P O W E R T R A N S F O R M E R CHASSIS MOUNT : TOROIDAL WORLD SERIES VPT230-10870 Electrical Specifications ( 25C) 1. Maximum Power: 2500VA 2. Input Voltage: Series: 230VAC, 50/60Hz Parallel: 115VAC, 50/60Hz 3. Output Voltage: Series: 230VAC CT 10.87A Parallel: 115VAC 21.74.0A 4. Voltage Regulation: 2.5% TYP from full load to no load 5. Temperature Rise: 50C TYP 6. Hipot: 4000VAC, Primary to Secondary 7. Efficiency: 97% TYP. full load RoHS 2002/95/EC Construction: The toroidal construction inherently helps reduce stray fields, increases efficiency and minimizes size compared to traditional EI transformers. Built with Class B (130) insulation system. Safety: World Series Transformers are designed and manufactured to meet most International Safety agency standards. OD Agency File: UL: File E122529, UL 5085-1 & 2 CE: EN 61558-1:2005, EN 61558-2-6:1995, Low Voltage Directive (LVD) EN 6-000-6-6:2001+A11:2004, EN 55014-1:2000+A1:2001+A2:2002, EN 6100-6-1:2001, EN 55014-2:1997+A1:2001, Electromagnetic Compatibility (EMC) FLAT BOLT MOUNTING WASHER METAL Dimensions (mm): PLATE H O.D. 120.0 Max 210.0 Max H Weight: 19.4Kg Mounting: SPRING RUBBER Transformer is provided with one rubber, M8 x 120mm bolt, nut, spring and flat WASHER NUT PAD washer. Connections: S Transformer is provided with 12 (305mm) long, 0.50 (12.7mm) stripped and tinned, E stranded UL 1015 lead wire. Primaries are 14AWG, Secondaries are 14AWG. P BLUE BLACK 1 C Input : Series BLUE and BROWN, Jumper GRAY to VIOLET R Parallel BLUE and BROWN, Jumper BLUE to VIOLET, GRAY to BROWN O 1 I Output : Series BLACK and YELLOW, Jumper RED to ORANGE GRAY RED Parallel BLACK and YELLOW, Jumper BLACK to ORANGE, RED to YELLOW N M RoHS Compliance: As of manufacturing date February 2016, all standard products VIOLET ORANGE D meet the requirements of 2015/863/EU, known as the RoHS 3 initiative. A A R * Upon printing, this document is considered uncontrolled. Please contact Triad Magnetics website for the BROWN YELLOW most current version. R Y SCHEMATIC Y 1 Primary and secondary windings are designed to be connected in series or parallel. Windings are not intended to be used independently. Web: www.TriadMagnetics.com 460 Harley Knox Blvd. Phone 951-277-0757 Publish Date: October 12, 2021 Perris, California 92571 Fax 951-277-2757 X-ON Electronics Largest Supplier of Electrical and Electronic Components Click to view similar products for Power Transformers category: Click to view products by Triad manufacturer: Other Similar products are found below : ET-030A F-102X F-120X F-14X-1 F-181U F-18A F-199U F-19X F-202U F-204U F-206U F-227X F-238U F-239U-1 F-23U F24-250-B F-242U F-245U F-264U F-265U F-267U F-281U F-283U F-290X F-295Z F-296Z F-298Z F-3143P F-3298Z F-33U F-346X F-35U F- 364U F-392A F-395X F-397U F-412X F-47U F-55X-1 F-60U F-68U F-71U F-72Z F-74U F-83A F-84AC F-85U F-86U F-9U PCT-02