Data sheet Weidmller Interface GmbH & Co. KG SCS 24VDC P1SIL3DS M Klingenbergstrae 26 D-32758 Detmold Germany www.weidmueller.com This safety relay is used in areas of process automation that require a functionally safe switch-off. The module meets the requirements for SIL3 according to EN 61508. Variant with monitoring circuit TUV certified and with Approved Safety Function cULus certified Multi-voltage input (24 - 230 V UC) in the monitoring circuit Available with G3 paint according to EN 60068-2-60 Externally accessible fuse General ordering data Version SAFESERIES, Safety relay,24 V DC 20%, 35 mA , Max. switching current, internal fuse : 5 A (refer to derating curve), SIL 3, EN 61508:2010 Order No. 1303760000 Type SCS 24VDC P1SIL3DS M GTIN (EAN) 4050118102703 Qty. 1 pc(s). Creation date January 22, 2022 11:36:56 AM CET Catalogue status 14.01.2022 / We reserve the right to make technical changes. 1Data sheet Weidmller Interface GmbH & Co. KG SCS 24VDC P1SIL3DS M Klingenbergstrae 26 D-32758 Detmold Germany www.weidmueller.com Technical data Dimensions and weights Depth 114.1 mm Depth (inches) 4.492 inch Height 117.3 mm Height (inches) 4.618 inch Width 22.5 mm Width (inches) 0.886 inch Net weight 200 g Temperatures Storage temperature -40 C...85 C Operating temperature -25 C...50 C Humidity 40 C / 93 % rel. humidity, no condensation Environmental Product Compliance REACH SVHC Lead 7439-92-1 Input (safety circuit) Connection designation (safety circuit) A1, A2 Rated control voltage 24 V DC 20% Current consumption Guaranteed current consumption of 24 42 mA VDC -10% 35 mA Inrush current < 250 mA / < 5 ms Status indicator LED yellow Protective circuit Reverse polarity protection, Free-wheeling diode Input (monitoring) Rated control voltage 24 V UC230 V UC 10 Current consumption 23 mA 24 V DC, 4,4 mA % 230 V AC Status indicator LED yellow Protective circuit Rectifier Output (safety circuit) Connection designation (safety output) Contact design 1 x de-energised to safe 13, 14, 15 (NO contact) Contact base material AgNi 0.15 gold flashed Max. permitted switching voltage 250 V AC / 30 V DC Max. permitted switching current Max. switching current, internal fuse 5 A (refer to derating 5 A curve) Max. switching current, external fuse 5 A (refer to derating Max. switching capacity curve) 1250 VA Internal fuse 5 A time-lag External back-up fuse 5 A time-lag Short circuit resistance No Switch-on time typ. 7 ms Switch-off time typ. 14 ms Min. switching capacity 10 mA 12 V Output (monitoring) Contact design CO contact Contact base material AgNi 5m Au Max. permitted switching voltage 24 V DC Max. allowed switching current 30 mA Switch-on time typ. 17 ms Short circuit resistant No Min. switching capacity 1 mA 1 V Control side Status indicator LED yellow Creation date January 22, 2022 11:36:56 AM CET Catalogue status 14.01.2022 / We reserve the right to make technical changes. 2