CircuitProtection 2016.QXD CircuitProtection 4/8/16 1:47 PM Page 20 L-Series AC or DC Miniature Molded Case Circuit Breakers UL489 Listed Circuit Breakers Available in AC and DC models DIN Rail Mounted 17.5mm width Thermal Magnetic 240V, 480Y/277V AC, 50/60Hz 125VDC (1 pole) 250VDC (2 pole) 10kA Short Circuit Interrupting Capacity Positive Trip indicator (Green - off/tripped, Red - on) HACR Type 40C Line/Load reversible LISTED E305318 AC Version Current/ Voltage Rating 0.2-63A/240VAC, 0.2-32A/480Y/277VAC* DC Version Current/ Voltage Rating 0.2-63A/125/250VDC Calibration Temperature 40C (104F) Operating Temperature -25 to 60C (-13 to 140F) Storage Temperature -25 to 75C (-13 to 167F) Terminal Size Acceptability 14-3 AWG: 17.5 lb-in. (2.0 Nm) and Torque 18-16 AWG: 25 lb-in. (2.8 Nm) Terminal Protection Degree IP20 at front Electrical Life 6,000 cycles on/off Mechanical Life 10,000 cycles on/off Wire Connection copper wire only 60/75C Vibration Resistance 3g (18-50Hz) Mounting Orientation In any plane *One device dual voltage ratings. aC - short CirCuit interruptinG ratinG DC - short CirCuit interruptinG ratinG No. No. Poles Type 0.2-32A 33-63A Poles Type 0.2-32A 33-63A 1 AC 10kA 120, 240, 277V 10kA 120, 240V 1 DC 10kA 125V 10kA 125V 2-4 AC 10kA 120, 240V, 480Y/277V 10kA 120, 240V 2 DC 10kA 250V 10kA 250V Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 P 908.806-9400 F 908.806.9490 www.altechcorp.com 20 Earth Leakage UL 1077 ANNEX UL 1077 UL 508 UL 489 Circuit Breakers Equipment Breakers CircuitProtection 2016.QXD CircuitProtection 4/4/16 12:22 PM Page 21 60 40 Time 10 4 versus 1 Current Trip Curve For the exact trip curve, 10 please refer to page 25. 4 1 Dimensions in mm 0.4 side view CCCDDD -1 10 -2 4x10 -2 10 -3 4x10 -3 10 2 34 6 8 101620 6.5mm Multiple of Rated Current 44mm (1.73 in.) (0.26 in.) 60mm (2.36 in.) 14.5mm (0.57 in.) 14.5mm (0.57 in.) 14.5mm (0.57 in.) 1 PoLe 2 PoLe 3 PoLe 17.5mm (0.69 in.) 17.5mm (0.69 in.) 17.5mm (0.69 in.) 35mm (1.38 in.) 35mm (1.38 in.) 52.5mm (2.07 in.) Trip-Characteristics* Type Applications Characteristic Trip Boundaries Lighting Motors Business Power Wiring Equipment Reactive Supplies Transformers Thermal Trip Magnetic Trip Protection Load Control Appliances Heaters Low High Must not Must Trip Must not Must Trip Circuits Trip>100ms <1hr Trip>100ms at 100ms Inrush Inrush C-Characteristics 1.05xRC 1.3xRC 5xRC 10xRC AC 1.05xRC 1.3xRC 5xRC 10xRC DC D-Characteristics 1.05xRC 1.3xRC 10xRC 16xRC AC 1.05xRC 1.3xRC 10xRC 16xRC DC *The value of each characteristic is shown vertically beneath its corresponding heading. Warning This information should only be used as a selection guide. The use of a Miniature Circuit Breaker in an application with a certain Trip-Characteristic always requires prototype testing It is the responsibility of the circuit design engineer to select the appropriate Miniature Circuit Breaker for his specific application. Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 P 908.806-9400 F 908.806.9490 www.altechcorp.com 21 Seconds Time t Minutes 109mm (4.29 in.) 69mm (2.72 in.) 109mm (4.29 in.) 69mm (2.72 in.) 109mm (4.29 in.) 69mm (2.72 in.) 45mm (1.77 in.) Earth Leakage UL 1077 ANNEX UL 1077 UL 508 UL 489 Circuit Breakers Equipment Breakers