambient temperature +23C. Other coil voltages on request. 1 04-2015, Rev. 0415 Datasheets and product specification Datasheets and product data is subject to the Datasheets, product data, Definitions sec- www.te.com according to IEC 61810-1 and to be used terms of the disclaimer and all chapters of tion, application notes and all specifications 2015 Tyco Electronics Corporation, only together with the Definitions section. the Definitions section, available at are subject to change. a TE Connectivity Ltd. company General Purpose Relays Product Sets SCHRACK Relay Package RT (Continued) Other data 1-pole 2-pole Mechanical endurance 6 6 DC coil > 30 x 10 > 30 x 10 6 6 AC coil > 10 x 10 > 5 x 10 Material compliance: EU RoHS/ELV, China RoHS, REACH, Halogen content refer to the Product Compliance Support Center at www.te.com/customersupport/rohssupportcenter Ambient temperature range DC coil -20...+85C AC coil -20...+70C Processing Terminals screw Terminal screw torque acc. IEC 61984 0.5 Nm max. 0.7 Nm Wire cross section 2 single wire 2 x 2.5 mm 2 fine wire 2 x 2.5 mm 2 with bootlace crimp (DIN 46228/1) 2 x 1.5 mm Insertion cycles A (10) Max. Insertion Force total 100 N Mounting distance 0, dense packing of sockets Weight 54 g Packaging unit 10 pcs Dimensions S0430-C 2 04-2015, Rev. 0415 Datasheets and product specification Datasheets and product data is subject to the Datasheets, product data, Definitions sec- www.te.com according to IEC 61810-1 and to be used terms of the disclaimer and all chapters of tion, application notes and all specifications 2015 Tyco Electronics Corporation, only together with the Definitions section. the Definitions section, available at are subject to change. a TE Connectivity Ltd. company