Catalog 1308242 Issued 3-03 (PDF Rev. 5-05) P&B P30/P40 series Definite Purpose Magnetic Contactor 30/40 Ampere Full Load 40/50 Ampere Resistive AC & DC Coils File E22575 File LR15734 Users should thoroughly review the technical data before selecting a product part DC Coil AC Coil number. It is recommended that users also seek out the pertinent approvals files of the agencies/laboratories and review them to ensure the product meets the requirements for a given application. Coil Data Features Nominal Resistance Must Maximum Nominal Coil AC and DC coils. VDC (Ohms 10% Operate* Operating Current (ma) Available with auxiliary switch. 25 C) Volts Volts Nominal Voltage Variety of main contact terminals. 12 20.8 9 15 577 For control of motors, power supplies, heating elements and lighting. 24 84 18 30 286 48 334 36 57 144 120 2,110 90 144 57 Contact Data 25C Arrangements: Up to 4 Form X (4PST-NO-DM) Ratings: See contact rating table. Material: Silver-cadmium oxide. Expected Life: 200,000 operations at full load. AC Voltage Nominal Must Operate* AC coil: 2 million operations, mechanical. Rating 50/60 Hz. 50/60 Hz. DC coil: 10 million operations, mechanical. 24 24 20.4 Minimum Contact Data: 3A 120VAC. 120 110/120 94 240 208/240 177 277 277 236 Main Contact Ratings Motor Rating in Amps, 33P or 12P Resistive Tungsten *Applicable for vertical mounting, but not for upside-down mounting. Type Full Load Locked Rotor Rating Rating Note: Coil suppression is recommended for all DC coil units, particulary 120 and 600V 240V 480V 600V 600V 277V 240VDC coils. P30 30A 180A 150A 120A 40A 40A P40 40A 240A 200A 160A 50A 50A Operate Data P30 Electrical Discharge Lamp Control: 40A 240V (Delta), 40A 600V (Wye). P40 Electrical Discharge Lamp Control: 50A 600V (Wye). Must-Operate Voltage: See coil data tables. Motor Rating in Horsepower Type 120V 240V 440-600V P30 12P 1.5HP 3HP 33P 3HP 7.5HP 7.5HP P40 12P 2HP 5HP Environmental Data 33P 5HP 10HP 15HP Temperature Range: 55C to +65C. Auxiliary Snap-Action Switch Arrangements: Up to 2 Form C (DPDT). Rating: 10 amps at 120-250VAC 25C. Material: Silver. Mechanical Data Mounting: Universal mounting bracket. See outline drawings. Initial Dielectric Strength Termination: Initial Breakdown Voltage: 2,200V rms minimum between all elements Contacts: Binder screw, box lug, captive pressure plate, combination and between all elements to ground. screw and dual .250 (6.35mm) quick connect, or combination box lug and dual .250 (6.35mm) quick connect. See Main Contact Terminal Options photo. Coil Data 25C Coil: Combination 8-32 screw and .250 (6.35mm) quick connect. Aux. Switch: .187 (4.75mm) quick connect. Voltage: From 12 to 120VDC, and 24 to 277VAC, 50/60 Hz. Weight: 3 Pole Models: 25 oz. (709g) approximately. Power: DC, 7.5 W AC, 92VA, In rush 12 VA Sealed. 4 Pole Models: 28 oz. (794g) approximately. Duty Cycle: Continuous. Insulation Class: Class A, standard, Class B available. Initial Insulation Resistance: 100 megohms, minimum. Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 823 specified. Refer to inside back cover.Catalog 1308242 Issued 3-03 (PDF Rev. 5-05) P&B Ordering Information Typical Part No. B P30 P 42 A 1 4 P 1 -240 1. Type: P30 = Definite Purpose Contactor, 30 amp. P40 = Definite Purpose Contactor, 40 amp. 2. Auxiliary Switch: P = No Aux. Switch C = 1 Form C (SPDT) F = 2 Form C (DPDT) 3. Main Contact Arrangement: 42 = 3 Form X (3PST-NO-DM) 47 = 4 Form X (4PST-NO-DM) 43 = 2 Form X (DPST-NO-DM) 48 = 2 Form X (DPST-NO-DM) & 1 Form Y (SPST-NC-DB) & 2 Form Y (DPST-NC-DB) 45 = 1 Form X (SPST-NO-DB) 49 = 4 Form Y (4PST-NC-DB) & 2 Form Y (DPST-NC-DB) Other contact arrangements are available. 4. Coil Control Input: A = Alternating Current, 50/60 Hz. D = Direct Current 5. Mounting and Installed Accessories: 1 = Standard Mounting 6. Main Contact Terminals: 2 = Screw Terminals 5 = Captive Pressure Plate 3 = Screw Terminals & Dual .250 (6.35mm) Quick Connect 6 = Box Lug & Dual .250 (6.35mm) Quick Connect 4 = Box Lug 7. Auxiliary Contact Terminals: P = No Auxiliary Switch C = .187 (4.75mm) Quick Connect 8. Coil Terminals: 1 = Combination 8-32* Screw Terminal and .250 (6.35mm) Quick Connect 9. Coil Voltage: 24, 120, 240 or 277VAC 12, 24 or 120VDC Our authorized distributors are more likely to maintain the following items in stock for immediate delivery. P30P42A12P1-120 P40P42A12P1-24 P30P42D12P1-24 P40P42A12P1-120 P30P47A12P1-120 P40P42A12P1-240 P30P47D12P1-24 P40P42D12P1-24 Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 824 specified. Refer to inside back cover.