Catalog: 1654001 Corcom Product Guide Issue Date: 06.2011 3-phase Delta External Power Line Filter for Frequency Converters FCD Series UL Recognized 6FCD10 FCD Series Specications Maximum leakage current Suitable to meet the latest EMC standards voltage drop to virtual N to PE/V: Insulated safety terminals 6FCD10: .26 mA/V Suitable for EMC troubleshooting in the eld 12 & 16FCD10: .45 mA/V 25, 36 & 50FCD10: .52 mA/V Very high attenuation 12 & 16FCD10B: .46 mA/V High insertion loss 25& 36FCD10B: .52 mA/V BS models optimized for very high insertion loss 50FCD10B: .57 mA/V 80 & 110FCD10B: .62 mA/V BS models suitable for infeed/regenerative (ER) 150FCD10B: .63 mA/V applications 180 & 230FCD10B: .92 mA/V Touch safe terminals provide easy connections FCD10BS: 3.25 mA/V and prevent inadvertent contact for safety in the Hipot rating (one minute): most demanding applications Line to Ground: 2250 VDC Line to Line: 1450 VDC Rated Voltage (max): Phase to Phase: 480 VAC Ordering Information Phase to Neutral / Ground: 277 VAC 150 FCD 10 BS -95 Operating Frequency: 50/60 Hz Rated Current: 6 to 230A Terminal Block Option Operating Ambient Temperature Range -95 95mm terminal block (at rated current I ): -10C to +40C available on 150A only r In an ambient temperature (T ) higher than +40C omit for standard terminals a the maximum operating current (I ) is calculated as o follows: I = I (85-Ta)/45 o r Filter Type B Single stage BS High performance Single stage. Electrical Schematics Omit for dual stage 6FCD10 Power line Device Input / Output Style 10 Terminal Block FCD Series Current Rating 6, 12, 16, 25, 36, 50, 80, 110, 150, 180 or 230A PE PE 118 Dimensions are in inches and millimeters unless otherwise specied. Values in italics For email, phone or live chat, please go to te.com/help are metric equivalents. Dimensions are shown for reference purposes only. corcom.com Specications subject to change.Three Phase Filters Catalog: 1654001 Corcom Product Guide Issue Date: 06.2011 3-phase Delta External Filter for Frequency Converters (continued) FCD Series Electrical Schematics Available Part Numbers (continued) 6FCD10 12FCD10B 50FCD10BS 12 to 50A FCD10 12FCD10 16FCD10B 80FCD10BS Power line Device L1 L1 16FCD10 25FCD10B 110FCD10BS 25FCD10 36FCD10B 150FCD10BS L2 L2 36FCD10 50FCD10B 150FCD10BS-95 L3 L3 50FCD10 80FCD10B 180FCD10BS 110FCD10B 230FCD10BS 150FCD10B 150FCD10B-95 2 PE PE 180FCD10B 230FCD10B 12 to 50A FCD10B Case Styles Power line Device L1 L1 6 to 50A FCD10 & FCD10B .260 Slots: L2 L2 6.61 L3 L3 BD PE PE F 80 to 230A FCD10B E Power line Device L1 L1 L2 L2 C L3 L3 A 80 to 150A FCD10B 50 to 150A FCD10BS .260 PE PE Slots: 6.61 FCD10BS BD Power line Device L1 L1 L2 L2 F L3 L3 E 150FCD10B-95 Terminal Block C PE PE A A (150FCD10B-95) 119 Dimensions are in inches and millimeters unless otherwise specied. Values in italics For email, phone or live chat, please go to te.com/help are metric equivalents. Dimensions are shown for reference purposes only. corcom.com Specications subject to change.