Three Phase Filters Catalog: 1654001 Corcom Product Guide Issue Date: 06.2011 Compact Low Current 3-phase WYE RFI Filters AYO Series UL Recognized CSA Certied VDE Approved 22 AYO Series Specications For 3-phase, four wire, WYE applications Maximum leakage current each Line to Ground: 3, 6, 10A 20A Filters each of the three lines plus neutral 120 VAC 60 Hz: 2.0 mA 3.5 mA Good for attenuation beginning at 100kHz 250 VAC 50 Hz: 3.0 mA 5.5 mA Space saving design Hipot rating (one minute): Low leakage current Line to Ground: 1500 VAC Line to Line: 1450 VDC Easy to connect terminals Rated Voltage (max): Phase to Phase: 440 VAC Phase to Neutral / Ground: 250 VAC Operating Frequency: 50/60 Hz Ordering Information Rated Current: 3 to 20A 10 AYO 1 Operating Ambient Temperature Range (at rated current I ): -10C to +40C r Input / Output Style In an ambient temperature (T ) higher than +40C a 1 0.25 6.3 spade terminals the maximum operating current (I ) is calculated as o follows: I = I (85-Ta)/45 o r AYO Series Current Rating Electrical Schematic 3, 6, 10 or 20A LINE LOAD Available Part Numbers 3AYO1 6AYO1 N N 10AYO1 20AYO1 111 Dimensions are in inches and millimeters unless otherwise specied. Values in italics For email, phone or live chat, please go to te.com/help are metric equivalents. Dimensions are shown for reference purposes only. corcom.com Specications subject to change.Catalog: 1654001 Corcom Product Guide Issue Date: 06.2011 Compact Low Current 3-phase WYE RFI Filters (continued) AYO Series Case Style Case Dimensions A D A B C D E Part No. AYO Series B C E Performance Data Typical Insertion Loss Measured in closed 50 Ohm system 3AYO1 6AYO1 10AY01 20AYO1 db db db db 100 100 100 100 90 90 90 90 80 80 80 80 70 70 70 70 60 60 60 60 50 50 50 50 40 40 40 40 30 30 30 30 20 20 20 20 10 10 10 10 0 0 0 0 0.1 1 10 30 0.1 1 10 30 0.1 1 10 30 0.1 1 10 30 Frequency in MHz Frequency in MHz Frequency in MHz Frequency in MHz Common Mode / Asymmetrical (L-G) Dierential Mode / Symmetrical (L-L) Minimum Insertion Loss Measured in closed 50 Ohm system Common Mode / Asymmetrical (Line to Ground) Dierential Mode / Symmetrical (Line to Line) 112 Dimensions are in inches and millimeters unless otherwise specied. Values in italics For email, phone or live chat, please go to te.com/help are metric equivalents. Dimensions are shown for reference purposes only. corcom.com Specications subject to change.