Catalog 1308242 Issued 3-03 P&B CS series Solid State Hybrid Voltage Sensor Close differential Choice of two types Fixed pick-up and knob adjustable drop-out Knob adjustable pick-up and drop-out Internal 2 Form C (DPDT) output relay File E22575 Fixed Pick-up and Adjustable Pick-up File LR15734 Adjustable Drop-out and Drop-out Users should thoroughly review the technical data before selecting a product part number. It is recommended that user also seek out the pertinent approvals files of the agencies/laboratories and review them to ensure the product meets the requirements for a given application. Engineering Data Sensing Modes Power Requirement: Typically less than 3VA or 3W. The CS can be used as an over or undervoltage sensor, depending upon Duty Cycle: Continuous. whether the load is connected to the normally closed (NC) or normally open Repeatability: 1%, max. (NO) contacts of the sensors output relay. Response Time: 10-25 ms, typ. Internal Relay Contact Arrangement: 2 Form C (DPDT). Overvoltage sensor The NC contacts are used. The relay remains de- Internal Relay Contact Rating: 10A 28VDC , res., or 120VAC, 80% p.f. energized until an overvoltage is sensed. Reverse Polarity Protection: On DC types. Temperature Range: -10C to +55C. Undervoltage sensor The NO contacts are used. The relay remains en- Temperature Coefficient: 0.2%/C, max. ergized until the voltage decreases to the preset level, where the sensor Enclosure: Plastic dust cover. de-energizes the relay. Mounting: 8-pin octal style plug. Fits either 27E122 or 27E891 (snap-on) screw terminal sockets. Weight: 8 oz. (227g) approximately. Adjustable Voltage Sensor Operation Ordering Information Distributors are more likely to stock boldface items. Note 1 As voltage increases, the RELAY Fixed Pick-Up and Adjustable Drop-Out relay will pick-up at its selected ENERGIZED point and remain energized while Part Number Pick-Up Drop-Out Range Maximum voltage is maintained at that level or (Volts) (Volts) Voltage higher. CSJ-38-71010 105 90-103 140VAC (50/60 Hz.) CSL-38-31010 22 16-21 32VDC Note 2 As voltage decreases, af- HYSTERISIS ter pick-up, the relay will drop-out at Adjustable Pick-Up and Adjustable Drop-Out 2 VOLTS its selected point. Part Number Pick-Up Range Drop-Out Range* Maximum (Volts) (Volts) Voltage Note 3 Minimum hysterisis, the RELAY CSJ-38-70010 92-140 90-138 150VAC (50/60 Hz.) voltage differential between pick-up DE-ENERGIZED CSL-38-30010 20-30 18-28 32VDC and drop-out, is typically 2% of CSL-38-40010 40-58 38-56 60VDC pick-up. CSL-38-60010 92-140 90-138 150VDC * Actual maximum drop-out voltage is the selected pick-up voltage less the hysterisis voltage. NOTE 1 NOTE 2 Outline Dimensions Wiring Diagrams Bottom Views (pins numbered clockwise from keyway) 1.781 MAX600 MAX. (42.24) (15.24) .875 2.937 MAX560 (22.23) (76.60) (14.22) - 1.187 + AC DC (30.15) INPUT INPUT Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 1302 specified. Refer to inside back cover. VOLTAGE 2.406 MAX. (61.11)X-ON Electronics Largest Supplier of Electrical and Electronic Components Click to view similar products for General Purpose Relays category: Click to view products by TE Connectivity manufacturer: Other Similar products are found below : PCN-105D3MH,000 59641F200 5JO-1000CD-SIL LY1SAC110120 5X827E 5X837F 5X840F 5X842F 5X848E LY2N-AC120 LY2S- AC220/240 LY2-US-AC120 LY3-US-AC120 LY4F-UA-DC12 LY4F-UA-DC24 LY4F-US-AC120 LY4F-US-AC240 LY4F-US-DC24 LY4F-VD-AC110 LYQ20DC12 M115C60 M115N010 M115N0150 6031007G 603-12D 61211T0B4 61212T400 61222Q400 61243B600 61243C500 61243Q400 61311BOA2 61311BOA6 61311BOA8 61311C0A2 61311COA1 61311COA6 61311F0A2 61311QOA1 61311QOA4 61311T0D6 61311TOA6 61311TOA7 61311TOB3 61311TOB4 61311U0A6 61312Q600 61312T400 61312T600 61313U200