PEM-01 ELECTROMAGNETIC RELAY INSTRUCTION MANUAL Zakad Mechaniki i Elektroniki ZAMEL sp.j. J.W. Dzida, K. odziska ul. Zielona 27, 43-200 Pszczyna, Poland Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04 www.zamelcet.com, e-mail: marketing zamel.pl DESCRIPTION TECHNICAL DATA PEM-01 Electromagnetic relays may be used in /012 /024 /048 /110 /230 various applications where load current Input (supply) terminals: A1, A2 increase is needed. The relays assure Input rated voltage: 12 V AC/DC 24 V AC/DC 48 V AC/DC 110 V AC/DC 230 V AC voltaic insulation between a control unit Input voltage tolerance: -15 +10 % and a load circuit. The relays are fitted Nominal frequency: 50 / 60 Hz with NO / NC dead contacts. It is possible Rated current: 33 mA AC 15 mA AC 8,2 mA AC 4,6 mA AC 23,2 mA AC to connect voltage of 0 250 V AC to the Relay state indicator: LED green contacts. Output (load) terminals: 11, 12, 14 Control element: 1 NO/NC - 16 A / 250 V AC Numer of terminal clamps: 5 FEATURES 2 Section of connecting cables: 0,2 2,5 mm o Ambitne temperature range: -20 +45 C Operating position: free Load current increase, Mounting: TH 35 rail (PN-EN 60715) Applicable together with typical Protection degree: IP20 control systems powered with typical Protective class: II voltages: 12, 24, 48, 110 V AC/DC, Overvoltage category: II 230 V AC, Pollution degree: 2 Maximum load current 1 x 16 A, Dimensions: Relay state indicator. monomodular (17,5 mm) 90x17,5x66 mm Weight: 0,07 kg Reference standards: PN-EN 60669-1 PN-EN 60669-2-1 PN-EN 61000-4-2,3,4,5,6,11 PN-EN 61095:2004 The device is designed for one-phase installation APPERANCE and must be installed in accordance with stan- dards valid in a particu- Input (supply) terminal (A1) Input (supply) terminal (A2) lar country. The device CAUTION should be connected according to the details included in this operating manual. Installation, connec- tion and control should be carried out by a qualified electrician staff, who act in accordance with the service manual and the device functions. Disassembling of Supply voltage indicator the device is equal with a loss of guaran- tee and can cause electric shock. Before installation make sure the connection ca- bles are not under voltage. The cruciform head screwdriver 3,5 mm should be used to instal the device. Improper transport, storage, and use of the device influence its wrong functioning. It is not advisable to instal the device in the following ca- ses: if any device part is missing or the device is damaged or deformed. In case of improper functioning of the device contact the producer. The symbol stands for selective Output relay collection of electrical and terminals (11,11,14) electronic devices. Placing used devices with other waste is not allowed VER. 001 13.01.2010MOUNTING, FUNCTIONING CONNECTING TIME COURSE 1. Disconnect the electric network by means of appropriate cut-off, curren- tlimiting circuit-breaker or separator. t 2. Check if there is no any voltage between power leads by means of t an appropriate gauge. t 3. Mount the device on TH 35 rail. 4. Connect the system leads according to the electrical diagram. 5. Connect power supply circuit. INNER DIAGRAM After power supply has been con- nected to A1, A2 terminals, the device, via the control circuit, makes the relay A1 A2 output contacts 11, 14 closed. When power supply has been OFF, the relay will be OFF and the output contacts 11, 12 will be closed. 14 12 RELAY CAPACITY 11 DIMENSIONS EXAMPLE OF INSTALLATION LIGHTING SENSOR PRODUCT FAMILY The PEM-01 electromagnetic relay is a member of the PEM-xx family. Input voltage: 12V, 24V, 48V, 110V, 230V STRET Device version: LIGHTING 01 input contacts 1 x 16 A 02 input contacts 2 x 8 A Device type GUARANTEE CARD There is 24 months guarantee on the product 1. ZMIE ZAMEL SP. J. assures 24 months guarantee for the product. 2. The manufacturers guarantee does not cover any of the following actions: a) mechanical damage during transport, loading / unloading or under other circumstances, b) damage caused by incorrect product mounting or misuse, c) damage caused by unauthorised modifications made by the PURCHASER or any third parties to the product or any other devices needed for the product functioning, d) damage caused by Act of God or any other incidents independent of the manufacturer. 3. The PURCHASER shall lay any claims in writing to the dealer or ZMIE ZAMEL SP. J. 4. ZMIE ZAMEL SP. J. is liable for processing any claim according to current Polish legislation. 5. ZMIE ZAMEL SP. J. shall process the claim at its own discretion: product repair, replacement or money return. 6. The manufacturers guarantee is valid in the Republic of Poland. 7. The PURCHASERs statutory rights in any applicable legislation whether against the retailer arising from the purchase contract or otherwise are not affected by this warranty. Salesman stamp and signature, date of sale VER. 001 13.01.2010