Datenblatt Weidmller Interface GmbH & Co. KG RS-SERIES Klingenbergstrae 16 RS 30 24VUC LD LP 1A D-32758 Detmold Germany Fon: +49 5231 14-0 Fax: +49 5231 14-292083 www.weidmueller.com Clip-on RS 30. 31. 32 relay bases are available in widths from 11.2 to 25 mm, depending on the type. The RSM relay multiplexers are available as 4, 8 and 16-way modules. To reduce the wiring work, the DC variants are fitted with a common plus or minus potential. The optional IEC603-1 plug-in connector enables the connection of pre-assembled lines. The screw connection system is used to connect the conductor with a rated cross-section of 2.5 mm. General ordering data Type RS 30 24VUC LD LP 1A Order No. 1101721001 Version RS-SERIES, Relays, No. of contacts: 1, NO contact, AgNi 0.15 gold flashed, Rated control voltage: 24 V UC 10 %, Continuous current: 6 A, Screw connection GTIN (EAN) 4032248032020 Qty. 10 pc(s). Erstellungs-Datum November 13, 2014 11:35:26 AM CET Katalogstand 15.08.2014 / Technische nderungen vorbehalten 1Datenblatt Weidmller Interface GmbH & Co. KG RS-SERIES Klingenbergstrae 16 RS 30 24VUC LD LP 1A D-32758 Detmold Germany Fon: +49 5231 14-0 Fax: +49 5231 14-292083 www.weidmueller.com Technische Daten Dimensions and weights Width 11.2 mm Height 70 mm Depth 56 mm Net weight 30.6 g Temperatures Humidity 40 C / 93 % rel. humidity, Operating temperature no condensation -25 C...40 C Storage temperature -40 C...60 C Input Rated control voltage 24 V UC 10 % Rated current AC 9 mA Rated current DC 9 mA Power rating 0.45 W // 0.7 VA Pull-in/drop-out voltage, typ. 21.5 V DC Pull-in/drop-out current, typ. 3.5 mA DC Output Max. switching voltage, AC 250 V Continuous current 6 A Inrush current 8 A AC switching capacity (resistive), max. 2000 VA Switch-on delay 8 ms Switch-off delay 16 ms Duration of Bounce 3 ms Min. switching power 250 mW Max. switching frequency at rated load 0.1 Hz Contact data No. of contacts 1 Contact design NO contact 6 Contact material Mechanical service life AgNi 0.15 gold flashed 20 x 10 switching cycles 5 5 Electrical service life of AC coil Electrical service life, DC coil > 7x10 Switching cycles > 5x10 switching cycles General data Version Relay coupler Insulation coordination Rated voltage Creepage and clearance distance input 250 V output > 3 mm Impulse withstand voltage 4 kV Protection degree IP 20 Pollution severity 2 Surge voltage category III Further details of approvals / standards Standards DIN EN 50178 Connection data Wire connection method Screw connection Clamping range, rated connection 2.5 mm Clamping range, rated connection, min. 0.5 mm Clamping range, rated connection, max. 4 mm Stripping length, rated connection 8 mm Erstellungs-Datum November 13, 2014 11:35:26 AM CET Katalogstand 15.08.2014 / Technische nderungen vorbehalten 2