Catalog 1308242
P&B
Issued 11-15
KUP93 series
General Purpose
3 to 10 Amp, Multicontact
AC or DC Relay
File E22575
File LR15734
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that users also seek out the pertinent approvals files
of the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Features
Coil Data
AC coils 24, 120 & 240V 50/60 Hz.; DC 12 & 24VDC.
DC Nominal
Contact arrangement to 3PDT.
Nominal Must
Sockets available for all models. Resistance Coil
Voltage Operate
Accepted pin pattern for HVAC industry.
in Ohms Current
Voltage
Primarily designed for the HVAC industry.
10%*
(mA)
DC 12 120 9.0 100
Coils 24 472 18.0 51
24 72 20.4 115
AC
120 1,700 102.0 24
Coils
240 7,200 204.0 12
*AC coils, 15%
Contact Data @ 25C
Material: Fine silver or silver-cadmium oxide.
Contact rating Operate Data @ 25C
Must Operate Voltage:
Life
DC Coils: 75% of nominal voltage or less.
Material
UL/CSA Ratings
Expected
AC Coils: 85% of nominal voltage or less.
Operate Time (Excluding Bounce): 15 milliseconds, typical,
5A @ 28VDC or 240VAC, 80% PF, 1/10
at nominal voltage.
Fine silver 100,000
HP @ 120VAC, 1/4 HP @ 240VAC
Release Time (Excluding Bounce):
DC Coils: 10 milliseconds, typical, at nominal voltage.
10A @ 28VDC or 240VAC, 80% PF,
100,000
AC Coils: 10 milliseconds, typical, at nominal voltage.
Silver cadmiun 1/4 HP @ 120VAC, 1/3 HP @ 240 VAC
oxide 10 FLA, 30 LRA @ 120 VAC, 5 FLA,
30,000
15 LRA @ 240 VAC
Environmental Data
Temperature Range:
Storage:
All Coils: -45C to +105C.
Initial Dielectric Strength
Between Open Contacts: 500V rms.
Operating:
Between Adjacent Contacts: 1,500V rms.
DC Coils: -45C to +70C.
Between Contacts and Coil: 1,500V rms.
AC Coils: -45C to +45C.
Coil Data @ 25C
Mechanical Data
Nominal Power:
DC Coils: 1.2 Watts.
Termination: .187 x .020 quick connect.
AC Coils: 2.7VA.
Enclosures: Clear polycarbonate dust cover.
Initial Insulation Resistance: 100 megohms, min., at 25C.r
Weight: 3.0 oz. (86g) approximately.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.te.com
reference purposes only.N (millimeters) unless otherwise subject to change. Technical support:
731
specified. Refer to inside back cover.Catalog 1308242
P&B
Issued 11-15
Ordering Information
Typical Part No. > KUP93 14 A 2 1 -24
1. Type:
KUP93 = Enclosed general purpose relay.
2. Contact Arrangement:
14 = 3 Form C (3PDT)
3. Coil Input:
A = AC D = DC
4. Mounting:
1 = PLAIN CASE;
5. Terminals, Contact Material & Rating:
1 = .187 (4.75mm) quick connect, silver, 5 amps.
3 = .187 (4.75mm) quick connect, silver-cadmium oxide, 10 amps.
6. Coil Voltage:
To 240VAC, 50/60 Hz. or 110VDC.
Our authorized distributors are more likely to stock the following items for immediate delivery.
No items in this series typically are stocked.o
Outline Dimensions Wiring Diagrams
3 Form C
5
2
8
6
9
3
4
1
7
C2 C1
KUP93 Sockets Socket PC Board Layout (Component Side of Board)
.218 REF.
.205 DIA.
(5.54) .790
(5.21)
20.07
(2 HOLES)
.395 .161 .005
.276
(10.03)
(4.09 .13)
2.350 (7.01)
DIA. (2) HOLES
.062
(59.69)
.338
(1.57)
MTG. HOLE
(8.58)
1.858
.737
.157 .003
(47.19)
(18.72)
(3.99 .08)
1.858
.710 (47.19)
(18.03) .097 .004
(2.46 .10)
.790
.469 .015 .465
DIA. (11) HOLES
(20.07) (11.91 .38) (11.81)
.100 .317
1.250
(2.54) (8.05)
(31.75)
KUP93 Socket Number
Socket P C Socket With
Color Terminals
Natural Nylon 27E168**
**UL Recognized, file E22575
Socket: Rated 10 amperes. Will accept .187 (4.75mm)
quick-connect terminals of all KUP93 relays.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.te.com
reference purposes only.N (millimeters) unless otherwise subject to change. Technical support:
732
specified. Refer to inside back cover.
1.308
(33.22)