Alpha Wire 711 Lidgerwood Avenue, Elizabeth, NJ 07207 Tel: 1-800-52 ALPHA (25742), Web: www.alphawire.com Customer Specification PART NO. 3080 Construction Diameters (In) 1) Component 1 1 X 1 HOOKUP a) Conductor 12 (65/30) AWG Tinned Copper 0.093 b) Insulation 0.032 Wall, Nom. PVC 0.157+/- 0.004 ALPHA WIRE E163872-* (UL) MTW OR TW 600V OR AWM STYLE 1015/1230 105C 600V VW-1 12 AWG ---- LLXXXX CSA AWM I A/B 105C 600V FT1 OR TEW 105C 600V FT1 (1) Print CE ROHS 0 * = Factory Code Note: Product may have c(UL) or CSA markings depending upon plant of manufacture. WHITE, BLACK, RED, GREEN, YELLOW, BLUE, BROWN (2) Color(s) ORANGE, SLATE, VIOLET, PINK, GREEN/YELLOW YELLOW/GREEN, WHITE/BLUE Applicable Specifications 105C / 600 V 1) UL AWM/STYLE 1015 RMS 90C Dry / 60C Wet / 600 V MTW RMS 105C Dry / 60C Wet / 600 V AWM/STYLE 1230 RMS 60C Dry / 60C Wet / 600 V TW RMS VW-1 105C / 600 V 2) CSA International TEW-105 RMS 105C / 600 V AWM I A/B RMS FT1 3) CE: EU Low Voltage Directive 2014/35/EU Environmental 1) EU Directive 2011/65/EU(RoHS2), EU Directive 2015/863/EU (RoHS3): All materials used in the manufacture of this part are in compliance with European Directive 2011/65/EU and the amending Directive 2015/863/EU of 4 June 2015 regarding the restriction of use of certain hazardous substances in electrical and electronic equipment. Consult Alpha Wire s web site for RoHS C of C. 2) REACH Regulation (EC 1907/2006): This product does not contain Substances of Very High Concern (SVHC) listed on the European Union s REACH candidate list in excess of 0.1% mass of the item. For up-to-date information, please see Alpha s REACH SVHC Declaration. Exempt from warning labels based on the Consent Judgment. Please see 3) California Proposition 65: Alpha s CA Prop 65 Statement for more information. Properties Physical & Mechanical Properties 1) Temperature Range -40 to 105C 2) Bend Radius 5X Cable Diameter 3) Pull Tension 51 Lbs, Maximum Electrical Properties (For Engineering purposes only) 600 V 1) Voltage Rating RMS 2) Inductance 0.05 H/ft, Nominal 3) Conductor DCR 1.75 /1000ft 20C, Nominal Other Packaging Flange x Traverse x Barrel (inches) a) 3000 FT 16 x 12 x 8 Continuous length b) 1000 FT 12 x 4.5 x 3.5 Continuous length c) 1000 FT UK 11 x 5.5 x 5 Continuous length d) 500 FT 12 x 4.5 x 3.5 Continuous length e) 100 FT UK 6.5 x 2 x 1.875 Continuous length f) 100 FT 6.5 x 2 x 1.9 Continuous length