SCD
SHF260-0113
SPECIFICATION CONTROL DRAWING
Date Revision
Title
WIRE, MODIFIED PERFLUOROALKOXY COPOLYMER RESIN-INSULATED, 1000 VOLT
7-10-17 K
This specification sheet forms a part of the latest issue of Raychem Specification WCD 3111.
CONDUCTOR - NICKEL-COATED COPPER INSULATION - MODIFIED PFA
TABLE I. CONSTRUCTION DETAILS
FINISHED WIRE
DIAMETER OF
CONDUCTOR
MAXIMUM
WIRE
STRANDED CONDUCTOR NOMINAL
DIAMETER
PART NUMBER STRANDING
RESISTANCE
SIZE
WEIGHT
(inch) (mm)
(inch) mm)
1/ (number x
AT 20C
(AWG)
(lbs/1000 ft.)
AWG)
(ohms/1000 ft.)
(kg/km)
(ohms/km)
MINIMUM MAXIMUM MINIMUM NOMINAL MAXIMUM
SHF260-0113-24-* 24 105 x 44 .023 (.584) .027 (.686) 30.6 (100.) .050 (1.27) .053 (1.35) .056 (1.42) 3.10 (4.61)
SHF260-0113-22-* 22 154 x 44 .029 (.737) .033 (.838) 21.9 (71.8) .058 (1.47) .061 (1.55) .064 (1.63) 4.23 (6.29)
SHF260-0113-20-* 20 154 x 42 .037 (.940) .043 (1.09) 13.3 (43.6) .069 (1.75) .072 (1.83) .075 (1.91) 5.96 (8.87)
SHF260-0113-18-* 18 259 x 42 .047 (1.19) .053 (1.35) 8.67 (28.4) .079 (2.01) .082 (2.08) .085 (2.16) 8.58 (12.8)
SHF260-0113-16-* 16 259 x 40 .061 (1.55) .067 (1.70) 5.10 (16.7) .093 (2.36) .096 (2.44) .099 (2.51) 12.2 (18.2)
SHF260-0113-14-* 14 665 x 42 .078 (1.98) .086 (2.18) 3.32 (10.9) .112 (2.84) .116 (2.95) .120 (3.05) 19.1 (28.4)
SHF260-0113-12-* 12 665 x 40 .096 (2.44) .106 (2.69) 1.99 (6.53) .131 (3.33) .137 (3.48) .143 (3.63) 27.3 (40.6)
SHF260-0113-10-* 10 665 x 38 .126 (3.20) .140 (3.56) 1.14 (3.74) .163 (4.14) .171 (4.34) .179 (4.55) 44.7 (66.5)
SHF260-0113-8-* 8 665 x 36 .157 (3.99) .173 (4.39) .714 (2.34) .195 (4.95) .205 (5.21) .215 (5.46) 67.7 (101.)
SHF260-0113-6-* 6 1045 x 36 .192 (4.88) .208 (5.28) .490 (1.61) .231 (5.87) .242 (6.15) .253 (6.43) 102. (152.)
SHF260-0113-4-* 4 1665 x 36 .265 (6.73) .285 (7.24) .326 (1.07) .310 (7.87) .323 (8.20) .336 (8.53) 168. (250.)
SHF260-0113-2-* 2 1665 x 34 .325 (8.26) .345 (8.76) .193 (.633) .373 (9.47) .387 (9.83) .401 (10.2) 250. (372.)
SHF260-0113-1-* 1 2109 x 34 .370 (9.40) .400 (10.2) .163 (.535) .426 (10.8) .441 (11.2) .456 (11.6) 308. (458.)
SHF260-0113-0-* 0 2660 x 34 .435 (11.0) .465 (11.8) .133 (.436) .494 (12.5) .510 (13.0) .526 (13.4) 395. (588.)
SHF260-0113-00-* 00 3325 x 34 .485 (12.3) .515 (13.1) .102 (.335) .546 (13.9) .564 (14.3) .582 (14.8) 491. (731.)
SHF260-0113-000-* 000 4123 x 34 .540 (13.7) .575 (14.6) .073 (.240) .606 (15.4) .626 (15.9) .646 (16.4) 604. (899.)
SHF260-0113-0000-* 0000 5320 x 34 .615 (15.6) .655 (16.6) .057 (.187) .685 (17.4) .707 (18.0) .729 (18.5) 774. (1152.)
NOTE: Nominal values are for information only. Nominal values are not requirements.
Users should evaluate the suitability of this product for their application. Specifications are subject to change without notice.
TE Connectivity also reserves the right to make changes in materials or processing, which do not affect compliance with any specification, without notification to Buyer.
1/ COLORS AND COLOR CODE DESIGNATORS SHALL BE IN ACCORDANCE WITH MIL-STD-681. OTHER CODES AND SUFFIXES MAY BE
ADDED TO THE PART NUMBER, AS NECESSARY, TO CAPTURE ANY ADDITIONAL REQUIREMENTS IMPOSED BY THE PURCHASE ORDER.
Raychem, TE Connectivity, and TE connectivity (logo) are trademarks.
Raychem Wire & Cable
501 Oakside Avenue
DIMENSIONS ARE IN INCHES AND, UNLESS OTHERWISE DESIGNATED, ARE NOMINAL.
Redwood City, CA 94063-3800
Page 1 of 2
Phone: 1-800-522-6752
THIS SPECIFICATION SHEET TAKES PRECEDENCE OVER DOCUMENTS REFERENCED HEREIN.
Fax: 1-650-361-6297
REFERENCED DOCUMENTS SHALL BE OF THE ISSUE IN EFFECT ON DATE OF INVITATION FOR BID.
2014-2017 TE Connectivity Ltd. family of companies. All Rights Reserved.
Page Revision SCD
SPECIFICATION CONTROL DRAWING
2 of 2 K SHF260-0113
TABLE II. PERFORMANCE DETAILS
BEND TESTING
MANDREL DIAMETER WEIGHT
PART NUMBER
(inch) (mm) ( 3%) (lb) (kg) ( 3%)
1/
LIFE MINIMUM WRAP COLD LIFE COLD
CYCLE BEND RADIUS TEST BEND CYCLE BEND
SHF260-0113-24-* .500 (12.7) .500 (12.7) .500 (12.7) 1.00 (25.4) 1.50 (.680) 3.00 (1.36)
SHF260-0113-22-* .500 (12.7) .750 (19.1) .750 (19.1) 1.00 (25.4) 2.00 (.907) 3.00 (1.36)
SHF260-0113-20-* .500 (12.7) .750 (19.1) .750 (19.1) 1.00 (25.4) 3.00 (1.36) 4.00 (1.81)
SHF260-0113-18-* .750 (19.1) 1.00 (25.4) 1.00 (25.4) 1.50 (38.1) 4.00 (1.81) 4.00 (1.81)
SHF260-0113-16-* 1.00 (25.4) 1.00 (25.4) 1.00 (25.4) 1.50 (38.1) 4.00 (1.81) 5.00 (2.27)
SHF260-0113-14-* 1.00 (25.4) 1.25 (31.8) 1.25 (31.8) 2.00 (50.8) 6.00 (2.72) 5.00 (2.27)
SHF260-0113-12-* 1.50 (38.1) 1.50 (38.1) 1.50 (38.1) 2.00 (50.8) 6.00 (2.72) 5.00 (2.27)
SHF260-0113-10-* 2.00 (50.8) 2.00 (50.8) 2.00 (50.8) 3.00 (76.2) 6.00 (2.72) 5.00 (2.27)
SHF260-0113-8-* 3.00 (76.2) 2.25 (57.2) 2.25 (57.2) 4.00 (102.) 8.00 (3.63) 6.00 (2.72)
SHF260-0113-6-* 4.00 (102.) 2.75 (69.9) 2.75 (69.9) 5.00 (127.) 8.00 (3.63) 10.0 (4.54)
SHF260-0113-4-* 5.00 (127.) 3.75 (95.3) 3.75 (95.3) 6.00 (152.) 8.00 (3.63) 10.0 (4.54)
SHF260-0113-2-* 6.00 (152.) 4.50 (114.) 4.50 (114.) 8.00 (203.) 12.0 (5.44) 15.0 (6.80)
SHF260-0113-1-* 8.00 (203.) 5.00 (127.) 5.00 (127.) 10.0 (254.) 12.0 (5.44) 15.0 (6.80)
SHF260-0113-0-* 8.00 (203.) 6.00 (152.) 6.00 (152.) 10.0 (254.) 12.0 (5.44) 15.0 (6.80)
SHF260-0113-00-* 10.0 (254.) 6.00 (152.) 6.00 (152.) 12.0 (305.) 16.0 (7.26) 20.0 (9.07)
SHF260-0113-000-* 10.0 (254.) 7.50 (191.) 7.50 (191.) 12.0 (305.) 16.0 (7.26) 20.0 (9.07)
SHF260-0113-0000-* 10.0 (254.) 8.00 (203.) 8.00 (203.) 12.0 (305.) 16.0 (7.26) 20.0 (9.07)
WIRE RATINGS AND ADDITIONAL REQUIREMENTS
TEMPERATURE RATING: 260C for 10,000 hours THERMAL SHOCK RESISTANCE: 260 2C,
VOLTAGE RATING: 1000 volts (rms) at sea level AWG 24-12: 0.060 in. (1.52 mm) (maximum)
COLOR: White preferred AWG 10-8: 0.100 in. (2.54 mm) (maximum)
CONCENTRICITY: 70% (minimum) AWG 6-00: 0.125 in. (3.18 mm) (maximum)
INSULATION ELONGATION AND TENSILE STRENGTH: AWG 000-0000: 0.250 in. (6.35 mm) (maximum)
Elongation, 150% (minimum) UV LASER MARKING (Per SAE AS4373, Method 1001):
2 2
Tensile Strength, 2000 lbf/in (13.8 N/mm ) (minimum) AWG 24-2, white (-9) wire only:
INSULATION FLAWS: Solid Laser, 50% (minimum)
Spark Test, 6.0 kV (rms) Dot Matrix Laser, 50% (minimum)
Impulse Dielectric Test, 8.0 kV (peak) VOLTAGE WITHSTAND (Post Environmental): 3000 volts (rms)
LOW TEMPERATURE-COLD BEND: -65 2C for 4 hours WRAP TEST: 290 2C for 2 hours
SHRINKAGE: 290 2C for 6 hours,
AWG 24-00: 0.125 in. (3.18 mm) (maximum) in 12 inches (305 mm) 1/ PART NUMBER:
AWG 000-0000: 0.250 in. (6.35 mm) (maximum) in 12 inches (305 mm) The in the part numbers in Tables I and II shall be replaced by
SMOKE TEST (Qualification): a color code designator.
Per WCD 3111, no visible smoke Example: AWG 0, white: SHF260-0113-0-9
Per SAE AS4373, Method 803 (Flaming Mode only),
0.02 Ds (nominal) after 16 minutes
1/ See footer section on page 1