Catalog: 1654001
Corcom Product Guide Issue Date: 06.2011
3-phase Delta External Power Line Filter for Frequency Converters
FCD Series
UL Recognized
6FCD10
FCD Series Specications
Maximum leakage current
Suitable to meet the latest EMC standards
voltage drop to virtual N to PE/V:
Insulated safety terminals
6FCD10: .26 mA/V
Suitable for EMC troubleshooting in the eld
12 & 16FCD10: .45 mA/V
25, 36 & 50FCD10: .52 mA/V
Very high attenuation
12 & 16FCD10B: .46 mA/V
High insertion loss
25& 36FCD10B: .52 mA/V
BS models optimized for very high insertion loss
50FCD10B: .57 mA/V
80 & 110FCD10B: .62 mA/V
BS models suitable for infeed/regenerative (ER)
150FCD10B: .63 mA/V
applications
180 & 230FCD10B: .92 mA/V
Touch safe terminals provide easy connections
FCD10BS: 3.25 mA/V
and prevent inadvertent contact for safety in the
Hipot rating (one minute):
most demanding applications
Line to Ground: 2250 VDC
Line to Line: 1450 VDC
Rated Voltage (max):
Phase to Phase: 480 VAC
Ordering Information
Phase to Neutral / Ground: 277 VAC
150 FCD 10 BS -95
Operating Frequency: 50/60 Hz
Rated Current: 6 to 230A
Terminal Block Option
Operating Ambient Temperature Range
-95 95mm terminal block
(at rated current I ): -10C to +40C
available on 150A only
r
In an ambient temperature (T ) higher than +40C
omit for standard terminals
a
the maximum operating current (I ) is calculated as
o
follows: I = I (85-Ta)/45
o r
Filter Type
B Single stage
BS High performance
Single stage.
Electrical Schematics
Omit for dual stage
6FCD10
Power line Device
Input / Output Style
10 Terminal Block
FCD Series
Current Rating
6, 12, 16, 25, 36, 50, 80, 110,
150, 180 or 230A
PE PE
118
Dimensions are in inches and millimeters unless otherwise specied. Values in italics For email, phone or live chat, please go to
te.com/help
are metric equivalents. Dimensions are shown for reference purposes only.
corcom.com
Specications subject to change.Three Phase Filters
Catalog: 1654001
Corcom Product Guide Issue Date: 06.2011
3-phase Delta External Filter for Frequency Converters (continued)
FCD Series
Electrical Schematics Available Part Numbers
(continued)
6FCD10 12FCD10B 50FCD10BS
12 to 50A FCD10
12FCD10 16FCD10B 80FCD10BS
Power line Device
L1 L1
16FCD10 25FCD10B 110FCD10BS
25FCD10 36FCD10B 150FCD10BS
L2 L2
36FCD10 50FCD10B 150FCD10BS-95
L3 L3
50FCD10 80FCD10B 180FCD10BS
110FCD10B 230FCD10BS
150FCD10B
150FCD10B-95
2
PE PE
180FCD10B
230FCD10B
12 to 50A FCD10B
Case Styles
Power line Device
L1 L1
6 to 50A FCD10 & FCD10B
.260
Slots:
L2 L2
6.61
L3 L3
BD
PE PE
F
80 to 230A FCD10B
E
Power line Device
L1 L1
L2 L2
C
L3 L3
A
80 to 150A FCD10B
50 to 150A FCD10BS
.260
PE PE Slots:
6.61
FCD10BS
BD
Power line Device
L1 L1
L2 L2
F
L3 L3 E
150FCD10B-95
Terminal Block
C
PE PE
A
A (150FCD10B-95)
119
Dimensions are in inches and millimeters unless otherwise specied. Values in italics For email, phone or live chat, please go to
te.com/help
are metric equivalents. Dimensions are shown for reference purposes only.
corcom.com
Specications subject to change.